Understanding NEC Article 225: Outside Branch Circuits and Feeders

Overview
NEC Article 225 establishes the rules for outside branch circuits and feeders operating at up to 1000 volts AC or 1500 volts DC. It governs electrical systems running between buildings, structures, or poles, and includes provisions for equipment located on exterior walls. This article ensures safety, reliability, and adherence to specific installation standards.


Scope of Article 225

This article applies to outdoor electrical conductors and their installation between buildings or structures. Typical applications include:

  • Circuits connecting detached garages, sheds, or storage units.
  • Power for outdoor systems, such as generators and solar energy installations.
  • Lighting and power for outdoor recreational or commercial spaces.

Conductor Insulation and Sizing

1. Insulation Requirements

  • Conductors extending within 10 feet of any structure must use properly insulated materials.
  • For conductors in wet locations, insulation must meet thermoplastic or thermoset material standards.

2. Conductor Sizing

  • Overhead spans:
    • Less than 50 feet: Minimum sizes are 10 AWG copper or 8 AWG aluminum.
    • Longer spans: Sizes increase to 8 AWG copper or 6 AWG aluminum, or additional support wires are required.
  • Conductors for festoon lighting must have support wires if smaller than 12 AWG.

Installation Standards

1. Approved Wiring Methods

Common methods for outdoor installations include:

  • Rigid Metal Conduit (RMC): Offers robust protection for exposed runs.
  • Electrical Metallic Tubing (EMT): Ideal for shorter, above-ground installations.
  • Underground Feeder Cables (UF Cable): For buried connections.
  • Liquidtight Flexible Metal Conduit (LFMC): Best for areas prone to water exposure.

2. Clearance Requirements

  • 10 feet: Minimum clearance above walkways or pedestrian access.
  • 18 feet: Clearance above roadways, especially where trucks operate.
  • Special allowances apply for railways and areas with high vehicle or machinery traffic.

Equipment and Safety Rules

1. Lampholders

Outdoor lampholders must be securely mounted, ensuring proper connections and avoiding accidental dislodgment.

2. Disconnecting Means

All outdoor circuits entering a building must include a disconnecting mechanism at or near the entry point. This ensures quick isolation during maintenance or emergencies.

3. Surge Protection

For sensitive applications like healthcare facilities or residential installations, surge protection devices (SPDs) are required to safeguard against voltage spikes.


Special Provisions

1. Multiple Feeders

In multifamily dwellings or large industrial campuses, additional feeders may be installed if they comply with NEC’s rules on load balancing and conductor sizing.

2. Prohibited Support

Conductors cannot be supported by trees or other vegetation. Structural or dedicated support mechanisms must be used to ensure stability and compliance.


Conclusion
NEC Article 225 serves as an essential guide for ensuring safe and compliant installation of outdoor electrical systems. By addressing conductor sizing, insulation, installation standards, and safety requirements, it helps electricians design reliable systems for various applications.

Understanding and adhering to these provisions is critical for maintaining safety and operational efficiency in outdoor electrical systems.