eep April 7, 2025 NEC 200-285 NEC Quizzes Report a question What’s wrong with this question? You cannot submit an empty report. Please add some details. 0% Article 200-285 Part10 This comprehensive quiz contains 50 questions carefully selected from the National Electrical Code (NEC) Articles spanning 200 through 285. These articles cover a broad spectrum of vital topics related to electrical installations within this section of the code. The questions in this quiz are chosen randomly to provide a thorough assessment of your knowledge across these essential NEC articles. While we strive for a diverse set of questions, some fundamental principles may be revisited in different contexts due to their relevance to multiple sections within this range. This approach ensures a robust evaluation of your understanding. We encourage you to actively participate and provide feedback. If you identify any issues or have suggestions for improving the quiz questions, please report them. Your contributions are invaluable in helping us maintain the accuracy and effectiveness of these learning resources. 1 / 37 If the ampacity of a feeder does not match a standard OCPD rating, then ____ be used. a. the next lower standard rating may b. a custom rating may c. a custom rating must d. the next higher standard rating may The National Electrical Code (NEC) mandates that the Overcurrent Protective Device (OCPD) rating for a feeder circuit must not exceed the ampacity of the feeder conductors it protects. This ensures the conductors can safely carry the current without overheating and potential fire hazards. Here's a breakdown of the relevant NEC sections: NEC Article 240 (Overcurrent Protection): This article establishes general requirements for overcurrent protection in electrical installations. NEC 240.4(B): This section specifies that the OCPD rating shall not be greater than the ampacity of the protected conductor. NEC 240.6(A) or B): These tables list standard OCPD ratings for various conductor sizes and materials. When the calculated ampacity of your feeder doesn't precisely match a standard OCPD rating, you must use the next higher standard rating. This approach guarantees adequate protection for the feeder conductors. Using a lower rating could lead to an overload situation, potentially damaging the conductors and posing a safety risk. 2 / 37 One receptacle outlet installed above each __ ft. section of show window: NEC 210.62 a. 5 b. 12 c. 10 d. 6 NEC Article 210.62 addresses receptacle outlets in show windows. It mandates that at least one 125-volt, single-phase, 15- or 20-ampere receptacle outlet be installed within 18 inches (450 mm) of the top of each show window. The spacing requirement is crucial to ensure convenient access to power for various purposes within a show window, such as lighting displays, powering temporary equipment for product demonstrations, or powering cleaning tools. By requiring outlets within 18 inches of the top and spacing them for every 12 linear feet or major fraction thereof, the NEC aims to minimize the use of extension cords, which can pose safety hazards and create a cluttered visual appearance in the show window. 3 / 37 Where do you have to use a raised cover? a. Surface mounted Boxes b. Recessed Box c. In Panels The National Electrical Code (NEC) doesn't explicitly mandate raised covers for specific locations, but it does address grounding requirements for certain box and cover combinations. Section 250.146(A) allows a listed exposed work cover (raised cover) to act as the grounding means for a device if the cover is securely fastened to the box and the cover itself is listed for grounding. However, raised covers are often used with surface-mounted boxes for several reasons: Accessibility: Raised covers provide additional clearance for bulky plugs or cords that might not fit easily into a standard box depth. This can be helpful in areas where large transformers or medical equipment might be plugged in. Protection: The extra space offered by a raised cover can provide some physical protection for the device mounted within the box. 4 / 37 There is more Volt-Amperes for duplex receptacles for HVAC equipment. a. True b. False The statement is generally False (Correct). Standard duplex receptacles are typically sufficient for HVAC equipment. Here's why: Volt-Amperes (VA): VA is a unit that represents the apparent power, accounting for both voltage and current. While important for electrical system design, it's not the only factor to consider for receptacle selection in this scenario. HVAC Equipment Power Consumption: Residential HVAC equipment (furnaces, air conditioners) generally operates on 120V or 240V circuits. Their power consumption can vary depending on size and type, but it usually falls within the range that standard 15A or 20A duplex receptacles can handle (1800 VA or 3600 VA, respectively). Standard Duplex Receptacles: Most homes use standard 15A or 20A, 125V duplex receptacles for various appliances. These receptacles are designed to handle the typical loads from these appliances, including most residential HVAC equipment. However, there are some exceptions to consider: Large HVAC Systems: In rare cases, very large or industrial HVAC systems might require higher voltage (e.g., 480V) and higher amperage circuits. These would necessitate specialized receptacles beyond the scope of standard duplex outlets. 5 / 37 A 3000 square foot store has 30 ft of show window. There are a total of 80 duplex receptacles. The serviceis 120/240 V, single-phase 3-wire service. The actual connected lighting load is 8,500 VA. Calculate the minimum size overcurrent protection for the service. a. 225-amperes b. 125-amperes c. 200-amperes d. 150-amperes NEC References: Article 220 – Branch Circuit and Feeder Calculations Table 220.12 – Branch Circuit Requirements Following the NEC guidelines for service calculations: Continuous Loads: The show window lighting (30 ft) needs to be considered at 100% of its VA rating. Look up the NEC table (likely Table 220.43) for show window lighting VA per linear foot. Multiply this value by the length of the show window (30 ft) to get the total VA for continuous load. Non-continuous Loads: The general lighting (8,500 VA) and receptacles (80 duplex) are non-continuous loads. Apply the appropriate demand factors from NEC Table 220.12 to these loads to determine their contributing VA to the service ampacity calculation. Service Ampacity: Sum the VA values from continuous and non-continuous loads. Apply a diversity factor (if applicable) and then divide by the single-phase voltage (120/240V) to get the minimum service ampacity in amperes. By following these steps and referring to the relevant NEC tables, you can determine the minimum size overcurrent protection for the service. 6 / 37 What is the minimum size equipment grounding conductor for grounding raceway and equipment for a 60 ampere circuit breaker. a. 8 AWG b. 12 AWG c. 14 AWG d. 10 AWG According to the National Electrical Code (NEC) Table 250.122, the minimum size for an equipment grounding conductor (EGC) for a circuit with a rating or setting of not more than 60 amps is 10 AWG copper. Reference: NEC Table 250.122 7 / 37 What does the letter T stand for in THHN? a. Thick b. Thermoset c. Thin d. Thermoplastic The letter "T" in THHN stands for Thermoplastic. Thermoplastic is a type of plastic that softens and melts when heated. This property is desirable for building wire insulation because it allows for easier installation and termination of the wires, especially when heat is applied with soldering tools or heat shrink tubing. THHN wire is a common type of building wire with additional letters indicating specific properties: H: Indicates the wire is rated for use in wet locations. HH: Indicates the wire is rated for even higher temperatures than standard THHN. N: Indicates a nylon jacket for added protection against abrasion and chemicals. 8 / 37 A separate insulated isolated equipment grounding conductors is sized according to NEC Table _______. a. 250.146 b. 250.110 c. 250.146(D) d. 250.122 The National Electrical Code (NEC) table that specifies the sizing of separate insulated isolated equipment grounding conductors is Table 250.122. This table outlines the minimum conductor size requirements for grounding raceways and equipment based on the ampere rating or setting of the overcurrent protective device for the circuit. Here's why Table 250.122 applies: Separate Insulated Isolated: This indicates a dedicated conductor specifically for grounding purposes, with insulation to prevent accidental contact with energized conductors. Equipment Grounding: This refers to the conductor that grounds non-current-carrying metal parts of electrical equipment. Sizing based on Overcurrent Protection: The size of the grounding conductor needs to be sufficient to carry any potential fault current that could flow through it in case of a ground fault. Therefore, Table 250.122 provides the necessary correlation between circuit protection and the minimum size required for the equipment grounding conductor. 9 / 37 Equipment grounding conductor connections to isolated ground receptacles are covered in _____. a. 250.148 b. 210.12(A) c. 230.52 d. 250.146(D) The National Electrical Code (NEC) covers equipment grounding conductor connections to isolated ground receptacles in section 250.146(D). This section outlines specific requirements for ensuring proper grounding and preventing potential hazards when using isolated grounding. 10 / 37 An isolated ground conductors are permitted to pass though panelboards without being connected to the panelboards grounding terminal bar. a. True b. False According to the National Electrical Code (NEC) Section 250.146(A), isolated grounding conductors shall not be connected to equipment grounding conductors or to other grounding conductors within the panelboard. Isolated ground conductors are used in specific applications, such as grounding sensitive electronic equipment, and connecting them to the panelboard's grounding terminal bar would defeat their intended isolation. Here's the relevant NEC excerpt: 250.146(A) Isolated Grounding Conductors. Isolated grounding conductors shall not be connected to equipment grounding conductors or to other grounding conductors within the panelboard. 11 / 37 In the first phase of the installation of a telephone system in a commercial building, the ____ will install an empty conduit system according to specifications for the commercial building and in the locations indicated on the working drawings. a. electrical contractor b. leasing agent c. city government d. telephone company The National Electrical Code (NEC) outlines regulations for safe electrical installations in buildings. For commercial buildings, NEC Article 800 covers specific requirements. Telephone systems, while considered low-voltage systems, often utilize electrical wiring for power and potentially require grounding. Therefore, their installation needs to comply with electrical codes. NEC mandates that electrical raceways, such as conduits, be installed by qualified electrical workers [NEC 110.3(B)]. These raceways will house electrical conductors for the phone system and ensure their protection. Since electrical contractors are licensed to handle electrical installations, they are the qualified professionals to install the empty conduit system according to building specifications and drawings. 12 / 37 Where in the code book can you find the volt-amperes per square foot? a. 102.12 b. 202.12 c. 220.12 d. 120.12 The National Electrical Code (NEC) provides guidelines for electrical installations. While it doesn't have a single section solely dedicated to volt-amperes per square foot, Article 220 covers branch circuits and feeders, which are directly related to electrical loads. Within Article 220, Section 220.12 focuses on lighting loads and specifies unit loads in volt-amperes per square foot for various occupancies. Table 220.12 contains these specific values. 13 / 37 Equipment grounding conductors and isolated equipment grounding conductors are the same thing. a. False b. True The National Electrical Code (NEC) clearly defines two separate conductors: Equipment Grounding Conductor (EGC): This conductor provides a low-impedance path for fault current to return to the source in case of a ground fault. It connects the non-current-carrying metal parts of electrical equipment to the grounded conductor (which is ultimately connected to earth). See NEC Section 250 [NEC 250]. Isolated Grounding Conductor: This term is not used in the NEC. Grounding systems must be connected to earth for safety reasons. There may be specific applications where a separate insulated conductor is used for sensitive equipment, but this conductor would still need to be bonded to the grounding system at some point. Therefore, equipment grounding conductors and isolated equipment grounding conductors are not the same. 14 / 37 The load to be included for general-purpose convenience receptacles is ___________ VA. a. 90 b. 360 c. 270 d. 180 The National Electrical Code (NEC) Article 220.14(I) specifies the load for convenience receptacle outlets in commercial locations. This article states that a value of 180 volt-amperes (VA) be used for each single or multiple receptacle on a yoke (basically, each outlet or a set of outlets mounted together). 15 / 37 The receptacle is required to be at the same level as the HVAC equipment and within 25 feet of the equipment. a. False b. True The statement is True (Correct). The NEC requires a service receptacle for servicing heating, air-conditioning, and refrigeration equipment according to Section 210.63: Article/Section: 210.63 – Receptacle Outlets for Heating, Air-Conditioning, and Refrigeration Equipment Requirement: A 125-volt, single-phase, 15- or 20-ampere rated receptacle outlet shall be installed at an accessible location for servicing heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 7.5 meters (25 feet) of the equipment. The NEC mandates this provision to ensure safe and convenient access to power for servicing technicians. Having a receptacle readily available at the same level and within close proximity to the HVAC equipment eliminates the need for extension cords, which can pose safety hazards like tripping or overloading circuits. 16 / 37 The use of an isolated equipment grounding conductor does not relieve the requirement for connecting the raceway system and outlet box to an equipment grounding conductor a. False b. True According to NEC Article 250.110(A), all raceways, metallic cable trays, metal enclosures for equipment, and other metallic parts of the electrical installation that are not intentionally grounded must be connected to the grounding electrode system by an equipment grounding conductor. An isolated equipment grounding conductor, as defined in NEC Article 400.3(A), is permitted to be used in certain situations with separately derived systems. However, its purpose is to ground the electrical system itself, not the raceway system. Therefore, even when using an isolated equipment grounding conductor, the raceway system and outlet boxes still require connection to a separate equipment grounding conductor for proper grounding path as per NEC 250.110(A). 17 / 37 Type S fuse-holders and adaptors shall be ________________ so that either the fuse-holder itself or the fuse-holder with a Type S adaptor inserted cannot be used for any fuse other than a Type S fuse. a. labeled b. installed c. designed d. registered The National Electrical Code (NEC) Section 240.53(A) requires Type S fuseholders and adapters to be designed to prevent the use of any fuse other than a Type S fuse. This design feature ensures safety by: Standardization: Type S fuses and adapters have specific physical dimensions and keying features that prevent them from being used interchangeably with other fuse types. Tamper Resistance: The design makes it difficult to remove a Type S fuse or insert a different type of fuse, even with tools. Amp Rating Limitation: Type S adapters are limited in amperage rating, further preventing the use of an oversized fuse. 18 / 37 The demand load for a dryer in a single-family dwelling unit, rate at 6,000 VA is ________________. a. 4,200 VA b. 3,000 VA c. 6,000 VA d. 10,200 VA According to NEC Section 220.54(E)(1), for a single dryer in a dwelling unit, the demand load is not less than the nameplate rating. This means the actual electrical rating of the dryer, in this case 6,000 VA, is considered the demand load. 19 / 37 Indicate the general lighting unit load that would be included in the branch-circuit calculations as set forth in NEC Table 220.12 for a: Restaurant: _____ VA/ft2“>2 a. 1.2 b. 1.5 c. 3.0 d. 0.3 The National Electrical Code (NEC) Table 220.12 specifies the minimum lighting load in volt-amperes per square foot (VA/ft²) for various occupancies, including restaurants. This table helps electricians determine the appropriate branch circuit size to handle the expected lighting load. According to NEC Section 220.12(A), a unit load of not less than that specified in Table 220.12 shall be used to calculate the minimum lighting load for non-dwelling occupancies. Table 220.12 lists "Restaurants" with a unit load of 1.2 VA/ft². 20 / 37 Indicate the general lighting unit load that would be included in the branch-circuit calculations as set forth in NEC Table 220.12 for a: Schoolroom: _____ VA/ft2“>2. a. 3.0 b. 0.3 c. 1.2 d. 1.5 The NEC sets the general lighting unit load for schools in Article 220.12: [invalid URL removed] – Branch-Circuit Requirements. Specifically, refer to Table 220.12(A): [invalid URL removed] – Occupancies. This table assigns a unit load of 1.2 VA/ft² for schools. 21 / 37 Noncontinuous loads are calculated for 125% of the load. a. False b. True The statement is False. Noncontinuous loads are generally not calculated for 125% of their actual load. They are typically sized based on their nameplate rating (actual load). However, it's continuous loads that are subject to a 125% sizing requirement according to the National Electrical Code (NEC). NEC Reference: Article 210.20(A)(1) Explanation based on NEC: NEC Article 210.20(A)(1) states that the rating of a branch circuit supplying continuous loads must not be less than the sum of the noncontinuous load plus 125% of the continuous load. This means: Noncontinuous load: Rated for its actual load (100%) Continuous load: Rated for 125% of its actual load The reason for the 125% derating for continuous loads is because they draw current for extended periods, which can cause increased heating in the conductors. This derating provides a safety factor to account for the additional heat generated by continuous operation. 22 / 37 To determine a reasonable minimum size for a neutral conductor, two types of loads must be considered—____. a. motors and hermetic units b. linear and nonlinear c. series and parallel d. fuses and circuit breakers The National Electrical Code (NEC) specifies requirements for determining the minimum size of a neutral conductor in a circuit. According to NEC Article 220, Branch Circuit Requirements, neutral conductor sizing is influenced by the type of load connected to the circuit. Table 220.6 of the NEC provides guidance on selecting the appropriate neutral conductor size based on the calculated neutral load. This table considers two main load types: Linear loads: These loads draw current that is proportional to the applied voltage. Examples include incandescent lighting, resistive heaters, and electric ovens. Non-linear loads: These loads draw current that is not proportional to the applied voltage and can introduce harmonics into the current waveform. Examples include electronic devices, computers, and many types of LED lighting. The presence of non-linear loads can cause current to flow in the neutral conductor even when the circuit is balanced between the phase conductors. Table 220.6 takes this into account when specifying the required neutral conductor size based on the percentage of non-linear load in the circuit. 23 / 37 Permission is given in NEC 250.146(D) to install a separate green insulated equipment grounding conductor from the green hexagonal screw on the receptacle all the way back to the main service disconnect or the source of a separately derived system. a. True b. False NEC section 250.146(D) allows the use of isolated ground receptacles to address electromagnetic interference (EMI) concerns. These receptacles have a grounding terminal that's intentionally insulated from the mounting frame. To maintain a separate grounding path and minimize EMI issues, NEC permits running a dedicated insulated equipment grounding conductor with the circuit conductors. This isolated grounding conductor connects the receptacle's grounding terminal directly to the grounding point of the derived system or service, bypassing connections to panel grounding bars along the way (refer to NEC section 408.40 Exception). Key Points: Isolated ground receptacles have an insulated grounding terminal. A separate insulated equipment grounding conductor is used. This conductor connects directly to the service or derived system grounding point. 24 / 37 Minimum size equipment grounding conductor for a 60 ampere branch circuit is ______ AWG. a. 10 b. 14 c. 12 d. 8 The National Electrical Code (NEC) dictates the minimum size requirements for equipment grounding conductors (EGCs) in Article 250.122. This table specifies the EGC size based on the rating or setting of the overcurrent device protecting the circuit. For a 60-ampere branch circuit, referring to NEC 250.122, you'll find that the minimum size for the EGC is: 10 AWG 25 / 37 Indicate the general lighting unit load that would be included in the branch-circuit calculations as set forth in NEC Table 220.12 for a: Corridor in a school: _____ VA/ft2“>2. a. 0.3 b. 1.2 c. 1.5 d. 3.0 The National Electrical Code (NEC) Table 220.12 specifies general lighting unit load values for different occupancies. These values are used in branch-circuit calculations to determine the minimum circuit capacity required to supply the expected lighting load. For corridors in schools, NEC Table 220.12 assigns a general lighting unit load of 3.0 VA/ft². 26 / 37 The unit load for a Library when calculating out a lighting load is ______VA/ft2“>2 a. 0.3 b. 1.3 c. 1.4 d. 1.5 According to Table 220.12(A) of the 2023 National Electrical Code (NEC), the unit load for Libraries is 1.5 volt-amperes per square foot (VA/ft²). This value represents the minimum recommended VA required to power the lighting in a library space per square foot of area. 27 / 37 Isolated ground receptacles installed in nonmetallic boxes shall be covered with either a metal or nonmetallic faceplate. a. False b. True The National Electrical Code (NEC) covers grounding requirements in Article 250. Pay close attention to the grounding path for isolated ground receptacles, which differs from standard outlets. Standard Receptacles: The grounding prong of a plug connects to the metal outlet box through the mounting strap, establishing a grounding path. Isolated Ground Receptacles: These outlets have an isolated ground terminal that is not connected to the mounting strap. Instead, it requires a separate insulated grounding conductor. Since a nonmetallic box doesn't inherently provide a grounding path, using a metal faceplate with an isolated ground receptacle becomes crucial for proper grounding. Here's the relevant NEC section for reference: NEC Section 250.146(D): Isolated grounding conductors shall be permitted to be used for grounding susceptible electronic equipment. Note: This section allows isolated grounding, but it doesn't address faceplate material. NEC grounding requirements focus on the grounding path, which is why a metal faceplate is necessary with a nonmetallic box. 28 / 37 The load to be included for an outlet for a specific appliance or load is ________ a. 360 VA b. The ampere rating of the appliance or load served c. the average ampere rating of all appliances together d. 180 VA The National Electrical Code (NEC) in Article 220.14(A) specifies that the load for an outlet serving a dedicated appliance or other load not covered in specific sections (220.14(B) through (L)) must be calculated based on the appliance's or load's ampere rating. In simpler terms, the outlet needs to be sized to handle the maximum current draw of the appliance it's designed to power. This ensures safe operation and prevents overloading the circuit. 29 / 37 What is the calculated service load for a 1500 square feet dwelling with the following: two 20-A small appliance circuits 20-A laundry circuit two 4-kW wall-mounted ovens 5.1-kW counter-mounted cooking unit 4.5-kW water heater, a 1.2 kW dishwasher 5-kW clothes washer and dryer six 7-A, 230-V room air-conditioning units 1.5-KW permanently installed bathroom space heater a. 155-amperes b. 122-amperes c. 115- amperes d. 162.-amperes The NEC provides a standard method for calculating the service load for dwelling units in Section 220. The key factors to consider for this specific scenario are: General Lighting and Appliance Load: NEC Table 220.14(B) assigns a base value for this category based on dwelling area. For a 1500 sq.ft. dwelling, this value is typically 10,000 VA. Two 20-A Small Appliance Circuits: NEC requires a minimum of two 20-amp circuits for small appliances in kitchens. These are sized at 1500 VA each (20 amps x 125 volts). 20-A Laundry Circuit: A dedicated 20-amp circuit for laundry is also mandated by NEC, sized at 1500 VA. Non-continuous Loads: Major Appliances: Two 4-kW wall-mounted ovens (4 kW each) 5.1-kW counter-mounted cooking unit Clothes dryer (assume same rating as washer, 5 kW) From NEC Table 430.22(B)(1), the largest of these loads is used (either the ovens at 8 kW or the cooktop/dryer at 5.1 kW). Other Loads: Water heater (4.5 kW) Dishwasher (1.2 kW) Bathroom heater (1.5 kW) Room air conditioners (six units at 7 amps x 230 volts each) – Calculate the total VA for these units. Applying NEC Demand Factors: NEC allows reducing the calculated load based on the assumption that not all appliances will operate simultaneously. Refer to Table 220.42 for the applicable demand factors. By following these steps and applying the appropriate NEC tables and demand factors, you can calculate the total service load for the dwelling. 30 / 37 An isolated ground conductor is connected with the rest of the grounding conductors in a box a. False b. True No, an isolated ground conductor should not be connected to the rest of the grounding conductors in a box. The National Electrical Code (NEC) distinguishes between two types of grounding conductors: Equipment grounding conductor (EGC): This conductor provides a path for fault current to return to the source. It is connected to all electrical equipment enclosures and metallic raceways. Isolated grounding conductor (IGC): This conductor is used in specific applications, such as grounding sensitive electronic equipment. It is isolated from the building's grounding system to minimize electrical noise and ground loops. NEC Section 250.146(A) specifically prohibits the connection of an isolated grounding conductor to the EGC or other grounding conductors: "The isolated grounding conductor grounding path shall not be connected to building steel, structural steel, lightning protection system grounding conductors, grounding electrodes as defined in Art. 250, or to any other grounding conductor or raceway." 31 / 37 Volt-Amperes for sign outlets are _____. a. 1200 b. 1000 c. 2000 d. 1800 The correct answer is 1200 VA. This minimum requirement is established in the National Electrical Code (NEC) under Article 220.14(F). It states that: "Sign and outline lighting outlets shall be calculated at a minimum of 1200 volt-amperes for each required branch circuit specified in 600.5(A)." This means that when designing a branch circuit specifically for signs or outline lighting, the circuit needs to be sized to handle a minimum load of 1200 VA. This ensures adequate capacity for powering various signs without overloading the circuit. 32 / 37 If a lighting load is considered to be continuous, as is the case in commercial buildings, a load factor of ____ percent must be applied. a. 120 b. 125 c. 100 d. 150 The National Electrical Code (NEC) specifies requirements for sizing electrical conductors and overcurrent protection devices (OCPDs) like circuit breakers. These requirements consider factors like the type of load (continuous vs. non-continuous) and its potential demand. Continuous Load: A load that operates for long periods or for expected durations [NEC 100]. Lighting in commercial buildings is a typical example. Demand Factor: A value that adjusts the connected load to account for the likelihood that all devices won't operate simultaneously at full capacity [NEC 300.5(b)]. For continuous loads like commercial lighting, NEC Article 210.20(A) requires applying a 125% load factor when determining the circuit rating and overcurrent protection. This ensures the circuit and breaker can handle potential surges or unexpected full operation of all lights. 33 / 37 When doing calculations for branch circuits, calculations shall be permitted to be rounded to the nearest whole ampere, with decimal fractions smaller than _____ dropped. a. 0.5 b. 0.4 c. 0.7 d. 0.2 The National Electrical Code (NEC) in section 220.5(B) permits rounding calculations for branch circuit loads to the nearest whole ampere. This simplifies electrical design and installation while maintaining safety standards. When a calculation results in a decimal fraction, it's rounded as follows: Decimals less than 0.5 are dropped. Decimals greater than or equal to 0.5 are rounded up to the nearest whole number. 34 / 37 The ground fault protection system shall operate to cause the service disconnect to open all ungrounded conductors of the fault circuit. The maximum setting of the ground-fault protection shall be____________________ amperes, and the maximum time delay shall be one second for ground-fault currents equal to or greater than _________________________ amperes. a. 1,000 / 1,200 b. 1,000 / 800 c. 1,200 / 3,000 d. 800 / 1,000 The National Electrical Code (NEC) Article 230.95 specifies requirements for ground-fault protection of equipment. This system safeguards electrical equipment on solidly grounded wye systems exceeding 150 volts to ground but not exceeding 600 volts phase-to-phase. The NEC mandates two key aspects of ground-fault protection: Maximum Setting: This value determines the minimum level of ground fault current that will trigger the system to disconnect the circuit. A lower setting offers more sensitive protection but might lead to unnecessary tripping for minor faults. Maximum Time Delay: This defines the allowable time for the system to disconnect the circuit after detecting a ground fault exceeding a specific current threshold. A shorter time delay provides faster response to high-level faults but might not give enough time for larger circuit breakers to trip. The NEC sets the maximum setting for ground-fault protection at 1,200 amperes. This ensures the system can detect even relatively low ground faults that could damage equipment over time. For ground-fault currents exceeding 3,000 amperes, the NEC allows a maximum time delay of one second. This enables the system to differentiate between smaller faults and larger ones that might require the intervention of upstream protective devices like fuses or higher-rated circuit breakers. 35 / 37 Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates. a. True b. False The NEC in Article 210.4(B) requires that all ungrounded conductors in a multiwire branch circuit be simultaneously disconnected at the point of origin. This is typically achieved by using: A double-pole circuit breaker: This breaker has a single handle that controls both hot conductors, ensuring both are switched off together. Two single-pole circuit breakers with an identified handle tie: These breakers have individual handles, but a connecting mechanism ensures they trip together, effectively disconnecting both hot conductors simultaneously. 36 / 37 The code makes it very clear that the white conductor can be used as a return conductor from the switch to the switched outlet. a. False b. True The National Electrical Code (NEC) Section 200.7(A) states that white or gray conductors, or conductors with three continuous white or gray stripes on other than green insulation, shall only be used as a grounded conductor unless specifically permitted for other uses in sections 200.7(B) or (C). One exception in NEC 200.7(C) allows a white conductor to be used as an ungrounded conductor for supplying power to a switch in single-pole, 3-way, or 4-way switch loops. However, in this case, the white conductor cannot be used as the return conductor from the switch to the outlet. Therefore, using a white conductor as a return conductor from the switch to the outlet violates the NEC. 37 / 37 Indicate the general lighting unit load that would be included in the branch-circuit calculations as set forth in NEC Table 220.12 for a: A hallway in a dwelling: _____ VA/ft2“>2. a. 3.0 b. 1.2 c. 1.5 d. 0.3 The National Electrical Code (NEC) provides unit load values for calculating minimum lighting loads in various occupancies. However, there's a distinction between dwelling units and non-dwelling spaces. NEC Table 220.12: This table specifies unit loads for various non-dwelling occupancies like restaurants, schools, and corridors in schools. NEC Table 210.8(A): This table defines unit loads specifically for dwelling units. Dwellings include single-family homes and individual units within multi-family residences. Hallways in dwellings fall under this category. Therefore, to determine the general lighting unit load for a hallway in a dwelling, we should refer to NEC Table 210.8(A), not NEC Table 220.12 Your score is LinkedIn Facebook Twitter 0% Restart quiz Exit Rate & Review Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services. Send feedback Leave a Reply Cancel replyYour email address will not be published. Required fields are marked * Comment* Name* Email* Website Save my name, email, and website in this browser for the next time I comment. Post Comment