eep April 7, 2025 NEC 300-399 NEC Quizzes Report a question What’s wrong with this question? You cannot submit an empty report. Please add some details. 0% Article 300-399 Part07 This comprehensive quiz contains 50 questions carefully selected from the National Electrical Code (NEC) Articles spanning 300 through 399. This section of the NEC addresses crucial aspects of wiring methods, materials, and general requirements for electrical installations within this portion of the code. The questions in this quiz are chosen randomly to provide a thorough assessment of your knowledge across these essential NEC articles. While we strive for a diverse set of questions, some fundamental principles may be revisited in different contexts due to their relevance to multiple sections within this range. This approach ensures a robust evaluation of your understanding. We encourage you to actively participate and provide feedback. If you identify any issues or have suggestions for improving the quiz questions, please report them. Your contributions are invaluable in helping us maintain the accuracy and effectiveness of these learning resources. Emerging conductors require physical protection. 1 / 50 What protection is required for conductors emerging from the ground per 305.15(C)? a. They must be enclosed in a listed raceway from the minimum cover depth to 8 feet above grade. b. Protective coatings must be applied to the conductors. c. No protection is required for direct burial cables. d. They must be wrapped with a moisture-resistant barrier. Incorrect. Conductors require raceway protection when transitioning above ground. Correct! Raceways provide necessary mechanical protection for emerging conductors. Conductors emerging from the ground must be enclosed in a raceway extending from the burial depth to 8 feet above grade for protection against mechanical damage. Moisture control is essential in underground installations. 2 / 50 When are raceways required to be sealed per 300.5(G)? a. When moisture may enter the raceway and contact live parts. b. Only in hazardous locations. c. Sealing is optional for spare raceways. d. When moisture may enter the raceway and contact live parts. Incorrect. Moisture-prone raceways must be sealed. Correct! Sealing is crucial for moisture-prone installations. Sealing prevents moisture or gases from entering raceways and contacting live parts, ensuring safety and reliability. The splice must ensure both mechanical strength and continuity of the circuit. 3 / 50 When concealed knob-and-tube wiring is spliced, _______________ or strain splices are permitted to be used. a. Constructed b. Separated c. In-line d. Soldered The selected option does not align with NEC requirements for splicing concealed knob-and-tube wiring. Correct! For concealed knob-and-tube wiring, in-line splices or strain splices are permitted, as specified in NEC Article 394.56(A). According to NEC Article 394.56(A), when splicing concealed knob-and-tube wiring, in-line splices or strain splices are permitted. These methods ensure the splices are mechanically secure and electrically continuous. The allowable number of conductors is determined by the box size and conductor size, factoring in space taken by devices, grounding conductors, and clamps. 4 / 50 A 4×2 1/8″ metal square box shall be allowed to have _______________ 12 AWG conductors. a. 10 b. 9 c. 12 d. 13 The selected number of conductors does not comply with NEC Table 314.16(A) for a 4×2 1/8″ box. Correct! A 4×2 1/8″ metal square box can hold up to 13 conductors of 12 AWG, as specified in NEC Table 314.16(A). According to NEC Table 314.16(A), a 4×2 1/8″ metal square box has a capacity of 21 cubic inches. Each 12 AWG conductor requires 2.25 cubic inches of space. Number of Conductors=Box VolumeConductor Volume=212.25≈13\text{Number of Conductors} = \frac{\text{Box Volume}}{\text{Conductor Volume}} = \frac{21}{2.25} \approx 13Number of Conductors=Conductor VolumeBox Volume=2.2521≈13 Therefore, the box can accommodate up to 13 conductors of 12 AWG. Article 310 addresses requirements for general wiring conductors. 5 / 50 1. What is the scope of Article 310? a. Grounding requirements for conductors in raceways. b. Voltage drop calculations for branch circuits. c. Installation methods for medium-voltage conductors. d. General requirements for conductors rated up to and including 2000 volts. Incorrect. This article focuses on conductors rated 2000 volts or less, not grounding or medium voltage. Correct! Article 310 addresses conductors up to 2000 volts. Article 310 provides rules for the type designations, ampacity ratings, and uses of conductors up to 2000 volts. Think about the physical equipment mentioned. 6 / 50 What is the scope of Article 312? a. Covers installation and construction specifications for cabinets, cutout boxes, and meter socket enclosures. b. Provides grounding requirements for electrical cabinets. c. Details requirements for overcurrent protection in high-voltage systems. d. Focuses on voltage drop calculations in feeder circuits. Incorrect. Article 312 is about physical specifications for cabinets and enclosures. Correct! This article covers specifications for these enclosures. Article 312 specifies how to construct and install cabinets, cutout boxes, and meter socket enclosures for electrical systems. The NEC specifies the alloy series for stranded aluminum conductors. 7 / 50 What material is required for stranded aluminum conductors (310.3(B)(2))? a. Any electrical-grade aluminum. b. Copper-clad aluminum with a minimum of 5% copper. c. Solid aluminum only. d. AA-8000 series electrical-grade aluminum alloy. Incorrect. Only AA-8000 series aluminum alloy is acceptable for stranded conductors Correct! The AA-8000 series alloy is required for stranded aluminum conductors. The AA-8000 series aluminum alloy is required for stranded aluminum conductors, ensuring safety and reliability. Airflow ducts require specialized wiring methods 8 / 50 What is required for electrical systems passing through ducts used for airflow per 300.22(B)? a. Insulation with a high-temperature rating is sufficient. b. They must use sealed conduit c. Only wiring methods listed for use in ducts are permitted. d. Airflow ducts cannot contain electrical systems. Incorrect. Wiring in airflow ducts must follow specific listing requirements. Correct! Only approved methods are allowed in airflow ducts. Only listed wiring methods designed for use in ducts are permitted to ensure fire safety and prevent contamination. Conductors with different voltage ratings need careful segregation. 9 / 50 How should conductors of different systems be separated per 305.4? a. Separation is only required for conductors over 2000 volts. b. They must be run in parallel raceways for safety. c. How should conductors of different systems be separated per 305.4? d. No separation is necessary if the conductors are insulated. Incorrect. Separation is required unless exceptions are met. Correct! Conductors of different systems must be properly separated or insulated Conductors of different systems must not share enclosures or raceways unless exceptions such as permanent physical separation or appropriate insulation apply. Termination temperature ratings dictate conductor usage. 10 / 50 What is the temperature limitation for conductors used with terminations rated 60°C per 310.14(A)(3)? a. rated 60°C per 310.14(A)(3)? b. No specific limitation applies. c. 75°C for copper conductors only. d. 60°C maximum for conductors used with these terminations. Incorrect. Conductors must match the temperature limitation of the terminations. Correct! Conductors must not exceed the termination’s temperature rating. Conductors must not exceed the temperature rating of the termination, which is 60°C for terminations rated as such. Wet locations require specific considerations for wiring. 11 / 50 What is required for raceways installed in wet locations above grade as per 305.8? a. No additional requirements are necessary. b. They must be buried at least 6 inches deep. c. They must be lined with a moisture barrier. d. No additional requirements are necessary. Incorrect. The interior of such raceways is considered a wet location by default Correct! Raceway interiors are treated as wet locations to ensure safety. The interior of raceways in wet locations above grade is classified as a wet location, so all conductors and cables must be listed for use in wet locations. Refer to the NEC ampacity tables for correction factors. 12 / 50 What ampacity correction factors apply for conductors in an ambient temperature of 40°C (104°F) (310.15(B)(1))? a. 0.91 for 75°C conductors. b. 1.00 for all conductor types. c. Correction factors do not apply for 40°C. d. 0.82 for 90°C conductors. Incorrect. Review the correction factor for 75°C conductors at 40°C ambient temperature. Correct! The ampacity correction factor is 0.91 for 75°C conductors at 40°C. For 75°C conductors at 40°C, a correction factor of 0.91 is applied to reduce ampacity Steel plates provide robust protection against nails or screws. 13 / 50 What material is required for protecting cables in notches of wood members per 300.4(A)(2)? a. No protection is required for wood applications. b. Steel plates or bushings at least 1.6 mm thick. c. Aluminum plates with reflective surfaces. d. Plastic inserts only. Incorrect. Steel plates or equivalent are required for protection. Correct! Steel plates ensure cables are shielded from damage. Steel plates or bushings of at least 1.6 mm thickness must protect cables in wood notches to prevent mechanical damage. The NEC allows specific fittings to be used instead of boxes under certain conditions to protect conductors. 14 / 50 A(n) _______________ shall be permitted to be used in lieu of a box at the end of a rigid metal conduit where the raceway terminates at unenclosed controls or motors. a. Coupling b. Elbow c. Bushing d. Connector The selected option does not meet NEC requirements for terminations at the end of rigid metal conduit. Correct! A bushing is allowed in lieu of a box at the end of a rigid metal conduit where the raceway terminates at unenclosed controls or motors, as specified in NEC Article 300.15(C). According to NEC Article 300.15(C), a bushing is permitted to be used in lieu of a box at the end of a rigid metal conduit when the conduit terminates at unenclosed controls or motors. This provides mechanical protection for the conductors while ensuring a safe and secure termination. Penetrations must prevent the spread of fire or combustion products. 15 / 50 What is required for electrical penetrations in fire-rated walls per 300.21? a. Firestopping methods approved to maintain the fire-resistance rating. b. Metallic bushings or seals. c. No special requirements for metallic conduits. d. Non-combustible insulation. Incorrect. Fire-rated walls require approved firestopping methods. Correct! Approved firestopping methods ensure safety in fire-rated assemblies Firestopping methods maintain the fire-resistance rating of walls, floors, and ceilings penetrated by electrical installations. Protection ensures durability in exposed areas. 16 / 50 How are conductors protected where exposed to physical damage per 300.5(D)? a. They must be painted for visibility. b. Use nonmetallic sheathing. c. They must be painted for visibility. d. Install at least 36 inches above ground level. Incorrect. Exposed conductors require raceway or armor for protection. Correct! Raceway or armored cable prevents physical damage to conductors. Conductors exposed to physical damage must be enclosed in a raceway or armored cable for mechanical protection. Check for a specific multiplier for nonshielded conductors. 17 / 50 What is the minimum bending radius for nonshielded conductors as specified in 305.5? a. specified in 305.5? b. 12 times the conductor diameter for all installations. c. 10 times the overall diameter of the conductor. d. No minimum bending radius is specified. Incorrect. The bending radius for nonshielded conductors is 8 times the diameter. Correct! Nonshielded conductors must adhere to this minimum bending radius. Nonshielded conductors must be bent to a radius not less than 8 times their overall diameter to prevent damage during installation. Wet locations require specific moisture-resistant types. 18 / 50 What insulation types are permitted for use in wet locations (310.10(C))? a. Types suitable for dry and damp locations. b. Moisture-impervious metal-sheathed or other listed types. c. Only types THHN and XHHN. d. No conductors are allowed in wet locations. Incorrect. Only conductors listed for wet locations are permitted Correct! Only moisture-resistant conductors are allowed in wet locations. Conductors must be moisture-impervious or listed for wet locations, such as THWN, THWN-2, or XHHW. Each component in the box contributes to the total cubic inch capacity based on the NEC’s volume allowances. 19 / 50 The cubic inch capacity required for a device box containing (1) duplex receptacle, (2) cable clamps, and (2) 12 AWG NM cables is _______________. a. 16 cu-in b. 15.75 cu-in c. 18 cu-in d. 13.5 cu-in The selected value does not match the NEC box fill calculation for this configuration. Correct! The cubic inch capacity required for the device box is 18 cu-in, as calculated using NEC Article 314.16(B). The total cubic inch capacity required for this configuration is 18 cu-in, ensuring adequate space for the conductors, clamps, and duplex receptacle. FMC is primarily intended for above-ground installations and is not suitable for certain environments. 20 / 50 FMC (Flexible Metal Conduit) shall not be used _______________. a. In dry locations b. Within 6 ft of the outside edge of a water source c. Underground d. In dwelling unit attic The selected option is not a restriction for the use of FMC according to NEC requirements. Correct! FMC shall not be used underground, as specified in NEC Article 348.12. According to NEC Article 348.12, FMC (Flexible Metal Conduit) is not permitted for use underground. FMC is designed for above-ground installations where flexibility is required, and it does not provide the necessary protection against moisture or mechanical damage in underground environments. Voltage limits are defined unless exceptions apply. 21 / 50 What is the voltage limitation for wiring methods per 300.2(A)? a. 1000 volts AC or 1500 volts DC nominal unless specified otherwise. b. Always less than 600 volts. c. Unlimited for industrial systems. d. Limited to low-voltage systems only. Incorrect. Voltage limits for wiring methods are clearly defined as 1000 volts AC or 1500 volts DC nominal. Correct! Wiring methods apply to these voltage limits unless otherwise specified. Wiring methods are designed for 1000 volts AC or 1500 volts DC nominal or less unless specifically allowed for higher voltages. These cables are commonly used in residential settings where they are protected from moisture and physical damage. 22 / 50 Type NM, Type NMC, and Type NMS cables shall be permitted to be used in _______________. a. Commercial kitchens b. One-family dwelling units c. Storage battery rooms d. Truck refueling stations The selected location does not comply with NEC requirements for the use of Type NM, Type NMC, and Type NMS cables. Correct! Type NM, Type NMC, and Type NMS cables are permitted for use in one-family dwelling units, as specified in NEC Article 334.10(A). According to NEC Article 334.10(A), Type NM (non-metallic sheathed), Type NMC (non-metallic sheathed with corrosion-resistant jacket), and Type NMS cables are permitted to be used in one-family, two-family, and multi-family dwelling units where they are not subject to physical damage. They are not suitable for locations like commercial kitchens, refueling stations, or storage battery rooms due to exposure to heat, moisture, or corrosive environments. To determine the minimum size auxiliary gutter, sum up the cross-sectional areas of all the conductors and ensure that the total conductor fill does not exceed 20% of the gutter’s cross-sectional area. 23 / 50 What is the minimum size auxiliary gutter that will contain the following conductors? (8) 350 kcmil THWN (4) 500 kcmil XHHW (4) 3/0 THW (1) 2/0 THWN (1) 4 AWG solid bare a. 58 sq in b. 72 sq in c. 64 sq in d. 69 sq in The selected value does not meet NEC requirements. The minimum size auxiliary gutter required is 64 sq in, considering conductor fill limits specified in NEC Article 366.22(A). Correct! The minimum size auxiliary gutter required for the conductors is 64 sq in, based on NEC Article 366.22(A). Conductor Areas: 350 kcmil THWN (from NEC Chapter 9, Table 5): 0.508 sq in per conductor (8)×0.508=4.064 sq in(8) \times 0.508 = 4.064 \, \text{sq in}(8)×0.508=4.064sq in 500 kcmil XHHW (from NEC Chapter 9, Table 5): 0.707 sq in per conductor (4)×0.707=2.828 sq in(4) \times 0.707 = 2.828 \, \text{sq in}(4)×0.707=2.828sq in 3/0 THW: 0.217 sq in per conductor (4)×0.217=0.868 sq in(4) \times 0.217 = 0.868 \, \text{sq in}(4)×0.217=0.868sq in 2/0 THWN: 0.158 sq in per conductor (1)×0.158=0.158 sq in(1) \times 0.158 = 0.158 \, \text{sq in}(1)×0.158=0.158sq in 4 AWG solid bare: 0.0243 sq in per conductor (1)×0.0243=0.0243 sq in(1) \times 0.0243 = 0.0243 \, \text{sq in}(1)×0.0243=0.0243sq in Total Conductor Area: 4.064+2.828+0.868+0.158+0.0243=7.9423 sq in4.064 + 2.828 + 0.868 + 0.158 + 0.0243 = 7.9423 \, \text{sq in}4.064+2.828+0.868+0.158+0.0243=7.9423sq in Calculate Minimum Gutter Size: Auxiliary gutters allow conductor fill up to 20% of their cross-sectional area. The minimum gutter size must satisfy: 7.9423 sq in≤0.2×Gutter Area7.9423 \, \text{sq in} \leq 0.2 \times \text{Gutter Area}7.9423sq in≤0.2×Gutter Area Solve for Gutter Area: Gutter Area≥7.94230.2=39.71 sq in\text{Gutter Area} \geq \frac{7.9423}{0.2} = 39.71 \, \text{sq in}Gutter Area≥0.27.9423=39.71sq in For practical usage, choose the next standard size: 64 sq in. Spacing helps manage heat dissipation. 24 / 50 What spacing is required between parallel underground direct-buried cables per 300.5(I)? a. 24 inches. b. 3 inches. c. No spacing is required. d. 12 inches. Incorrect. The minimum spacing for direct-buried cables is 12 inches Correct! 12 inches of separation ensures safe operation. Parallel direct-buried cables must be separated by at least 12 inches to allow for heat dissipation and prevent overheating. GFCI protection allows reduced burial depth for residential circuits. 25 / 50 What are the burial depth requirements for residential branch circuits with GFCI protection (300.5)? a. Always 24 inches. b. 18 inches for all circuits. c. 12 inches for circuits rated 120 volts or less with GFCI protection. d. Burial depth depends on conductor material. Incorrect. GFCI-protected circuits have specific reduced burial depth requirements. Correct! GFCI-protected circuits allow burial at 12 inches. Circuits with GFCI protection can be buried at 12 inches instead of the standard 18-24 inches for residential systems. Larger conductors need more frequent support. 26 / 50 How are conductors supported in vertical raceways per 300.19(A)? a. Conductors under 4 AWG need no support. b. Support intervals depend on conductor size per Table 300.19(A). c. Support is required for all conductor sizes. d. Vertical raceways require no additional support. Incorrect. Refer to Table 300.19(A) for proper support intervals. Correct! Support intervals depend on conductor size. Conductor size determines support intervals in vertical raceways, ensuring they are not damaged by weight or movement. Voltage ratings dictate conductor compatibility. 27 / 50 What conductors are permitted in the same raceway as 1000-volt AC circuits per 300.3(C)(1)? a. Only grounding conductors. b. Any low-voltage circuits. c. Conductors with insulation rated for the maximum circuit voltage. d. No other conductors are allowed. Incorrect. Voltage compatibility is essential for conductors in shared raceways. Correct! Insulation ratings must match the highest circuit voltage. Conductors in the same raceway must have insulation rated for the highest voltage present to ensure safety. Conductor fill is limited by the conduit size and the cross-sectional area of the conductors. 28 / 50 The largest number of 4 AWG THW conductors that can be installed in an 18-inch piece of 1 1/4″ Liquidtight Flexible Nonmetallic Conduit shall be: a. 9 b. 8 c. 6 d. 7 The selected number of conductors exceeds or does not meet the allowable fill for 4 AWG THW conductors in a 1 1/4″ Liquidtight Flexible Nonmetallic Conduit. Correct! The maximum number of 4 AWG THW conductors that can be installed in a 1 1/4″ Liquidtight Flexible Nonmetallic Conduit is 9, as specified in NEC Chapter 9, Table 4 and Annex C. Using NEC Chapter 9, Table 4 and Annex C for Liquidtight Flexible Nonmetallic Conduit, the maximum allowable number of 4 AWG THW conductors in a 1 1/4″ conduit is 9 conductors. This ensures that the conduit fill does not exceed the NEC’s 40% fill capacity for raceways. NEC tables specify adjustment factors. 29 / 50 How are adjustment factors applied for more than three current-carrying conductors in a raceway (310.15(C))? a. Adjustment depends only on the conductor material. b. No adjustments are required. c. Factors are applied based on the number of conductors per Table 310.15(C)(1). d. Adjustments apply only to aluminum conductors. Incorrect. Adjustment factors must follow the NEC table for conductors exceeding three. Correct! Table 310.15(C)(1) specifies adjustment factors for heat dissipation. Table 310.15(C)(1) provides adjustment factors for more than three current-carrying conductors in a raceway or cable to account for heat dissipati Continuity is essential for grounding and bonding. 30 / 50 What must be ensured for metal raceways per 300.10? a. They are grounded separately at each junction. b. They are metallically joined for electrical continuity. c. They are electrically insulated from boxes. d. They are painted for corrosion resistance. Incorrect. Raceways must be joined to ensure continuity. Correct! Continuous electrical paths are mandatory. Metal raceways must form a continuous electrical path to provide effective grounding and bonding. The NEC specifies a bending radius limit for cables to prevent damage and ensure proper performance. 31 / 50 The radius of the curve of the inner edge of any bend of Type SE cable, during or after installation, shall not be less than _______________ the diameter of the cable. a. Six times b. Seven times c. Five times d. Eight times The selected option does not meet NEC requirements for terminations at the end of rigid metal conduit. Correct! The minimum bending radius for Type SE cable is five times the diameter of the cable, as specified in NEC Article 338.24. According to NEC Article 338.24, the radius of the inner edge of any bend in Type SE cable must be not less than five times the diameter of the cable. This ensures the cable insulation and conductors are not damaged during or after installation. Insulation is essential unless otherwise allowed. 32 / 50 What is the requirement for insulated conductors not specifically permitted elsewhere in the Code (310.3(D))? a. They can be bare or covered. b. No specific requirements are stated. c. They must be stranded and covered with thermoplastic. d. They must be insulated. Incorrect. Insulation is required unless the Code allows other types. Correct! Insulation is required unless otherwise permitted. Insulated conductors are required unless specifically permitted to be bare or covered by another section of the Code. When using cable trays for service-entrance conductors, the NEC limits the conductor type to those suitable for the purpose. 33 / 50 Cable trays used to support service-entrance conductors shall contain only service-entrance conductors and shall be limited to _______________. a. Type MC b. Type UF c. Type SO d. Type EV The selected cable type does not meet NEC requirements. Only Type MC cables are permitted in cable trays for service-entrance conductors, per NEC Article 392.10(B). Correct! Cable trays used to support service-entrance conductors can only contain Type MC cables, as specified in NEC Article 392.10(B). Type MC: The NEC allows Type MC cable for use as service-entrance conductors when supported in cable trays. This type is designed for such applications, ensuring safety and compliance. Type UF and Type SO: These cables are not suitable for service-entrance conductor installations in cable trays as they do not meet the NEC requirements for this application. Type EV: This is used for electric vehicle applications and is not appropriate for service-entrance conductors in cable trays. Article 300 provides overarching rules for wiring methods. 34 / 50 What is the primary scope of Article 300? a. Grounding and bonding of conductors. b. Energy-efficient wiring systems. c. General requirements for wiring methods and materials for all installations. d. Overcurrent protection for electrical systems. Incorrect. Article 300 focuses on general wiring requirements, not grounding or overcurrent protection. Correct! Article 300 establishes general wiring rules for all installations. Article 300 covers the basic requirements for installing and maintaining wiring systems in all installations unless specifically modified by other articles. Conductors must be grouped for proper operation. 35 / 50 What is required when using multiconductor cables in raceways per 300.3(B)? a. They must all have the same ampacity rating. b. Conductors of different systems can share the same raceway. c. All conductors of the circuit must be grouped together. d. They must be separated by at least 1 inch. Incorrect. All circuit conductors must be grouped within the same raceway. Correct! Grouping maintains balance and prevents interference. Grouping conductors ensures electromagnetic balance and prevents interference or overheating. The NEC emphasizes fire safety and containment for penetrations through building walls. 36 / 50 Busway runs that have sections located both inside and outside of buildings shall have a(n) _______________ at the building wall. a. Bonding bushing b. Vapor seal c. Bushing d. 4 hour fire barrier The selected option does not align with NEC requirements for fire safety at building wall penetrations for busway installations. Correct! A 4-hour fire barrier is required at the building wall for busway runs transitioning between inside and outside, as specified in NEC Article 368.10(C). According to NEC Article 368.10(C), when busway runs transition between the inside and outside of a building, a 4-hour fire-rated barrier must be installed at the building wall. This ensures fire resistance and compliance with building safety standards. Metric designators are used alongside traditional trade sizes. 37 / 50 How are metric designators and trade sizes related per 300.1(C)? a. Metric designators replace trade sizes in the NEC. b. Metric designators correspond to traditional trade sizes. c. Metric threads are required for conduit connections. d. Metric sizes are exact dimensions. Incorrect. Metric designators and trade sizes are equivalent for identification, not dimensional changes. Correct! Metric designators match traditional trade sizes for identification. Metric designators are equivalent to trade sizes for identification but do not change the physical dimensions or thread standards of conduits. Proper clearance prevents damage from fasteners. 38 / 50 How must cables and raceways be installed under metal-corrugated roof decking per 300.4(E)? a. Installed at least 1 1/2 inches below the lowest surface. b. Attached using self-tapping screws. c. Secured directly to the decking. d. Buried within thermal insulation. Incorrect. The minimum clearance under metal decking is 1 1/2 inches. Correct! Clearance ensures protection from potential fastener damage. Cables and raceways must be installed with at least 1 1/2 inches of clearance to avoid damage from screws or nails. Materials must withstand environmental conditions 39 / 50 What must be done when installing raceways in corrosive environments per 300.6(A)? a. Use materials approved for the environment or provide corrosion protection. b. Apply paint to all metallic raceways. c. Use only plastic raceways. d. No special treatment is necessary. Incorrect. Corrosion protection is required for raceways in corrosive environments. Correct! Approved materials or coatings protect against corrosion. Metallic raceways in corrosive environments must be corrosion-resistant or have protective coatings to prevent damage. Consider depth and additional safety measures. 40 / 50 What requirement applies to underground installations of direct-buried cables per 305.15(A)? a. Backfill with large rocks or angular substances is permissible. b. No specific depth is required for direct-buried cables. c. The burial depth must meet Table 305.15(A) requirements and use warning ribbons if 12 inches above the cable. d. Direct-buried cables must be installed in metal conduits. Incorrect. Burial depth and warning ribbons are critical safety measures. Correct! Depth and warning ribbons ensure safety during installation and excavation. Direct-buried cables must meet specified burial depths in Table 305.15(A), and a warning ribbon must be installed at least 12 inches above the cables to indicate their location. To determine the correct conduit size, calculate the total cross-sectional area of the conductors and compare it with the allowable conduit fill for Schedule 40 PVC. 41 / 50 The minimum size PVC Schedule 40 conduit required for the following conductors is: (10) 12 AWG THW (12) 10 AWG TW (6) 8 AWG THHN (6) 6 AWG THHN a. 1 1/2 inch b. 2 inch c. 2 1/2 inch d. 3 inch The selected conduit size is either too large or too small to accommodate the conductors while adhering to NEC requirements. Correct! The minimum size PVC Schedule 40 conduit required is 2 inches, based on NEC Chapter 9, Table 4 and Table 5. A 2-inch Schedule 40 PVC conduit can accommodate the total conductor area of 0.8236 in² without exceeding the 40% fill limit. Only metal conduits require clearance. 42 / 50 What is the required clearance for bored holes in wood members per 300.4(A)(1)? a. At least 1 inch from the edge. b. Only metal conduits require clearance. c. No clearance is required for concealed locations. d. At least 1 inch from the edge. Incorrect. The clearance must be 1 1/4 inches or more. Correct! This clearance prevents accidental damage to conductors. Holes must maintain a clearance of 1 1/4 inches from the edge of wood members to prevent penetration by screws or nails. Separation prevents screws or fasteners from damaging cables. 43 / 50 What is the minimum separation required for cables installed under metal-corrugated roof decking per 300.4(E)? a. 1 1/2 inches from the lowest surface of the decking. b. No separation is required for concealed locations. c. 2 inches from the roof insulation. d. 3 inches from the highest point of the decking. Incorrect. The required separation is 1 1/2 inches from the decking surface. Correct! The 1 1/2-inch clearance ensures cable protection. A 1 1/2-inch separation from the lowest surface of the roof decking protects cables from penetration by screws or fasteners. The fittings must be designed to prevent water ingress in wet environments. 44 / 50 For enclosures in wet locations, raceways entering above the level of uninsulated live parts shall use fittings listed for _______________. a. Wet locations b. Damp locations c. Outdoor use d. Weather-proof use The selected option does not meet the NEC requirements for fittings used in wet location enclosures. Correct! Fittings for raceways entering enclosures in wet locations must be listed for wet locations, as specified in NEC Article 314.15. According to NEC Article 314.15, for enclosures in wet locations, raceways entering above the level of uninsulated live parts must use fittings specifically listed for wet locations. This ensures that water does not enter the enclosure and come into contact with live parts, maintaining safety and compliance. Grounded conductors follow general NEC identification rules. 45 / 50 How are grounded conductors identified per 310.6(A)? a. By the methods outlined in 200.6. b. Grounded conductors require no identification. c. By size and voltage rating. d. With red insulation or tags. Incorrect. Refer to 200.6 for grounded conductor identification methods. Correct! Identification follows the rules in 200.6. Grounded conductors must be identified in accordance with 200.6, using colors, tags, or other methods. Conductors in parallel must have matching characteristics. 46 / 50 What is required for conductors used in parallel installations (310.10(G))? a. Parallel installations are not permitted for ungrounded conductors. b. They must be of the same size, insulation, and length. c. They require additional grounding conductors. d. They must be sized larger than 1/0 AWG. Incorrect. Matching characteristics are required for parallel installations. Correct! Parallel conductors must meet these criteria. Conductors in parallel must be the same size, insulation type, and length to ensure equal current distribution. The NEC outlines specific distance requirements for securing and supporting MV cables to ensure stability and compliance. 47 / 50 Type MV cable terminated in equipment shall be secured and supported at intervals not exceeding _______________ from terminations or a maximum of _______________ between supports. a. 5 ft / 6 ft b. 6 ft / 4 ft c. 4 ft / 5 ft d. 5 ft / 5 ft The selected option does not meet NEC requirements. Type MV cables must be secured within 5 feet of terminations and supported at intervals not exceeding 6 feet, as stated in NEC Article 328.30(B). Correct! Type MV cables must be secured and supported within 5 feet of terminations and at intervals not exceeding 6 feet between supports, as per NEC Article 328.30(B). 5 ft from terminations and 6 ft between supports: NEC Article 328.30(B) states that Type MV cables must be secured and supported within 5 feet of terminations and at intervals not exceeding 6 feet between supports to ensure proper mechanical stability. Other options do not match the NEC’s stated requirements for Type MV cables. The NEC specifies different minimum sizes for copper and aluminum conductors 48 / 50 What is the minimum size of conductors for general wiring up to 2000 volts (310.3(A))? a. 16 AWG copper or copper-clad aluminum. b. 18 AWG copper or aluminum. c. 14 AWG copper or 12 AWG aluminum or copper-clad aluminum. d. 10 AWG for all installations. Incorrect. Check the NEC minimum size requirements for conductors. Correct! These are the NEC minimum sizes for general wiring. The minimum conductor sizes for general wiring are 14 AWG for copper and 12 AWG for aluminum or copper-clad aluminum. Proximity to buildings requires added protection for underground wiring. 49 / 50 What is the requirement for underground wiring within 6 feet of a building per 300.5(D)(1)? a. building per 300.5(D)(1)? b. The wiring must be in a raceway. c. It must use direct burial cables only. d. It must be buried at least 36 inches deep. Incorrect. Wiring must be installed in a raceway near buildings. Correct! A raceway is required for wiring within 6 feet of a building Underground wiring within 6 feet of a building must be enclosed in a raceway to ensure mechanical protection. Support intervals vary based on raceway type. 50 / 50 How often must nonmetallic raceways be secured per 300.11(C)? a. Every 10 feet, regardless of size. b. Every 5 feet for all installations. c. As required by the type of raceway used. d. Securing is optional for concealed installations. Incorrect. The securing intervals depend on the raceway type. Correct! Securing requirements are based on the raceway type. Nonmetallic raceways must be secured according to the specific requirements for their type, such as EMT or PVC. Your score is LinkedIn Facebook Twitter 0% Restart quiz Exit Rate & Review Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services. Send feedback Leave a Reply Cancel replyYour email address will not be published. Required fields are marked * Comment* Name* Email* Website Save my name, email, and website in this browser for the next time I comment. Post Comment