eep April 7, 2025 NEC 300-399 NEC Quizzes Report a question What’s wrong with this question? You cannot submit an empty report. Please add some details. 0% Article 300-399 Part09 This comprehensive quiz contains 50 questions carefully selected from the National Electrical Code (NEC) Articles spanning 300 through 399. This section of the NEC addresses crucial aspects of wiring methods, materials, and general requirements for electrical installations within this portion of the code. The questions in this quiz are chosen randomly to provide a thorough assessment of your knowledge across these essential NEC articles. While we strive for a diverse set of questions, some fundamental principles may be revisited in different contexts due to their relevance to multiple sections within this range. This approach ensures a robust evaluation of your understanding. We encourage you to actively participate and provide feedback. If you identify any issues or have suggestions for improving the quiz questions, please report them. Your contributions are invaluable in helping us maintain the accuracy and effectiveness of these learning resources. Consider the minimum support requirements for safety and compliance in electrical installations. 1 / 50 At least ______ support method(s) shall be provided for each conductor at the top of the vertical raceway or as close to the top as practical if the vertical rise exceeds the values in Table 300.19(A). a. one b. four c. three d. two Incorrect. The correct answer is one. At least one support method is required for each conductor in vertical raceways exceeding specified heights. Correct! At least one support method shall be provided for each conductor at the top of the vertical raceway when the vertical rise exceeds the values in Table 300.19(A). According to NEC Article 300.19, at least one support method must be provided for each conductor at the top of the vertical raceway or as close to the top as practical if the vertical rise exceeds the specified values in Table 300.19(A). Therefore, the correct answer is one. Think about the certification standards that ensure electrical materials are safe and suitable for use. 2 / 50 Type NM cable and its associated fittings must be ______. a. identified b. marked c. approved d. listed That’s not correct. Remember, Type NM cable and its fittings must meet specific certification standards to ensure safety and compliance. Correct! Type NM cable and its associated fittings must be listed to ensure they meet safety standards and code compliance. Great job! According to NEC Article 334.10, Type NM (Nonmetallic-Sheathed) cable and its associated fittings must be listed. This means they have been tested and approved by a recognized laboratory to ensure they meet specific safety and performance standards. Listing is essential for ensuring compliance with the National Electrical Code and the safety of electrical installations. Think about the classification and certification standards for electrical equipment and materials. 3 / 50 AC cables and their associated fittings must be ______. a. listed b. labeled c. identified d. approved That’s not correct. Remember, AC cables and their fittings must be certified to meet safety and performance standards. Correct! AC cables and their associated fittings must be listed to ensure they meet safety standards and code compliance. Well done! According to the NEC, particularly Article 320, AC cables and their fittings must be listed. This means they have been tested and certified by a recognized testing laboratory to meet safety and performance standards. Using listed materials ensures that installations comply with code requirements and are safe for use. Consider the impact of direct sunlight on conductors and the necessary temperature adjustments for proper installation. 4 / 50 Where conductors are installed in raceways or cables exposed to direct sunlight on or above rooftops, a temperature adder of __ shall be added to the outdoor temperature where the conduits are less than ½ inch from the rooftop. a. 60°F b. 50°F c. 30°F d. 40°F Incorrect. The correct answer is 60°F. This temperature adjustment is specified for conductors exposed to direct sunlight in NEC Article 310.15. Correct! When conductors are installed in raceways or cables exposed to direct sunlight on rooftops and are less than ½ inch from the rooftop, a temperature adder of 60°F must be applied, as outlined in NEC Article 310.15. According to NEC Article 310.15, when conductors are installed in raceways or cables exposed to direct sunlight on or above rooftops, and the conduits are less than ½ inch from the rooftop, a temperature adder of 60°F must be added to the outdoor temperature. Therefore, the correct answer is 60°F. Consider the various approved methods for securing NM cable as specified in the code to ensure proper installation. 5 / 50 Type NM cable can be supported and secured using ______. a. straps b. any of these c. cable ties listed and identified for securement and support d. staples That’s not correct. Remember, Type NM cable can be supported and secured using multiple approved methods according to the code. Correct! Type NM cable can be supported and secured by staples, cable ties, straps, or any of these methods. Well done! According to NEC Article 334.30, Type NM (Nonmetallic-Sheathed) cable can be supported and secured by staples, cable ties that are listed and identified for securement, straps, or any other approved means. The flexibility in securing methods ensures that installations comply with safety standards while accommodating various installation scenarios. Consider the distance allowed for flush-type covers in noncombustible installations. 6 / 50 What is the maximum distance that the front edge of a box, plaster ring, extension ring, or listed extender with a flush-type cover can be set back from the finished surface in installations within or behind noncombustible walls or ceilings? a. 3/8 in b. 1/2 in c. 1/4 in d. 1/8 in Incorrect. The correct answer is 1/4 in. This is the maximum distance for proper installation in noncombustible wall or ceiling applications. Correct! The front edge of the box, plaster ring, extension ring, or listed extender must be set back no more than 1/4 inch from the finished surface according to NEC guidelines. According to NEC Article 314.20, in installations within or behind noncombustible walls or ceilings, the front edge of a box, plaster ring, extension ring, or listed extender employing a flush-type cover must be set back no more than 1/4 inch from the finished surface to ensure compliance and safety. Think about the methods used to prevent moisture from entering conduits or raceways that could potentially affect live electrical components. 7 / 50 Conduits or raceways through which moisture may contact live parts shall be _____ at either or both ends. a. a or b b. bushed c. plugged d. sealed Incorrect. The correct answer is a or b. Conduits or raceways must be sealed or plugged to prevent moisture from contacting live parts. Correct! To prevent moisture from contacting live parts, conduits or raceways must be either sealed or plugged at either or both ends, as specified in NEC Article 300.7. According to NEC Article 300.7, conduits or raceways that may allow moisture to contact live parts must be either sealed or plugged at either or both ends to ensure protection against moisture intrusion. Therefore, the correct answer is a or b. Think about the specific requirements for drainage openings and the types of ratings that apply to electrical equipment in various environmental conditions. 8 / 50 ____ drainage openings not smaller than 1/8 in. and not larger than 1/4 in. in diameter shall be permitted to be installed in the field in boxes or conduit bodies listed for use in damp or wet locations. a. Listed b. Identified c. Labeled d. Approved Incorrect. The correct answer is Listed. Drainage openings must be installed in boxes or conduit bodies that are listed for damp or wet locations. Correct! Drainage openings not smaller than 1/8 in. and not larger than 1/4 in. in diameter are permitted in boxes or conduit bodies that are Listed for use in damp or wet locations, as specified in NEC Article 314.15. According to NEC Article 314.15, drainage openings that are between 1/8 inch and 1/4 inch in diameter are allowed in boxes or conduit bodies that are specifically listed for use in damp or wet locations. Therefore, the correct answer is Listed. Consider the maximum length allowed for unsupported installations in accessible ceiling spaces according to the code. 9 / 50 Armored cable that connects recessed luminaires or equipment in an accessible ceiling can be unsupported and unsecured for a distance of up to ______ feet. a. 2 b. 3 c. 6 d. 4 1/2 That’s not correct. Remember, there is a specific length limit for unsupported armored cable in accessible ceilings. Correct! Armored cable used for connecting recessed luminaires or equipment in accessible ceilings can be unsupported and unsecured for up to 6 feet. Great job! According to NEC Article 320.23(B), armored cable (AC) can be unsupported and unsecured for lengths up to 6 feet when used to connect recessed luminaires or equipment within an accessible ceiling. This allowance facilitates installation in areas where additional support may not be feasible, while still adhering to safety standards. Consider the physical properties of materials and how they change with temperature when installed in electrical systems. 10 / 50 Raceways shall be provided with expansion, expansion-deflection, or deflection fittings where necessary to compensate for thermal expansion, deflection, and contraction. a. False b. True Incorrect. The correct answer is True. Raceways must have the necessary fittings to accommodate thermal changes. Correct! Raceways must be equipped with expansion, expansion-deflection, or deflection fittings as required to handle thermal expansion, deflection, and contraction, as specified in NEC Article 300.7. According to NEC Article 300.7, raceways must indeed be provided with appropriate fittings, such as expansion, expansion-deflection, or deflection fittings, to effectively manage thermal expansion, deflection, and contraction. Therefore, the correct answer is True. Consider the insulation types that are commonly recognized for their heat resistance and suitability for various applications in electrical installations. 11 / 50 Unless otherwise specified, which type of insulation do the applicable product standards evaluate for the fill markings covered in 314.28(A)(3)? a. THHW b. XHHW c. RHW d. THHN Incorrect. The correct answer is XHHW. This type of insulation is recognized for its performance in various electrical applications. Correct! The applicable product standards evaluate the fill markings covered in 314.28(A)(3), based on conductors with Type XHHW insulation. Unless otherwise specified, the applicable product standards evaluate the fill markings covered in 314.28(A)(3) based on conductors with Type XHHW insulation. Consider the term used in the NEC to denote products that have been evaluated and meet specific standards for installation. 12 / 50 For locations not specifically identified in Table 300.5, a lesser cover depth than required in Column 5 shall be permitted where specified in the installation instructions of a(n) _____ low-voltage lighting system. a. none of these b. labeled c. listed d. approved Incorrect. The correct answer is listed. A lesser cover depth is permitted for low-voltage lighting systems that are listed according to the NEC. Correct! For low-voltage lighting systems not specifically identified in Table 300.5, a lesser cover depth is permitted when specified in the installation instructions of a listed system, as outlined in NEC Article 300.5. According to NEC Article 300.5, for locations not specifically identified in Table 300.5, a lesser cover depth than required in Column 5 may be allowed if specified in the installation instructions of a listed low-voltage lighting system. Therefore, the correct answer is listed. Think about the specific scenarios outlined in the code that allow for unsupported installations of nonmetallic-sheathed cable. 13 / 50 Nonmetallic-sheathed cable is allowed to be unsupported in situations where the cable is ______. a. none of these b. fished between access points through concealed spaces in finished buildings or structures where supporting is impractical c. not more than 4 1/2 ft from the last point of cable support to the connection point of a luminaire or other electrical equipment, provided both the cable and connection point are within an accessible ceiling in one-, two-, or multifamily dwellings d. a or b That’s not correct. Remember, there are specific conditions under which nonmetallic-sheathed cable can be installed unsupported. Correct! Nonmetallic-sheathed cable can be unsupported in certain situations, such as when fished through concealed spaces or within specified distances to luminaires in accessible ceilings. Great job! According to NEC Article 334.30(B), nonmetallic-sheathed cable is permitted to be unsupported when it is fished between access points through concealed spaces in finished buildings or structures where supporting is impractical. Additionally, it can be unsupported if it is not more than 4 1/2 feet from the last point of support to the connection point of a luminaire or other electrical equipment, provided both are located within an accessible ceiling in one-, two-, or multifamily dwellings. This flexibility ensures compliance with safety standards while accommodating various installation conditions. Consider how the installation method and number of current-carrying conductors affect the ampacity adjustments required. 14 / 50 If cables meeting the requirements in 310.15(B)(3)(4)a through c with more than 20 current-carrying conductors are installed longer than 24 inches without maintaining spacing, are stacked, or are supported on bridle rings, a __ percent adjustment factor shall be applied. a. 50 b. 40 c. 60 d. 30 Incorrect. The correct answer is 60. This adjustment factor applies to specific installation conditions as specified in NEC Article 310.15. Correct! If cables meeting the requirements in NEC Article 310.15 are installed under the specified conditions, a 60 percent adjustment factor shall be applied. According to NEC Article 310.15, if cables with more than 20 current-carrying conductors are installed longer than 24 inches without proper spacing, stacked, or supported on bridle rings, a 60 percent adjustment factor must be applied to the ampacity of the conductors. Therefore, the correct answer is 60. Consider the safety requirements for fixtures attached to ceilings and the potential weight of lighting equipment. 15 / 50 What is the minimum weight that boxes used at luminaire or lampholder outlets in a ceiling must be designed to support? a. 20 lb b. 30 lb c. 50 lb d. 40 lb Incorrect. The correct answer is 50 lb. This ensures that the outlet boxes are capable of safely supporting the weight of luminaires installed in ceilings. Correct! Boxes used at luminaire or lampholder outlets in a ceiling must support a minimum weight of 50 lb, as required by NEC guidelines to ensure safety and reliability. NEC Article 314.27 specifies that boxes used at luminaire or lampholder outlets in a ceiling must be designed to support a luminaire weighing a minimum of 50 lb to ensure adequate safety and structural integrity. Consider the common fasteners used in electrical installations to secure electrical boxes. 16 / 50 What can be used to secure boxes to a structural member using brackets on the outside of the enclosure? a. Bolts b. Screws c. Nails d. a and b Incorrect. The correct answer is a and b. Both nails and screws can be used to secure boxes to structural members using brackets. Correct! Boxes can be secured to structural members using either nails or screws with brackets on the outside of the enclosure, as specified by NEC guidelines. According to NEC Article 314.23, boxes can be secured to structural members using nails or screws. Both methods are acceptable as long as the installation complies with safety standards. Consider how sunlight exposure can affect the installation requirements for raceways and cables. 17 / 50 Where raceways or cables are exposed to direct sunlight on or above rooftops, raceways or cables shall be installed a minimum distance of __ inches above the roof to the bottom of the raceway or cable. a. 1/2 b. 1/4 c. 1/3 d. 7/8 Incorrect. The correct answer is 7/8 inches. This minimum distance is required to protect raceways and cables from the effects of direct sunlight as specified in NEC Article 300.7. Correct! Raceways or cables exposed to direct sunlight on or above rooftops must be installed a minimum distance of 7/8 inches above the roof, as stated in NEC Article 300.7. According to NEC Article 300.7, when raceways or cables are exposed to direct sunlight on or above rooftops, they must be installed a minimum distance of 7/8 inches above the roof to ensure proper protection and performance. Therefore, the correct answer is 7/8. Think about the type of cable that is specifically designed for flexibility and mechanical protection with an armored exterior. 18 / 50 Type ______ cable is a fabricated assembly of insulated conductors in a flexible interlocked metallic armor. a. NMC b. b and c c. NM d. AC Incorrect. The correct answer is AC. NEC Article 320.2 defines Type AC cable as having insulated conductors within flexible interlocked metallic armor. Correct! NEC Article 320.2 specifies that Type AC cable is a fabricated assembly of insulated conductors enclosed in a flexible interlocked metallic armor, providing both mechanical protection and grounding. According to NEC Article 320.2, Type AC cable is defined as a fabricated assembly of insulated conductors that is protected by a flexible interlocked metallic armor. This type of cable is commonly used in various electrical installations for its durability and protective qualities. Think about the requirements for sealing in raceways that deal with temperature variations and condensation without needing to rely solely on explosion-proof seals. 19 / 50 If remote-control, signaling, and power-limited circuits are installed in a raceway that is subjected to different temperatures, and where condensation is known to be a problem, the raceway shall be filled with an approved material that will prevent the circulation of warm air to a colder section of the raceway. An explosion-proof seal ______. a. isn't required for this purpose b. has been proven effective for this purpose c. is required for this purpose d. is the only method of doing this Incorrect. The correct answer is isn’t required for this purpose. NEC Article 300.7 specifies that while a seal can be used, it is not mandatory for preventing air circulation and condensation in temperature-variable conditions. Correct! NEC Article 300.7 states that an explosion-proof seal is not required for preventing air circulation in raceways subjected to different temperatures where condensation may occur, allowing for other approved materials to be used. According to NEC Article 300.7, when remote-control, signaling, and power-limited circuits are installed in a raceway subjected to different temperatures, the raceway should be filled with an approved material to prevent the circulation of warm air to colder sections. An explosion-proof seal is not required for this purpose, as there are alternative methods available. Consider the components that may be affected by improper backfill material in underground installations. 20 / 50 Backfill used for underground wiring shall not damage ____ or prevent adequate compaction of fill or contribute to corrosion. a. cables b. conductors c. all of these d. raceways Incorrect. The correct answer is all of these. The backfill must not damage raceways, cables, or conductors. Correct! Backfill used for underground wiring should not damage all of these components—raceways, cables, and conductors—as specified in NEC Article 300.5. According to NEC Article 300.5, the backfill used for underground wiring must not damage any of the components involved, including raceways, cables, and conductors. Additionally, it should not prevent adequate compaction of the fill or contribute to corrosion. Therefore, the correct answer is all of these. Think about the standards that ensure the safe and effective installation of electrical components. 21 / 50 What should the mounting holes for screws used to secure boxes to a structural member using brackets on the outside of the enclosure be? a. Approved b. Listed c. Labeled d. Identified Incorrect. The correct answer is approved. The mounting holes must be approved to ensure safety and compliance with installation standards. Correct! The mounting holes for screws used to secure boxes must be approved, as per NEC guidelines, to ensure safe and effective installation. NEC Article 314.23 requires that mounting holes for screws securing boxes must be approved. This ensures that the mounting method is safe and compliant with electrical installation standards. Consider what types of equipment can be included in the wiring space of enclosures and what requirements must be satisfied. 22 / 50 The wiring space of enclosures for switches or overcurrent devices shall be permitted to contain power monitoring equipment where the ____. a. none of these b. power monitoring equipment is identified as a field-installable accessory as part of the listed equipment, or is a listed kit evaluated for field installation in switch or overcurrent device enclosures c. total area of all conductors, splices, taps, and equipment at any cross-section of the wiring space does not exceed 75 percent of the cross-sectional area of that space d. a and b Incorrect. The correct answer is a and b. Both conditions must be met to ensure compliance with NEC Article 314.28 regarding the use of power monitoring equipment in enclosures. Correct! The wiring space of enclosures for switches or overcurrent devices can contain power monitoring equipment if both specified conditions are satisfied, as outlined in NEC Article 314.28. According to NEC Article 314.28, the wiring space of enclosures for switches or overcurrent devices can include power monitoring equipment if two conditions are met: (1) the equipment must be identified as a field-installable accessory as part of the listed equipment, or it must be a listed kit evaluated for installation in the enclosure; and (2) the total area of all conductors, splices, taps, and equipment must not exceed 75 percent of the cross-sectional area of the wiring space. Therefore, the correct answer is a and b. Consider all the environmental conditions that could potentially harm electrical conductors and equipment. 23 / 50 Unless identified for use in the operating environment, no conductors or equipment shall be ______ having a deteriorating effect on the conductors or equipment. a. exposed to fumes, vapors, liquids, or gases b. all of these c. exposed to excessive temperatures d. located in damp or wet locations Incorrect. The correct answer is all of these. NEC Article 300.9 states that conductors and equipment should not be exposed to environments that could cause deterioration unless they are specifically identified for such conditions. Correct! NEC Article 300.9 specifies that unless conductors or equipment are identified for use in specific operating environments, they should not be exposed to conditions that could have a deteriorating effect, including being located in damp or wet locations, exposed to fumes, vapors, liquids, or gases, or subjected to excessive temperatures. According to NEC Article 300.9, conductors and equipment must not be installed in environments that may cause deterioration unless they are rated or identified for such use. This encompasses being in damp or wet locations, exposure to fumes, vapors, liquids, or gases, and being subjected to excessive temperatures. Consider the specific ratings and standards that apply to electrical equipment used in environments where they may be exposed to moisture. 24 / 50 Boxes, conduit bodies, and fittings installed in wet locations shall be listed for use in wet locations. a. True b. False Incorrect. The correct answer is True. Boxes, conduit bodies, and fittings installed in wet locations must be listed for use in those environments as per NEC requirements. Correct! Boxes, conduit bodies, and fittings installed in wet locations must be listed for use in wet locations, as specified in NEC Article 314.15. According to NEC Article 314.15, all boxes, conduit bodies, and fittings that are installed in wet locations must be specifically listed for that purpose to ensure safety and compliance with electrical code standards. Thus, the statement is true. Consider the various conditions that must be met for safe installation and use of enclosures in electrical systems. 25 / 50 Cabinets, cutout boxes, and meter socket enclosures can be used for conductors feeding through, spliced, or tapping off to other enclosures, switches, or overcurrent devices where ____. a. a warning label on the enclosure identifies the closest disconnecting means for any feed-through conductors b. the total area of conductors, splices, and taps installed at any cross section does not exceed 75 percent of the cross-sectional area of that space c. all of these d. the total area of the conductors at any cross section does not exceed 40 percent of the cross-sectional area of that space Incorrect. The correct answer is all of these. Each condition ensures the safe use of cabinets, cutout boxes, and meter socket enclosures as outlined in NEC Article 314.28. Correct! Cabinets, cutout boxes, and meter socket enclosures can be used for conductors feeding through, spliced, or tapping off as long as all specified conditions are met, as detailed in NEC Article 314.28. According to NEC Article 314.28, cabinets, cutout boxes, and meter socket enclosures can be utilized for conductors feeding through, splicing, or tapping off to other enclosures or devices as long as they meet multiple conditions: the total area of conductors at any cross-section does not exceed 40 percent, the total area of conductors, splices, and taps does not exceed 75 percent, and there is a warning label identifying the nearest disconnecting means for any feed-through conductors. Therefore, the correct answer is all of these. Consider the requirements for flush-type covers and the materials of the walls or ceilings. 26 / 50 In installations within walls or ceilings made of wood or other combustible materials, what should be the positioning of boxes, plaster rings, extension rings, or listed extenders? a. Be set back no more than 1/4 in. b. Extend to the finished surface c. a or b d. Project from the finished surface Incorrect. The correct answer is a or b. Boxes and related components should either extend to or project from the finished surface in combustible installations. Correct! In combustible installations, boxes, plaster rings, extension rings, or listed extenders can either extend to the finished surface or project from the finished surface as per NEC guidelines. According to NEC Article 314.20, in installations within walls or ceilings made of combustible materials, boxes, plaster rings, extension rings, or listed extenders must either extend to the finished surface or project from the finished surface, ensuring that they are properly installed to maintain safety and accessibility. Think about the specific cover depth allowed for low-voltage lighting systems in recreational water settings according to NEC guidelines. 27 / 50 For locations not specifically identified in Table 300.5, a cover depth of _____ in. shall be permitted for pool, spa, and fountain lighting, installed in a nonmetallic raceway, limited to not more than 30V where part of a listed low-voltage lighting system. a. 6 b. 12 c. 18 d. 24 Incorrect. The correct answer is 6. This is the permitted cover depth for low-voltage lighting systems in pool, spa, and fountain applications. Correct! For pool, spa, and fountain lighting installed in a nonmetallic raceway as part of a listed low-voltage lighting system, a cover depth of 6 inches is allowed, as specified in NEC Article 300.5. According to NEC Article 300.5, for locations not specifically identified in Table 300.5, a cover depth of 6 inches is permitted for pool, spa, and fountain lighting installed in a nonmetallic raceway, provided that it is limited to not more than 30V and is part of a listed low-voltage lighting system. Therefore, the correct answer is 6. Consider the sections that specify the conditions under which additional wiring may be included in the enclosures. 28 / 50 The wiring space within enclosures for switches and overcurrent devices shall be permitted for other wiring and equipment subject to limitations for specific equipment as provided in ____. a. none of these b. a and b c. 312.8(A) d. 312.8(B) Incorrect. The correct answer is a and b. Both sections 312.8(A) and 312.8(B) provide guidelines for the wiring space within enclosures. Correct! The wiring space within enclosures for switches and overcurrent devices can be used for other wiring and equipment, as specified in both NEC Article 312.8(A) and 312.8(B). According to NEC Article 312.8, the wiring space within enclosures for switches and overcurrent devices is permitted for other wiring and equipment, provided that the limitations for specific equipment are adhered to as outlined in both 312.8(A) and 312.8(B). Therefore, the correct answer is a and b. Consider the specific installation rules for NM cable in various residential and commercial applications. 29 / 50 Type NM cable is permitted to be installed as open runs in dropped or suspended ceilings in buildings other than one- and two-family and multifamily dwellings. a. True b. False That’s not correct. Remember, there are specific restrictions on the installation of NM cable in certain types of buildings. Correct! Type NM cable cannot be installed as open runs in dropped or suspended ceilings in buildings other than one- and two-family and multifamily dwellings. Great job! According to NEC Article 334.12, Type NM (Nonmetallic-Sheathed) cable is not permitted to be installed as open runs in dropped or suspended ceilings in any buildings other than one- and two-family and multifamily dwellings. This restriction is in place to ensure safety and compliance with building codes, as NM cable is primarily intended for residential applications. Think about the importance of securing electrical components to ensure safety and proper function in electrical installations. 30 / 50 Raceways, cable assemblies, boxes, cabinets, and fittings shall be securely fastened in place. a. False b. True Incorrect. The correct answer is True. It is essential for raceways and related components to be securely fastened. Correct! Raceways, cable assemblies, boxes, cabinets, and fittings must be securely fastened in place, as required by NEC Article 300.11. According to NEC Article 300.11, raceways, cable assemblies, boxes, cabinets, and fittings must indeed be securely fastened in place to ensure safety and integrity in electrical installations. Therefore, the correct answer is True. Think about the maximum allowable filling percentage for wiring space in electrical enclosures. 31 / 50 Enclosures for switches or overcurrent devices are allowed to have conductors feeding through where the wiring space at any cross section is not filled to more than ____ percent of the cross-sectional area of the space. a. 40 b. 20 c. 30 d. 60 Incorrect. The correct answer is 40 percent. This limit is set to ensure safe and effective use of wiring space in accordance with NEC Article 314.28. Correct! Enclosures for switches or overcurrent devices can accommodate conductors feeding through as long as the wiring space is not filled to more than 40 percent of the cross-sectional area, as specified in NEC Article 314.28. According to NEC Article 314.28, enclosures for switches or overcurrent devices can have conductors feeding through, provided that the wiring space at any cross section does not exceed 40 percent of the cross-sectional area of the space. Therefore, the correct answer is 40. Consider how safety and reliability are ensured in electrical installations, especially regarding mounting and support. 32 / 50 What type of support is required for outlet boxes specified in NEC Article 314.27 when used with locking support and mounting receptacles? a. Approved b. Identified c. Labeled d. Listed Incorrect. The correct answer is listed. This designation ensures that the outlet box meets specific safety and performance criteria. Correct! Outlet boxes required in NEC Article 314.27 are permitted to support listed locking support and mounting receptacles used with compatible attachment fittings, ensuring they adhere to safety regulations. According to NEC Article 314.27, outlet boxes required in this section shall be permitted to support listed locking support and mounting receptacles used in combination with compatible attachment fittings, ensuring they meet safety standards. Think about the specific types of electrical elements involved in underground installations and their flexibility requirements as recognized by the NEC. 33 / 50 “S” loops in underground direct burial _____ to raceway transitions, expansion fittings in raceway risers to fixed equipment, and, generally, the provision of flexible connections to equipment subject to settlement or frost heaves are recognized by the NEC. a. wireways and cable trays b. feeders and circuits c. none of these d. cables and conductors Incorrect. The correct answer is cables and conductors. The NEC recognizes the need for “S” loops in these components to accommodate movement and flexibility. Correct! “S” loops in underground direct burial cables and conductors are recognized by the NEC for transitions and flexibility requirements, as specified in NEC Article 300.5. According to NEC Article 300.5, “S” loops in underground direct burial cables and conductors are recognized for their flexibility and the need for movement due to factors like settlement or frost heaves, especially at transitions to raceways and in expansion fittings. Therefore, the correct answer is cables and conductors. Consider the number of ungrounded conductors typically used in residential single-phase systems. 34 / 50 For one-family dwellings and the individual dwelling units of two-family and multifamily dwellings, single-phase feeder conductors consisting of __ ungrounded conductor(s) and the neutral conductor from a 208Y/120 volt system shall be permitted to be sized in accordance with 310.15(B)(7)(1) through (3). a. 4 b. 1 c. 2 d. 3 Incorrect. The correct answer is 2 ungrounded conductors. This sizing allowance is specified in NEC Article 310.15(B)(7). Correct! For one-family and multifamily dwellings, single-phase feeder conductors can consist of 2 ungrounded conductors and the neutral conductor from a 208Y/120 volt system, as outlined in NEC Article 310.15(B)(7). According to NEC Article 310.15(B)(7), for one-family dwellings and the individual dwelling units of two-family and multifamily dwellings, single-phase feeder conductors consisting of 2 ungrounded conductors and the neutral conductor from a 208Y/120 volt system may be sized in accordance with the specified sections. Therefore, the correct answer is 2. Consider how barriers in electrical boxes affect the total volume available for conductors and devices. 35 / 50 Where a box is provided with __ or more securely installed barriers, the volume shall be apportioned to each of the resulting spaces; each barrier, if not marked with its volume, shall be considered to take up ½ cu in. if metal, and 1 cu in. if nonmetallic. a. three b. four c. two d. one Incorrect. The correct answer is one. A box with one or more securely installed barriers requires volume apportionment as specified by NEC. Correct! Where a box is provided with one or more securely installed barriers, the volume shall be apportioned to each of the resulting spaces, as specified in NEC Article 314.16. According to NEC Article 314.16, if a box is equipped with one or more securely installed barriers, the volume of the box must be apportioned to each resulting space. If the barriers are not marked with their volume, they are assumed to occupy ½ cu in. for metal barriers and 1 cu in. for nonmetallic barriers. Therefore, the correct answer is one. Think about how to properly prepare HDPE conduit after cutting to avoid rough edges that could damage conductors. 36 / 50 The cut ends of HDPE conduit shall be _______ to remove rough edges. a. trimmed inside and outside b. all of these c. filed on the inside d. cut only with a hacksaw Incorrect. The correct answer is trimmed inside and outside. NEC Article 353.28 requires that the cut ends of HDPE conduit be trimmed both inside and outside to remove rough edges. Correct! NEC Article 353.28 specifies that the cut ends of HDPE conduit must be trimmed inside and outside to remove rough edges, ensuring safe installation and preventing damage to conductors. According to NEC Article 353.28, after cutting HDPE conduit, the ends must be trimmed both inside and outside to remove any rough edges. This ensures that the conduit can be safely joined and that the conductors will not be damaged during installation or pulling. Think about the certification and compliance standards that electrical cables must meet to ensure safety and reliability. 37 / 50 Types SE and USE cables, along with their associated fittings, must be ______. a. approved b. identified c. labeled d. listed That’s not correct. Remember, Types SE and USE cables must be listed to meet safety and performance standards. Correct! Types SE and USE cables and their associated fittings must be listed to ensure they comply with safety standards and code requirements. Great job! According to NEC Article 338.10, Types SE (Service Entrance) and USE (Underground Service Entrance) cables and their associated fittings must be listed. This means they have undergone testing and certification by an approved laboratory to meet specific safety and performance standards. This requirement ensures that these cables are suitable for their intended applications and comply with the National Electrical Code. Consider the maximum allowable gap size around flush-mounted boxes to maintain safety and proper enclosure. 38 / 50 Noncombustible surfaces that are broken or incomplete around boxes employing a flush-type cover or faceplate shall be repaired so there will be no gaps or open spaces larger than ________ in. at the edge of the box. a. 1/4 b. 1/2 c. 1/16 d. 1/8 Incorrect. The correct answer is 1/8 inch. NEC Article 314.21 specifies that gaps around flush-mounted boxes must not exceed 1/8 inch to maintain safety and prevent fire hazards. Correct! NEC Article 314.21 requires that any gaps or open spaces around boxes employing flush-type covers or faceplates must be repaired so that no gaps larger than 1/8 inch exist to ensure safety and proper sealing. According to NEC Article 314.21, the gap or open space around a flush-mounted box with a cover or faceplate must be repaired to ensure that no gaps larger than 1/8 inch exist. This prevents the risk of fire hazards or exposure of electrical components. To find the volume of a rectangular box, multiply the length, width, and height together. 39 / 50 According to the NEC, what is the volume of a 3 in. x 2 in. x 2 in. device box in cubic inches? a. 10 b. 8 c. 14 d. 12 Incorrect. The correct answer is 10 cu in. While the raw calculation gives 12, NEC specifications adjust this based on other factors. Correct! The volume of a 3 in. x 2 in. x 2 in. device box is 10 cu in according to NEC guidelines. To calculate the volume of a device box, you use the formula for the volume of a rectangular prism: Volume=Length×Width×Height\text{Volume} = \text{Length} \times \text{Width} \times \text{Height}Volume=Length×Width×Height For a box measuring 3 in. x 2 in. x 2 in., the calculation is: 3 in×2 in×2 in=12 cu in3 \, \text{in} \times 2 \, \text{in} \times 2 \, \text{in} = 12 \, \text{cu in}3in×2in×2in=12cu in However, for device boxes, the NEC usually provides specific volume allowances, and the answer is listed as 10 cu in due to additional considerations for internal components. Consider the specific conditions under which wiring methods can be used in air-handling ducts for safety and compliance. 40 / 50 Wiring methods and cabling systems, listed for use in other spaces used for environmental air (plenums), shall be permitted to be installed in ducts specifically fabricated for environmental air-handling purposes __. a. a and b b. if the total length of such wiring methods or cabling systems does not exceed 4 ft c. only if necessary to connect equipment or devices associated with the direct action upon or sensing of the contained air d. none of these Incorrect. The correct answer is a and b. Both conditions must be met for the installation of wiring methods in air-handling ducts. Correct! Wiring methods and cabling systems may be installed in ducts for environmental air-handling purposes only if necessary to connect equipment or devices and if the total length does not exceed 4 ft, as specified in NEC Article 300.22. According to NEC Article 300.22, wiring methods and cabling systems listed for use in other spaces used for environmental air can be installed in ducts specifically fabricated for environmental air-handling purposes if necessary to connect equipment or devices associated with the direct action upon or sensing of the contained air, and the total length does not exceed 4 ft. Therefore, the correct answer is a and b. Consider the various methods allowed for securing MC cable as outlined in the code to ensure proper installation without causing damage. 41 / 50 Type MC cable must be supported and secured by staples, cable ties, ______, or other approved means that are designed and installed to prevent damage to the cable. a. none of these b. listed c. identified d. a and b That’s not correct. Remember, the requirements for supporting and securing Type MC cable include multiple approved methods to ensure the cable is not damaged. Correct! Type MC cable can be supported and secured using staples, cable ties, straps, hangers, or similar approved means, as long as they are designed to prevent damage to the cable. Great job! According to NEC Article 330.30(A), Type MC (Metal Clad) cable must be secured and supported using staples, cable ties, straps, hangers, or similar fittings. These means must be designed and installed to avoid damaging the cable, ensuring both compliance with the code and the safety of the installation. The options “listed” and “identified” refer to the standards for fittings, which are also important but not the only methods for securing the cable. Think about the standards for securely attaching lighting fixtures to ensure they are safe and adequately supported. 42 / 50 What is the weight threshold for a luminaire that allows it to be supported by an outlet box specifically listed for that weight? a. 50 lb b. 20 lb c. 40 lb d. 30 lb Incorrect. The correct answer is 50 lb. This weight limit is critical for ensuring the outlet box is designed to support the luminaire safely. Correct! A luminaire that weighs more than 50 lb can be supported by an outlet box that is specifically listed for that weight, ensuring compliance with safety regulations. According to NEC Article 314.27, a luminaire that weighs more than 50 lb can be supported by an outlet box that is listed for the weight of the luminaire to ensure it meets safety standards and regulations. Consider the specific scenarios in which Type MC cable installation allows for flexibility and the absence of support. 43 / 50 Type MC cable can be unsupported and unsecured in situations where the cable is ______. a. not more than 6 ft from the last point of support within an accessible ceiling for the connection of luminaires or other electrical equipment b. not more than 2 ft at terminals where flexibility is necessary c. a or c d. fished between concealed access points in finished buildings or structures where support is impractical That’s not correct. Remember, Type MC cable can be unsupported in specific scenarios outlined in the code regarding its installation. Correct! Type MC cable can be unsupported and unsecured when fished between concealed access points where support is impractical or when it is not more than 6 feet from the last point of support. Well done! According to NEC Article 330.30(B), Type MC (Metal Clad) cable can be left unsupported and unsecured when fished between concealed access points in finished buildings or structures where support is impractical or when it is not more than 6 feet from the last point of support within an accessible ceiling for the connection of luminaires or other electrical equipment. These allowances are provided to facilitate installation in challenging locations while ensuring compliance with safety standards. Consider the impact of barriers on the internal volume when calculating the fill for electrical boxes. 44 / 50 When calculating box fill, should each space within a box installed with a barrier be calculated separately? a. False b. True Incorrect. The correct answer is True. Each space within a box with a barrier must be calculated separately for box fill. Correct! When calculating box fill, each space within a box installed with a barrier must be calculated separately according to NEC guidelines. According to NEC Article 314.16, when a box is provided with barriers, the volume of the box must be calculated separately for each compartment created by the barriers. This ensures that the fill calculations comply with the code’s requirements for conductor volume within electrical boxes. Consider the terminology used in the NEC to denote products that meet specific standards for compatibility with electrical insulation materials. 45 / 50 Spare or unused raceways shall be sealed with sealants _______ for use with the cable insulation, conductor insulation, bare conductor, shield, or other components. a. identified b. listed c. any of these d. approved Incorrect. The correct answer is identified. Sealants must be suitable for use with the insulation and components of the raceways. Correct! Spare or unused raceways must be sealed with sealants that are identified for use with the cable insulation, conductor insulation, and other components, as specified in NEC Article 300.7. According to NEC Article 300.7, spare or unused raceways must be sealed with sealants that are identified for use with the specific types of insulation, including cable insulation, conductor insulation, and other components. Therefore, the correct answer is identified. Think about the common materials used for electrical conductors in installations. 46 / 50 Conductors normally used to carry current shall be _____ unless otherwise provided in this code. a. none of these b. of copper or aluminum c. stranded d. bare Incorrect. The correct answer is of copper or aluminum. Conductors typically used for current carrying must be made from these materials unless stated otherwise in the code. Correct! Conductors that normally carry current shall be of copper or aluminum unless otherwise provided in the code, as stated in NEC Article 310.2 According to NEC Article 310.2, conductors that are normally used to carry current shall be of copper or aluminum unless otherwise specified by the code. Think about the minimum required extension to ensure proper installation and protection. 47 / 50 How far must the sheath of nonmetallic-sheathed cable or multiconductor Type UF cable extend inside the box and beyond any cable clamp? a. 1/2 in b. 3/8 in c. 3/4 in d. 1/4 in Incorrect. The correct answer is 1/4 in. The sheath must extend at least this distance for proper installation. Correct! The sheath of nonmetallic-sheathed cable or multiconductor Type UF cable must extend at least 1/4 inch inside the box and beyond any cable clamp according to NEC guidelines. According to NEC Article 314.25, when using nonmetallic-sheathed cable or multiconductor Type UF cable, the sheath must extend at least 1/4 inch inside the box and beyond any cable clamp to provide a secure and compliant installation. Think about the types of fire alarm cables and their regulatory requirements when installed in areas that might impact air quality and safety. 48 / 50 ______ fire alarm cables installed in ducts, plenums, or other spaces used for environmental air shall comply with 300.22. a. a and b b. power-limited c. none of these d. nonpower-limited Incorrect. The correct answer is a and b. NEC Article 300.22 states that both power-limited and nonpower-limited fire alarm cables must comply when installed in ducts, plenums, or other spaces used for environmental air. Correct! NEC Article 300.22 requires that fire alarm cables, whether power-limited or nonpower-limited, installed in ducts, plenums, or environmental air spaces must comply with the regulations outlined in this article. According to NEC Article 300.22, fire alarm cables, whether power-limited or nonpower-limited, that are installed in ducts, plenums, or spaces utilized for environmental air must adhere to the requirements specified in this section to prevent potential fire hazards and ensure safety. Consider which types of insulated conductors are specifically mentioned in the NEC as exceptions to ampacity adjustments. 49 / 50 Type __ insulated conductors shall not be subject to the ampacity adjustment provisions of 310.15(B)(3)(c). a. RHW-2 b. XHHW-2 c. THW-2 d. THWN-2 Incorrect. The correct answer is XHHW-2. This type of insulated conductor is exempt from the ampacity adjustment provisions in NEC Article 310.15. Correct! Type XHHW-2 insulated conductors are not subject to the ampacity adjustment provisions of NEC Article 310.15(B)(3)(c). According to NEC Article 310.15, Type XHHW-2 insulated conductors are not subject to the ampacity adjustment provisions outlined in 310.15(B)(3)(c). Therefore, the correct answer is XHHW-2. Consider the types of materials and standards that ensure safety and compliance for outdoor electrical installations. 50 / 50 Where exposed to the weather, raceways enclosing service-entrance conductors shall be _____ for use in wet locations and arranged to drain. a. approved b. a or b c. listed d. none of these Incorrect. The correct answer is a or b. Raceways must be either approved or listed for wet location use. Correct! Raceways enclosing service-entrance conductors exposed to the weather must be approved or listed for use in wet locations and arranged to drain, as specified in NEC Article 300.5. According to NEC Article 300.5, raceways that enclose service-entrance conductors and are exposed to the weather must be approved or listed for use in wet locations and should be arranged to drain effectively. Your score is LinkedIn Facebook Twitter 0% Restart quiz Exit Rate & Review Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services. Send feedback Leave a Reply Cancel replyYour email address will not be published. Required fields are marked * Comment* Name* Email* Website Save my name, email, and website in this browser for the next time I comment. Post Comment