What you’ll learn
After this post, you will be able to explain power factor, say what lagging and leading mean, work out why a low power factor costs money, and show how capacitors correct it — using the same 120 V circuit from the Power Triangle post.
Power factor: how much of the apparent power is useful
Power factor (PF) is the ratio of true power to apparent power: PF = P / S = cos θ (Eq. 9-4). It is a number between 0 and 1, with no unit. A power factor of 1 — unity power factor — means the load is purely resistive: voltage and current are in phase, and every volt-ampere does useful work. A power factor of 0 means no useful work at all: the load is purely reactive. Most real loads sit in between, and the lower the number, the more of the delivered power is borrowed and returned instead of used.
Lagging and leading
Power factor is not just a number — it has a direction. An inductive load (motors, transformers, coils) makes current lag voltage, so the power factor is lagging. A capacitive load makes current lead voltage, so the power factor is leading. Utilities and engineers say “0.8 lagging” or “0.9 leading” because the direction tells you what is causing it — and what will fix it. A lagging power factor is corrected with capacitors; a leading one with inductors.
The worked example: the same circuit, now as a bill
Take the Power Triangle post’s circuit again: 120 V, R = 3 Ω, XL = 4 Ω, Z = 5 Ω, I = 24 A, P = 1,728 W, Q = 2,304 VAR, S = 2,880 VA. Its power factor is PF = P / S = 1,728 / 2,880 = 0.6 — and because the load is inductive, it is 0.6 lagging. Only 60% of the apparent power does useful work. Now imagine the same 1,728 W of useful work delivered at unity power factor (PF = 1): the apparent power would be only 1,728 VA, and the current would be I = S / E = 1,728 / 120 = 14.4 A — instead of 24 A. Same work, 40% less current. That is the whole story of power factor in one number.
Why a low power factor costs money
A low power factor means more current for the same useful work, and more current means: larger conductors to carry it, larger transformers and generators to supply it, and higher I²R losses in every wire it flows through. The utility must build and run equipment sized for the apparent power, not just the true power — so many utilities charge industrial customers extra when their power factor is low. The handbook’s point is practical, not academic: a low power factor is a bigger, hotter, more expensive system doing the same work.
Correcting it: add capacitors
The fix for a lagging power factor is to add capacitors in parallel with the load. Capacitors supply reactive power of the opposite sign: their leading current cancels part of the inductive lagging current, shrinking the reactive power the source must deliver and raising the power factor toward unity. Back to the example circuit: it has Q = 2,304 VAR of inductive reactive power. Add capacitors that supply 2,304 VAR of capacitive reactive power, and the net reactive power becomes zero — the power triangle collapses to a single line, S = P = 1,728 VA, current falls from 24 A to 14.4 A, and the power factor becomes 1. In practice you rarely correct all the way to unity — a small margin is left, because over-correction swings the power factor leading — but the principle is the same: cancel the reactive power at the load, so the source does not have to carry it.
Common mistakes
- “Power factor is a percentage of efficiency.” It is not. PF = P / S = cos θ, a ratio between 0 and 1 with no unit — not the same as efficiency, which compares useful output to total input energy.
- “A power factor of 0.6 means 60% of the energy is wasted.” It does not. The other 40% is reactive power — stored in fields and returned each cycle, not lost as heat. It is carried, not wasted.
- “Lagging and leading are the same thing.” They are not. Lagging means current lags voltage (inductive load); leading means current leads voltage (capacitive load). The direction tells you the cause and the cure.
- “You fix a low power factor by adding resistance.” You do not. Adding resistance burns real power. You fix a lagging power factor by adding capacitors in parallel, which cancel reactive power without burning any.
- “Correcting to unity is always the goal.” Not quite. In practice a small margin is left — over-correction swings the power factor leading, which brings its own problems.
- “Power factor only matters to utilities.” It matters to anyone with a big inductive load: more current means larger conductors, larger equipment, and higher I²R losses — all paid for by someone.
- “A purely resistive load has a power factor of 0.” It has a power factor of 1 — unity. Voltage and current are in phase, and every volt-ampere does useful work.
Summary
Power factor is PF = P / S = cos θ, a number between 0 and 1 that says how much of the apparent power actually does work. Unity (1) is purely resistive; below 1, the missing part is reactive power, borrowed and returned. Inductive loads lag, capacitive loads lead, and the direction names the cure: capacitors correct a lagging power factor. In the handbook’s circuit, PF = 0.6 lagging — 24 A to do 1,728 W of work. Add 2,304 VAR of capacitors and the current falls to 14.4 A, the power factor becomes 1, and the same work costs the system far less.
Quick-check questions
- What is power factor, and what is its formula?
- What does a power factor of 1 mean? What does 0 mean?
- What is the difference between lagging and leading power factor?
- In the handbook’s example circuit, what is the power factor, and what current would the same work need at unity power factor?
- How do capacitors correct a lagging power factor?
Answers: 1. The ratio of true power to apparent power: PF = P / S = cos θ, a number between 0 and 1 with no unit. 2. PF = 1 (unity) means a purely resistive load: voltage and current in phase, every volt-ampere does useful work. PF = 0 means no useful work: a purely reactive load. 3. Lagging: current lags voltage (inductive load). Leading: current leads voltage (capacitive load). 4. PF = 1,728 / 2,880 = 0.6 lagging. At unity PF the same 1,728 W would need only S = 1,728 VA and I = 14.4 A, instead of 24 A. 5. Capacitors in parallel supply reactive power of the opposite sign, cancelling part of the inductive lagging current, shrinking the reactive power the source must deliver and raising PF toward unity.
Based on DOE-HDBK-1011/92, Electrical Science, Module 9, paraphrased for study.
Video lesson for this module is in production — coming soon.
Top 10 Scorers
| Pos. | Name | Score | Duration |
|---|---|---|---|
| There is no data yet |
What is power factor?
The ratio of true power to apparent power: PF = P / S = cos θ
Question Explanation:
Power factor (PF) is the ratio of true power to apparent power: PF = P / S = cos θ (Eq. 9-4). It is a number between 0 and 1, with no unit.
What does a power factor of 1 (unity) mean?
A purely resistive load: voltage and current in phase, every volt-ampere does useful work
Question Explanation:
A power factor of 1 — unity power factor — means the load is purely resistive: voltage and current are in phase, and every volt-ampere does useful work.
What is the difference between lagging and leading power factor?
Lagging: current lags voltage (inductive load). Leading: current leads voltage (capacitive load).
Question Explanation:
An inductive load (motors, transformers, coils) makes current lag voltage, so the power factor is lagging. A capacitive load makes current lead voltage, so the power factor is leading.
In the handbook's example circuit (P = 1,728 W, S = 2,880 VA, inductive load), what is the power factor?
0.6 lagging
Question Explanation:
PF = P / S = 1,728 / 2,880 = 0.6 — and because the load is inductive, it is 0.6 lagging. Only 60% of the apparent power does useful work.
At unity power factor, what current would the same 1,728 W of work need at 120 V?
14.4 A
Question Explanation:
At unity power factor (PF = 1), apparent power would be only 1,728 VA, and current I = S / E = 1,728 / 120 = 14.4 A — instead of 24 A. Same work, 40% less current.
Why does a low power factor cost money?
More current for the same useful work means larger conductors, larger equipment, and higher I²R losses — and utilities may charge extra
Question Explanation:
A low power factor means more current for the same useful work, and more current means larger conductors, larger transformers and generators, and higher I²R losses — so many utilities charge industrial customers extra when their power factor is low.
How do capacitors correct a lagging power factor?
They supply reactive power of the opposite sign, cancelling part of the inductive lagging current
Question Explanation:
Capacitors in parallel with the load supply reactive power of the opposite sign: their leading current cancels part of the inductive lagging current, shrinking the reactive power the source must deliver and raising the power factor toward unity.
How much capacitive reactive power would fully correct the example circuit, and what would the current become?
2,304 VAR of capacitors; current falls from 24 A to 14.4 A, PF becomes 1
Question Explanation:
Add capacitors that supply 2,304 VAR of capacitive reactive power, and the net reactive power becomes zero — S = P = 1,728 VA, current falls from 24 A to 14.4 A, and the power factor becomes 1.
Why is a load rarely corrected all the way to unity power factor?
Because over-correction swings the power factor leading, which brings its own problems
Question Explanation:
In practice a small margin is left, because over-correction swings the power factor leading — which brings its own problems.
- Tags:
- VOL3