What You’ll Learn
- What turns an arc into a blast: metal vaporizing and expanding 67,000 times in volume
- The temperatures involved — an arc terminal hotter than the surface of the sun
- The four ways a blast injures: pressure, sound, shrapnel, and toxic metal-oxide smoke
- Why arc-rated clothing, by itself, is not arc blast protection
- How to estimate blast pressure with Lee’s equation — and the caution that comes with it
The Arc Is Also a Bomb
An arc blast is the explosive side of an arcing fault. K.3 covers the arc’s thermal injury — the burn. K.4 covers what the same event does as an explosion. The tremendous temperatures of the arc cause the explosive expansion of both the surrounding air and the metal in the arc path, and the danger that follows is a combination of high pressures, sound, and shrapnel. A worker can be fully protected against the heat of an arc and still be thrown off a ladder, deafened, or struck by molten metal. That is the gap this article closes: the arc is not only a burn source, it is a pressure event.
Copper Expands 67,000 Times
The vaporization expansion of the conductor metal is the engine of the blast. When copper turns from a solid to a vapor, it expands by a factor of 67,000 times. Set that beside a familiar phase change: water expands 1,670 times when it becomes steam. The arc’s metal expansion is roughly forty times more violent than a steam explosion’s, and it happens essentially instantaneously, in the space the conductor occupied a moment before. The scale is easy to picture with the annex’s own figures: 53 kW of power will vaporize 0.05 in.³ of copper into 3,350 in.³ of vapor, and a single cubic inch of copper vaporizes into 1.44 cubic yards of vapor. This expansion also drives everything else in the event — it is what expels molten metal droplets from the arc, thrusting them up to distances around 10 ft, and it generates the ionized vapor — plasma — that radiates outward for distances proportional to the arc power.
Hotter Than the Surface of the Sun
The arc temperatures explain why the expansion is so extreme. The arc terminal temperature is estimated to be in excess of 35,000°F (19,430°C), and the plasma of vaporizing metal runs at about 23,000°F (12,760°C). The annex offers two comparisons to make those numbers land. After 0.3 seconds, an atomic bomb reaches only 12,600°F (6,980°C). The surface of the sun is only about 10,000°F (5,540°C). The air caught in this heat is superheated just as violently as the metal, and that superheating of air by the arc passing through it creates an acoustic wave — generated the same way thunder is generated by lightning.
Shrapnel at 700 Miles per Hour
The shrapnel hazard is the blast’s projectile. Material and molten metal are expelled away from the arc at speeds exceeding 1,120 km/h (700 mph) — fast enough for shrapnel to completely penetrate the human body. Molten droplets are thrust up to about 10 ft (3 m) from the arc, and the pressure behind them has propelled large objects — personnel, switchboard doors, and busbars — several feet at high rates of speed. This is not a hazard confined to the worker’s hands at the point of work; it fills the space in front of the equipment, which is exactly where the worker is standing.
Smoke Made of Poisoned Metal
The metal-oxide smoke is the hazard that lingers after the pressure wave passes. Before the hot vapor that forms the arc starts to cool, it combines with the oxygen in the air to become an oxide of the metal vapor. As it cools it solidifies into minute particles that appear as smoke — copper and iron oxides are black, and aluminum oxide is grey. Those particles are poisonous if inhaled, they are quite hot, and they will cling to any surface they touch. A worker who survives the blast unburned can still breathe a toxic dose of metal oxide in the seconds that follow, standing in the cloud the arc left behind.
Pressure That Breaks the Body
The blast pressure itself injures directly. The high pressures generated can easily exceed hundreds or even thousands of pounds per square foot. At those levels the annex lists the consequences plainly: pressures can knock workers off ladders, rupture eardrums, and collapse lungs. The sound wave compounds the pressure wave — an arc blast can create enough pressure to collapse lungs and rupture eardrums if hearing protection is not used. Note how different these injuries are from burns: they are mechanical and acoustic injuries, they can occur at distances where the thermal exposure is survivable, and some of them — a fall from a ladder after being knocked off balance — arrive a second after the arc itself is over.
Arc-Rated Is Not Blast-Rated
A limit of arc-rated clothing belongs in every discussion of this material. Protection against the arc flash hazards described in K.3 — the thermal exposure — can prevent incurable burns, and arc-rated garments are the answer to that hazard. But the annex’s enhanced content states the boundary explicitly: although arc-rated garments are available, they are not intended to provide arc blast protection. The concussive forces, sounds, and shrapnel of a blast event are a separate hazard set, and clothing selected for a calorie rating does not answer them. Distance, pressure awareness, and hearing protection do the work that the garment cannot.
Worked Scenario
An engineer is reviewing a switching procedure for a 25 kA fault-level lineup and wants the crew to understand — in numbers, not adjectives — why nobody stands directly in front of the equipment at arm’s length during the operation. She uses the pressure equation from Ralph H. Lee’s IEEE paper “Pressures Developed by Arcs,” which the annex reproduces: P = (11.5 × Ia) / D^0.9, where P is pressure in lb/ft², Ia is arcing current in kA, and D is distance from the center of the arc in feet. First she checks the equation against the annex’s reference case: a 100-kA arc produces a pressure of around 400 lb/ft² at a distance of 3.3 ft (1 m). Then she runs the crew’s actual case. A 25-kA arc at a distance of 2 ft (0.6 m) produces a pressure of around 160 lb/ft². That number alone sounds abstract, so she converts it to force on a body: the average man’s upper body has about 2.2 ft² of surface area, and 2.2 ft² × 160 lb/ft² ≈ 352 lb of total force on the worker’s chest — the equivalent of being struck by a 352-pound blow, at the distance a worker naturally stands to operate the gear. She also gives the crew Lee’s caution along with his equation: the equation has not been generally adopted and additional testing is required, so the figures are estimates for building respect for distance, not design values. The procedure is rewritten so the operation is done from the side, at the greatest practical distance.
Common Mistakes and Safety Notes
- Assuming arc-rated PPE covers the blast. Arc-rated garments address the thermal hazard; they are not intended to provide arc blast protection against pressure, sound, and shrapnel.
- Standing squarely in front of the gear at close range. Pressure falls with distance, and at 2 ft even a moderate 25 kA arc delivers roughly 352 lb of force to a worker’s chest.
- Forgetting the smoke. The vaporized metal oxidizes into fine particles that are poisonous if inhaled, hot, and cling to surfaces — the hazard remains after the bang.
- Skipping hearing protection because “it’s only a switching job.” Blast pressure can rupture eardrums and collapse lungs; the acoustic wave is generated like thunder.
- Treating Lee’s equation as settled engineering. The annex notes the equation has not been generally adopted and additional testing is required — use it to estimate and to teach, not as a precise prediction.
- Thinking only the operator is at risk. Molten metal travels up to about 10 ft, and blast pressure has thrown doors, busbars, and people several feet — bystanders in front of the equipment are inside the event.
Summary
An arc blast is the explosive half of an arcing fault. Arc temperatures above 35,000°F vaporize the conductor metal, and copper expanding 67,000 times in volume — together with superheated air — produces pressures that can exceed hundreds or thousands of pounds per square foot, an acoustic wave like thunder, molten shrapnel moving faster than 700 mph, and a cloud of toxic metal-oxide smoke. The pressure can knock workers off ladders, rupture eardrums, and collapse lungs, and arc-rated clothing, for all its value against burns, is not intended to protect against any of it. Lee’s equation, P = (11.5 × Ia) / D^0.9, lets you put an estimated number on the pressure — about 400 lb/ft² for a 100-kA arc at 3.3 ft, and about 160 lb/ft², some 352 lb against a worker’s chest, for a 25-kA arc at 2 ft — with the annex’s own caution that the equation is not generally adopted and needs more testing behind it.
Quick-Check Questions
1. By what factor does copper expand when it turns from a solid to a vapor?
Answer: 67,000 times — compared with 1,670 times for water turning to steam.
2. How hot is the arc, compared with familiar references?
Answer: The arc terminal temperature exceeds 35,000°F (19,430°C) — hotter than the surface of the sun at about 10,000°F, and hotter than an atomic bomb reaches after 0.3 seconds (12,600°F).
3. What does Lee’s equation estimate, and from what inputs?
Answer: Arc blast pressure P in lb/ft², from arcing current Ia in kA and distance D in feet: P = (11.5 × Ia) / D^0.9.
4. A worker’s chest (about 2.2 ft²) is 2 ft from a 25-kA arc. What force does he face?
Answer: The pressure is about 160 lb/ft², which works out to roughly 352 lb of total force on the chest (2.2 ft² × 160 lb/ft²).
5. Does an arc-rated garment protect the worker against an arc blast?
Answer: No. Arc-rated garments protect against the thermal hazard of arc flash; they are not intended to provide arc blast protection against pressure, sound, and shrapnel.
Based on NFPA 70E (2024), Informative Annex K, paraphrased for study.