eep April 7, 2025 NEC 100-110 NEC Quizzes Report a question What’s wrong with this question? You cannot submit an empty report. Please add some details. 0% Article 100-110 Quiz05 This quiz includes 20 questions selected from NEC Articles 100 to 110. The questions are chosen randomly, with no repeats from other quizzes—unless a particular question is used again on purpose because it relates to more than one topic, such as both cable ampacity and cable application. If you spot any issues or have suggestions, you’re welcome to report questions or review the quiz. Your feedback matters, and contributions to help improve and refine the questions and quizzes are always appreciated. Consider the NEC’s requirement for ensuring reliable manual control of lighting in working spaces around electrical equipment. 1 / 25 Is it true that control of all the illumination for the working space is not permitted to be by automatic systems only? a. False b. True Incorrect. NEC 110.26(D) specifies that working space illumination cannot be controlled solely by automatic systems; manual control must also be provided. Correct! NEC 110.26(D) ensures that illumination for working spaces must have a manual control option and cannot be solely automatic. NEC 110.26(D) requires that the illumination for the working space must not rely solely on automatic controls. There must be a manual method available to ensure that the working space can be adequately lit whenever needed, enhancing safety during maintenance or emergency situations. Consider the name given to the overhead conductors that connect the utility’s supply system to the service point at a building. 2 / 25 What are the overhead service conductors between the utility electric supply system and the service point called? a. Service-Entrance Conductors, Underground b. Service Lateral c. Service Drop d. Service-Entrance Conductors, Overhead “Incorrect. The correct term for the overhead service conductors between the utility supply system and the service point is ‘Service Drop,’ as defined in NEC Article 100.” “Correct! The overhead service conductors between the utility supply system and the service point are called the ‘Service Drop,’ as defined in NEC Article 100.” The Service Drop consists of the overhead service conductors that connect the utility supply system to the service point at the customer’s premises. These conductors are typically installed by the utility and carry electrical power from the overhead distribution lines to the building where the service entrance begins. Consider the minimum NEC-required working space width for equipment to ensure proper clearance. 3 / 25 For equipment with a width equal to or less than 30 inches, is it true that the working space must be at least 30 inches wide? a. False b. True Incorrect. NEC 110.26(A)(2) requires a minimum working space width of 30 inches for equipment with a width of 30 inches or less. Correct! NEC 110.26(A)(2) specifies that equipment with a width of 30 inches or less must have a working space with a minimum width of 30 inches. According to NEC 110.26(A)(2), for equipment that is 30 inches wide or less, the minimum width of the working space in front of it must be at least 30 inches. This ensures adequate room for electricians to access the equipment safely. Think about the NEC section that outlines specific requirements for electrical equipment installed outdoors, ensuring proper clearance and access. 4 / 25 Where in the NEC is the dedicated equipment space for outdoor installations referenced? a. 110.26(A) b. 110.26(E)(2) c. 110.8 d. 110.26(E) “Incorrect. The dedicated equipment space for outdoor installations is specifically addressed in NEC 110.26(E)(2).” “Correct! NEC 110.26(E)(2) refers to the dedicated equipment space requirements for outdoor electrical installations.” NEC 110.26(E)(2) covers the requirements for dedicated equipment space for electrical installations located outdoors. This ensures that outdoor electrical equipment has adequate space for maintenance, ventilation, and safety, just as indoor equipment does. Clearances must be maintained around outdoor equipment to allow safe access for servicing. Consider the NEC’s required clearance to ensure safe access to electrical panels for maintenance and operation. 5 / 25 What is the minimum working space required for a 120-volt panel? a. 4 ft b. 2 ft c. 1 ft d. 3 ft Incorrect. NEC 110.26(A)(1) requires at least 3 feet of working space in front of a 120-volt panel to ensure safe access. Correct! NEC 110.26(A)(1) specifies that a 120-volt panel requires at least 3 feet of working space in front of it. According to NEC 110.26(A)(1), a minimum of 3 feet of working space is required in front of a 120-volt panel. This clearance ensures that electricians and technicians have enough space to safely work on the panel without obstruction. Think about where the NEC provides general definitions for key electrical terms used throughout the code. 6 / 25 Where can the definition of a panelboard be found in the NEC? a. Article 210 b. Article 90 c. Article 100 d. Article 215 Incorrect. The definition of a panelboard can be found in NEC Article 100, which contains definitions of key electrical terms. Correct! The definition of a panelboard is found in NEC Article 100, which provides general definitions for electrical equipment and systems. NEC Article 100 provides the definition of a panelboard, along with other essential electrical terms. Panelboards are components used to control and distribute electrical power to various branch circuits, and Article 100 is where this term is officially defined. Think about the voltage-to-ground in a 120/240V delta-connected system with a grounded transformer and a high-leg (B phase). 7 / 25 In a delta-connected system with one transformer grounded, the B phase is commonly referred to as the “high-leg,” “red-leg,” or “wild-leg.” What is the voltage to ground when testing the B phase? a. 120 b. 347 c. 208 d. 277 Incorrect. In a delta-connected system with one transformer grounded, the high-leg (B phase) has a voltage of 208 volts to ground. Correct! In a delta-connected system with a grounded transformer, the B phase (high-leg) has a voltage of 208 volts to ground. In a delta-connected system with one transformer grounded, the B phase (also known as the high-leg, red-leg, or wild-leg) has a voltage of 208 volts to ground. This occurs in 120/240V systems and is a key characteristic of delta systems with a grounded transformer. Think about the distance requirement for visibility and proximity of equipment as defined by the NEC. 8 / 25 “Within sight” is defined as the specified equipment being visible and no more than how many feet from the other? a. 25 b. 50 c. 100 d. 75 “Incorrect. NEC Article 100 defines ‘within sight’ as equipment being visible and no more than 50 feet apart.” “Correct! ‘Within sight’ is defined by NEC Article 100 as being no more than 50 feet away and visible from the associated equipment.” According to NEC Article 100, “within sight” means that one piece of equipment must be visible from and no more than 50 feet away from the other. This requirement ensures that someone working on the equipment can see and access the associated disconnect or control device without obstruction, enhancing safety during operation and maintenance. Look for the NEC sections that discuss how much working space is needed around electrical equipment to ensure safety. 9 / 25 Which NEC section covers working space requirements? a. 110.26(A) b. 110.27 c. 110.26(B) d. 110.26(C)(3) “Incorrect. The working space requirements are primarily addressed in NEC 110.26(A) and NEC 110.26(B), which provide clearances for safe access to electrical equipment.” “Correct! NEC 110.26(A) and NEC 110.26(B) both cover working space requirements around electrical equipment.” NEC 110.26(A) specifies the general working space clearances required around electrical equipment, depending on the voltage and installation conditions. NEC 110.26(B) addresses clear spaces and ensures that nothing obstructs the working space around electrical equipment. These sections ensure that there is enough room for safe maintenance and operation of electrical systems. Consider the NEC section that defines how much vertical clearance is needed in front of electrical equipment to ensure proper working space. 10 / 25 Which NEC section covers the height of the working space? a. 110.26(A)(3) b. 110.26(B) c. 110.26(A)(2) d. 110.26(A)(1) “Incorrect. The NEC section that addresses the height of working space is 110.26(A)(3), which specifies the vertical clearance needed in front of electrical equipment.” “Correct! NEC 110.26(A)(3) covers the height requirements for the working space around electrical equipment, ensuring proper clearance.” NEC 110.26(A)(3) outlines the minimum height requirement for the working space around electrical equipment. It ensures that the working space extends from the floor to a height of at least 6 ½ feet or the height of the equipment, whichever is greater, providing sufficient space for safe access and maintenance. Consider the NEC requirements for working space in front of electrical equipment, especially when the equipment’s width is 30 inches or less. 11 / 25 For equipment with a width equal to or less than 30 inches, is it required to provide a working space with a width of not less than 30 inches? a. True b. False “Incorrect. NEC 110.26(A)(2) requires that for equipment 30 inches wide or less, the working space must still be at least 30 inches wide for safe access.” “Correct! According to NEC 110.26(A)(2), for equipment 30 inches wide or less, the working space must still be at least 30 inches in width.” NEC 110.26(A)(2) specifies that the minimum width of the working space in front of electrical equipment must be at least 30 inches, even if the equipment itself is narrower. If the equipment width exceeds 30 inches, the working space must match that width. This ensures there is enough space for safe access and work on the equipment. Consider the NEC requirements for maintaining the integrity of enclosures by closing unused openings. 12 / 25 Is it true that unused openings, other than those intended for equipment operation, mounting purposes, or permitted as part of the design for listed equipment, must be closed to provide protection equivalent to the equipment’s wall? a. True b. False “Incorrect. NEC 110.12(A) requires that unused openings in electrical equipment be closed to provide protection equivalent to the wall of the equipment, preventing hazards such as dust or moisture from entering.” “Correct! NEC 110.12(A) mandates that unused openings in electrical equipment must be closed to offer protection equivalent to the equipment’s wall.” NEC 110.12(A) states that any unused openings in electrical equipment, unless intended for operation, mounting, or as part of the listed equipment’s design, must be closed to offer protection that is substantially equivalent to the wall of the equipment. This ensures that the electrical enclosure remains safe from environmental hazards and maintains its structural integrity. Look for the NEC requirement regarding the minimum working space for electrical panels to ensure safe access for workers. 13 / 25 What is the minimum required working space in front of a 120-volt panel? a. 1 ft b. 2 ft c. 3 ft d. 4 ft “Incorrect. NEC 110.26(A)(1) specifies that the minimum working space in front of a 120-volt panel must be at least 3 feet to ensure safe access for maintenance and operation.” “Correct! According to NEC 110.26(A)(1), the minimum required working space in front of a 120-volt panel is 3 feet.” NEC 110.26(A)(1) requires a minimum of 3 feet of working space in front of electrical equipment, including 120-volt panels, to provide adequate room for maintenance, troubleshooting, and safe operation. This clearance helps prevent accidents and ensures that workers have enough space to safely work on or around the panel. Look for the NEC section that outlines the safety requirements for access to and from working spaces around electrical equipment. 14 / 25 Which NEC section covers the minimum entrance to and egress from working space? a. 110.26(C)(2) b. 110.26(A)(3) c. 110.26(B) d. 110.26(C)(1) “Incorrect. NEC 110.26(C)(1) specifies the requirements for entrance and egress to working spaces to ensure safe access for personnel.” “Correct! NEC 110.26(C)(1) covers the minimum entrance to and egress from working space around electrical equipment.” NEC 110.26(C)(1) outlines the minimum requirements for entrances and egress from working spaces around electrical equipment. This section ensures that workers have sufficient room to safely enter and exit the area, particularly in case of an emergency, and that the entrance space is unobstructed. Consider the NEC’s requirement to follow the manufacturer’s labeling and instructions for electrical equipment. 15 / 25 If equipment is marked with a maximum fuse size only rather than an overcurrent device, is it true that a circuit breaker should not be used? a. True b. False Incorrect. If equipment is marked with a maximum fuse size, only fuses should be used. Substituting a circuit breaker could compromise the equipment’s safety and protection. Correct! According to NEC 110.3(B), if the equipment is marked with a maximum fuse size only, a circuit breaker should not be used as a substitute. According to NEC 110.3(B), if equipment is labeled with a specific maximum fuse size, only fuses should be used, and circuit breakers cannot be substituted. The equipment has been tested and rated for specific overcurrent protection, and using a circuit breaker instead of a fuse may lead to improper protection and unsafe conditions. Think about the conditions outdoor electrical equipment faces, and why enclosures are necessary to protect the equipment from environmental hazards. 16 / 25 Must outdoor electrical equipment be installed in suitable enclosures? a. no b. Yes “Incorrect. NEC 110.28 requires that outdoor electrical equipment must be installed in suitable enclosures to protect it from environmental factors such as moisture, dust, and weather.” “Correct! NEC 110.28 specifies that outdoor electrical equipment must be installed in suitable enclosures to protect it from environmental hazards.” According to NEC 110.28, outdoor electrical equipment must be installed in enclosures that are appropriate for the environment. These enclosures are designed to protect the equipment from exposure to rain, dust, and other elements that could damage the equipment or cause electrical hazards. The use of suitable enclosures ensures that the equipment remains safe and functional in outdoor conditions. Look at NEC Table 110.26(A)(1) for the clearance requirements based on voltage and the type of wall or surface in front of the equipment. 17 / 25 According to Table 110.26(A)(1), how much working space must be provided in front of a 480/277-volt dead front switchboard that faces a concrete block wall? a. 3 ft b. 3 1/2 ft c. 4 1/2 ft d. 4 ft “Incorrect. NEC Table 110.26(A)(1) specifies that the working space in front of a 480/277-volt dead front switchboard facing a concrete block wall must be 3 1/2 feet.” “Correct! The working space in front of a 480/277-volt dead front switchboard facing a concrete block wall must be 3 1/2 feet, as per NEC Table 110.26(A)(1).” According to NEC Table 110.26(A)(1), for electrical equipment rated 480/277 volts that faces a concrete block wall, the required working space in front of the switchboard is 3 1/2 feet. This clearance ensures that there is enough room for workers to safely perform maintenance and operations on the equipment. Look at the characteristics of delta-connected systems with a grounded transformer. The B phase, also known as the “wild-leg,” will have a distinct voltage to ground compared to the other phases. 18 / 25 In a delta-connected system with one transformer grounded, the system creates a “high-leg,” “red-leg,” or “wild-leg” on the B phase. What is the voltage to ground when testing the B phase? a. 208 b. 120 c. 347 d. 277 “Incorrect. The voltage to ground on the B phase, or high-leg, in a delta-connected system is typically 208 volts. This is higher than the 120 volts seen on the other phases.” “Correct! In a delta-connected system with a grounded transformer, the B phase, or ‘high-leg,’ has a voltage to ground of 208 volts.” In a delta-connected system with one transformer grounded, a “high-leg” or “wild-leg” is created on the B phase. The voltage from the high-leg to ground in a standard 120/240V system is typically 208 volts. This is higher than the voltage from the other phases to ground, which is 120 volts. The high-leg must be identified per **NEC 110.15** to avoid confusion and ensure safety during installation and maintenance. Look for the NEC sections that address safety measures for personnel doors near large electrical equipment, ensuring safe egress in emergencies. 19 / 25 Which NEC section covers the requirements for personnel doors? a. 110.26(E)(2) b. 110.26(E)(1) c. 110.26(D) d. 110.26(C)(3) “Incorrect. The requirements for personnel doors are found in both NEC 110.26(C)(3) and NEC 110.26(E)(1), ensuring quick and safe egress near high-rated electrical equipment.” “Correct! NEC 110.26(C)(3) and NEC 110.26(E)(1) both cover the requirements for personnel doors, particularly in areas with large electrical equipment, ensuring safe egress.” NEC 110.26(C)(3) and NEC 110.26(E)(1) specify the requirements for personnel doors in electrical rooms and spaces. These sections ensure that personnel doors allow for quick and safe exit from areas with high-rated electrical equipment. The doors must swing outwards or be equipped with panic hardware to facilitate rapid egress, particularly in emergency situations. Look for the NEC section that specifies the requirements for clear and dedicated space around indoor electrical equipment to allow for safe access and maintenance. 20 / 25 Which NEC section covers indoor dedicated equipment space? a. 110.26(E)(1) b. 110.26(D) c. 110.26(C)(3) d. 110.26(E)(2) “Incorrect. NEC 110.26(E)(1) specifically covers the requirements for dedicated equipment space for indoor electrical installations.” “Correct! NEC 110.26(E)(1) goes over the requirements for indoor dedicated equipment space, ensuring safe and unobstructed access for maintenance.” NEC 110.26(E)(1) specifies the requirements for dedicated equipment space for indoor installations. It ensures that space is reserved above and around electrical equipment for access, servicing, and maintenance, preventing the installation of other equipment or materials in that space, which could obstruct access or compromise safety. Consider the NEC’s requirement to protect outdoor electrical equipment from environmental conditions. 21 / 25 Is it true that outdoor electrical equipment must be installed in suitable enclosures? a. False b. True Incorrect. NEC 110.28 requires outdoor electrical equipment to be installed in suitable enclosures to protect it from environmental conditions. Correct! NEC 110.28 specifies that outdoor electrical equipment must be installed in suitable enclosures to protect it from the elements. According to NEC 110.28, outdoor electrical equipment must be installed in suitable enclosures to protect it from weather, moisture, and other environmental factors. The enclosure must meet the necessary ratings for the specific conditions where the equipment is installed to ensure safe and reliable operation. Consider the specific color required by the NEC for identifying the high-leg in a delta-connected system. 22 / 25 With a “wild leg” in a delta-connected system, the conductor is generally required to be identified with what color insulation or marking? a. Blue b. Orange c. Black d. Red Incorrect. The NEC requires the high-leg (wild leg) conductor to be identified with orange insulation or marking. Correct! The ‘wild leg’ or high-leg in a delta-connected system is required to be identified with orange insulation or marking, as per NEC 110.15. In a delta-connected system with a high-leg (wild leg), the NEC requires that the high-leg conductor be identified with orange insulation or marking. This identification ensures that the high-leg is easily recognizable, especially in systems where the voltage to ground is higher on this conductor. Look for the NEC section that specifically addresses maintaining clear and unobstructed spaces around electrical equipment. 23 / 25 Which NEC section covers clear spaces? a. 110.26(A)(3) b. 110.26(A)(1) c. 110.26(A)(2) d. 110.26(B) “Incorrect. The NEC section that covers clear spaces is 110.26(B), which ensures safe, unobstructed access around electrical equipment.” “Correct! NEC 110.26(B) covers the clear spaces required around electrical equipment to ensure safe access and working conditions.” NEC 110.26(B) focuses on the requirement for clear spaces around electrical equipment. This section ensures that areas around the equipment are kept free from obstructions to provide safe working conditions and easy access for maintenance or servicing. These clearances are vital for safety and operational efficiency. Think about the NEC’s requirement for equipment doors and panels to open fully to allow for safe access and servicing. 24 / 25 All working spaces must allow for the opening of equipment doors and hinged panels to at least a ___° position. a. 180° b. 30° c. 45° d. 90° ncorrect. NEC 110.26(A)(2) requires that equipment doors and hinged panels must be able to open to at least 90 degrees for safe access. Correct! NEC 110.26(A)(2) specifies that equipment doors and panels must be able to open to at least a 90-degree position. According to NEC 110.26(A)(2), all working spaces around electrical equipment must allow doors and hinged panels to open to at least 90 degrees. This clearance ensures safe and convenient access to the equipment during maintenance and troubleshooting. The section where common electrical terms and their definitions are found in the NEC. 25 / 25 Where can the definition of a panelboard be found in the NEC? a. Article 215 b. Article 210 c. Article 100 d. Article 90 “Incorrect. The definition of a panelboard is found in Article 100, which contains general definitions used throughout the NEC. Articles 210 and 215 cover specific circuit and feeder requirements, while Article 90 is an introduction to the NEC.” “Correct! The definition of a panelboard can be found in NEC Article 100, which is where general terms and definitions are located.” *NEC Article 100* contains the definitions of key terms used in the NEC, including the definition of a panelboard. A panelboard is a component of the electrical distribution system that serves to distribute power to different branch circuits. It typically contains circuit breakers or fuses to provide overcurrent protection. Your score is LinkedIn Facebook Twitter 0% Restart quiz Exit Rate & Review Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services. Send feedback Leave a Reply Cancel replyYour email address will not be published. Required fields are marked * Comment* Name* Email* Website Save my name, email, and website in this browser for the next time I comment. Post Comment