Report a question

You cannot submit an empty report. Please add some details.
0%

Article 200-285 Part04

This comprehensive quiz contains 50 questions carefully selected from the National Electrical Code (NEC) Articles spanning 200 through 285. These articles cover a broad spectrum of vital topics related to electrical installations within this section of the code.

The questions in this quiz are chosen randomly to provide a thorough assessment of your knowledge across these essential NEC articles. While we strive for a diverse set of questions, some fundamental principles may be revisited in different contexts due to their relevance to multiple sections within this range. This approach ensures a robust evaluation of your understanding.

We encourage you to actively participate and provide feedback. If you identify any issues or have suggestions for improving the quiz questions, please report them. Your contributions are invaluable in helping us maintain the accuracy and effectiveness of these learning resources.

This voltage is commonly used in residential electrical systems.

1 / 50

Optional feeder and service load calculations shall be permitted for a dwelling unit having a load served by a _______________ set of 3-wire service conductors.

Grounded conductors are typically identified with specific markings or colors.

2 / 50

An insulated grounded conductor of 4 AWG or larger shall be identified by which one of the following means:

The size of the equipment grounding conductor depends on the ampere rating of the overcurrent protective device protecting the feeder.

3 / 50

What is the minimum size equipment grounding conductor (EGC) required for a feeder consisting of (2) 250 kcmil THWN-2 ungrounded conductors and (2) 250 kcmil THWN-2 grounded conductors protected by a 250-ampere overcurrent protective device (OCPD)?

The NEC provides specific guidance on when conductors are considered “outside the building” for safety and installation requirements.

4 / 50

Conductors shall be considered _______________ when installed in conduit and under not less than 18 inches of earth beneath a building or other structure.

The minimum clearance ensures safety for pedestrians and prevents accidental contact with overhead conductors.

5 / 50

Overhead service conductors shall have a minimum clearance of _______________ feet from final grade above pedestrian sidewalks.

The NEC assigns a standard value for the laundry circuit load to ensure proper service capacity.

6 / 50

When calculating a service load, a load of not less than _______________ volt-amperes shall be included for each 2-wire laundry branch circuit installed.

The grounding electrode conductor size depends on the ampacity of the service and the material of the conductor.

7 / 50

A single-phase, 3-wire, 200-amp service is constructed at a residence. What size copper grounding electrode conductor needs to be installed on this service?

The NEC requires a specific conductor to be connected to the screw shell to minimize the risk of electrical shock.

8 / 50

For devices with screw shells, the terminal for the _______________ conductor shall be connected to the screw shell.

Grounding is required for fixed equipment with certain voltage characteristics to ensure safety.

9 / 50

Exposed, normally non-current-carrying metal parts of fixed equipment supplied by or enclosing conductors or components that are likely to become energized shall be connected to an equipment grounding conductor under which of the following conditions:

Consider the NEC rule limiting the number of manual operations required for disconnecting all ungrounded conductors.

10 / 50

Two single-pole switches capable of individual operation shall be permitted on multiwire circuits provided they are equipped with identified handle ties to disconnect all ungrounded conductors _______________.

The EGC size increases with the ampere rating of the circuit to ensure safe fault current paths.

11 / 50

The minimum sized Equipment Grounding Conductor (EGC) required to ground equipment served by a 40-ampere rated branch circuit is _______________ AWG.

The bonding jumper must ensure a continuous low-impedance path between the generator and the disconnecting means.

12 / 50

A(n) _______________ shall be installed between the generator equipment grounding terminal and the equipment grounding terminal of the disconnecting means.

The supply-side bonding jumper size is related to the ungrounded conductor size in the derived system.

13 / 50

In a separately derived system, a supply-side bonding jumper shall not be required to be larger than the _______________ conductors.

Consider user safety and ease of operation when accessing the circuit breaker handle.

14 / 50

The operating handle of a circuit breaker shall be permitted to be accessible _______________ opening a door or cover.

The NEC requires GFCI protection for receptacles located near sinks to prevent electric shock hazards.

15 / 50

In a bathroom, where receptacles are installed within 6 feet from the _______________ edge of the bowl of a sink, they must be GFCI protected.

NEC Article 220.56 allows demand factors for loads like water heaters, ovens, and fryers in commercial kitchens.

16 / 50

The feeder/service calculated load for (2) 15 kW water heaters, (1) 3 kW oven, and (1) 2 kW deep fryer in a commercial kitchen is _______________.

For continuous loads, the NEC requires an additional percentage to ensure the overcurrent protection device is not overloaded.

17 / 50

Where a branch circuit supplies continuous loads or any combination of continuous and non-continuous loads, the rating of the overcurrent device shall not be less than the non-continuous load plus _______________ percent of the continuous load.

The NEC requires a minimum separation to prevent physical contact and interference between conductors of different circuits.

18 / 50

Open outside branch circuit conductors shall be separated from open conductors of other circuits or systems by not less than:

The NEC provides a specific list of standard ampere ratings for overcurrent protection devices.

19 / 50

______________ are standard ampere ratings for fuses and inverse time circuit breakers.

The NEC assigns a specific VA value per foot for multi-outlet assemblies in different applications.

20 / 50

The total calculated load for 50 feet of non-simultaneous multi-outlet assembly installed in a retail store is _______________.

The number of feeders permitted to share a neutral depends on the configuration of the wiring system.

21 / 50

Up to three sets of 3-wire feeders or _______________ sets of 4-wire or 5-wire feeders shall be permitted to utilize a common neutral.

Concrete-encased electrodes must meet specific size and material requirements to ensure effective grounding.

22 / 50

A concrete-encased electrode shall consist of at least 20 feet of:

The size of the equipment grounding conductor is based on the rating of the overcurrent protection device.

23 / 50

A single-family dwelling has a single-phase 125-ampere sub-panel in the garage with a main breaker rated at 125 amperes. What size equipment grounding conductor shall be used to feed the sub-panel?

Type 1 SPDs must be properly bonded to ensure effective surge protection at the service.

24 / 50

When installed at services, Type 1 SPDs shall be connected to which of the following?

Grounding electrode conductor size increases as the size of the ungrounded service-entrance conductors increases.

25 / 50

A 1/0 copper grounding electrode conductor is used for what size ungrounded service-entrance conductors?

Multi-wire branch circuits are designed to share a common neutral conductor.

26 / 50

Multi-wire branch circuits shall supply only _______________.

Supplementary overcurrent protection provides additional safety but does not replace mandatory branch-circuit protection.

27 / 50

Where supplementary overcurrent protection is used for appliances, it _______________ as a substitute for required branch-circuit overcurrent devices.

This type of system requires careful grounding to manage faults and ensure proper overcurrent device operation.

28 / 50

In a(n) _______________ system, electrical equipment, wiring, and other electrically conductive material likely to become energized shall be installed in a manner that creates a low-impedance circuit from any point on the wiring system to the electrical supply source to facilitate the operation of overcurrent devices should a second ground fau

The NEC limits the load on receptacles to ensure safety and compliance with continuous load requirements.

29 / 50

Where connected to a branch circuit supplying two or more receptacles or outlets, a 30-ampere receptacle shall not supply a total cord-and-plug connected load in excess of:

The NEC permits smaller conductors in specific scenarios where additional support is provided.

30 / 50

Overhead conductors for festoon lighting shall not be smaller than 12 AWG unless the conductors are:

The NEC mandates service receptacle outlets for specific equipment types, but certain exclusions exist.

31 / 50

A receptacle outlet is not required at one- and two-family dwellings for the service of _______________.

Floor receptacles need to be within a certain distance of the wall to count as part of the required receptacle outlets.

32 / 50

Receptacle outlets in or on floors shall not be counted as part of the required number of receptacle outlets unless located within _______________ inches of the wall.

The size of the grounding electrode conductor depends on the largest ungrounded conductor in the service entrance.

33 / 50

A single-phase, 3-wire, 240-volt service has (2) 2/0 THHN ungrounded service entrance conductors. What is the minimum size grounding electrode conductor that must be installed?

Convert VA to Amperes: Using a 240-volt system:

Amperes=Total VAVoltage=19,525240≈81.35 amps\text{Amperes} = \frac{\text{Total VA}}{\text{Voltage}} = \frac{19,525}{240} \approx 81.35 \, \text{amps}

34 / 50

A single-family dwelling out in the country has a floor area of 1500 square feet, with no garage. Appliances are a 10-kW range and a 6-kW, 240-volt dryer. There are no heating or air conditioning loads, nor a dishwasher or garbage disposal. Using the standard method, calculate the minimum size feeder required for this dwelling.

35 / 50

The strength of the electromagnetic field surrounding a conductor will _______________ with a(n) _______________ in current flow through the conductor.

Shorter tap conductors are permitted under specific NEC rules when they remain within the equipment they supply.

36 / 50

Tap conductors not over _______________ feet do not extend beyond the switchboard or control devices they supply.

This percentage ensures that the branch circuit can safely accommodate other loads.

37 / 50

The rating of any one cord-and-plug-connected utilization equipment not fastened in place shall not exceed _______________ percent of the branch-circuit ampere rating.

Metal covers must ensure proper grounding when installed in junction boxes.

38 / 50

Where used, metal covers for junction boxes shall:

The NEC specifies a standard lighting load in volt-amperes (VA) per square foot for dwelling units.

39 / 50

What is the general lighting load for a 2,000 square foot dwelling unit?

Tap conductor ampacity must always meet or exceed the calculated load to ensure safe operation.

40 / 50

The ampacity of tap conductors not over 10 feet is _______________ than the combined calculated loads supplied by the tap conductors.

The size of the supply-side bonding jumper is determined by the largest ungrounded conductor.

41 / 50

A generator is fed with (2) 250 kcmil copper ungrounded conductors. This generator shall have what sized minimum supply-side bonding jumper?

The grounding conductor in the MC cable must meet specific NEC requirements to function as an EGC.

42 / 50

Type MC cable that contains a(n) _______________ or uninsulated EGC can be used as an EGC.

The NEC allows a demand factor to be applied to the total connected load for commercial cooking equipment.

43 / 50

Determine the demand load of the service-entrance conductors for a restaurant kitchen that contains the following cooking equipment:

  • (1) 14 kW range
  • (1) 5 kW water heater
  • (1) 750 W mixer
  • (1) 2500 W dishwasher
  • (1) 2 kW booster heater
  • (1) 2 kW broiler

The size of the main bonding jumper is based on the size of the largest ungrounded service entrance conductor.

44 / 50

A 3-phase 240-volt service fed with (3) 2/0 aluminum conductors shall have a minimum size main bonding jumper of what size?

This rule applies when multiple types of loads are connected to a single branch circuit.

45 / 50

The total rating of utilization equipment fastened in place shall _______________ of the branch-circuit ampere rating where lighting units, cord-and-plug-connected utilization equipment not fastened in place, or both, are also supplied.

The NEC mandates a minimum number of circuits to ensure sufficient capacity for typical kitchen appliances.

46 / 50

Receptacles installed in a kitchen to serve countertop surfaces shall be supplied by not fewer than _______________ small-appliance branch circuits.

Consider the importance of having a low-impedance path for fault current to ensure the proper operation of overcurrent protection devices.

47 / 50

The earth _______________ considered as an effective fault-current path.

The size of the supply-side bonding jumper depends on the cross-sectional area of the ungrounded conductors it serves.

48 / 50

The supply-side bonding jumper for a 240-volt single-phase service fed with (2) 300 kcmil aluminum ungrounded conductors is _______________ aluminum.

The NEC limits the number of disconnecting means to ensure safety and simplicity in disconnecting power during maintenance or emergencies.

49 / 50

The service disconnecting means for each service shall consist of a combination of not more than _______________ switches.

Bathroom receptacle outlets must be placed within a certain distance to ensure accessibility near the basin.

50 / 50

At least one receptacle outlet shall be installed in bathrooms within _______________ feet of the outside edge of each basin.

Your score is

0%

Exit

Rate & Review

Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services.

Leave a Reply

Your email address will not be published. Required fields are marked *