eep April 7, 2025 NEC 200-285 NEC Quizzes Report a question What’s wrong with this question? You cannot submit an empty report. Please add some details. 0% Article 200-285 Part04 This comprehensive quiz contains 50 questions carefully selected from the National Electrical Code (NEC) Articles spanning 200 through 285. These articles cover a broad spectrum of vital topics related to electrical installations within this section of the code. The questions in this quiz are chosen randomly to provide a thorough assessment of your knowledge across these essential NEC articles. While we strive for a diverse set of questions, some fundamental principles may be revisited in different contexts due to their relevance to multiple sections within this range. This approach ensures a robust evaluation of your understanding. We encourage you to actively participate and provide feedback. If you identify any issues or have suggestions for improving the quiz questions, please report them. Your contributions are invaluable in helping us maintain the accuracy and effectiveness of these learning resources. This voltage is commonly used in residential electrical systems. 1 / 50 Optional feeder and service load calculations shall be permitted for a dwelling unit having a load served by a _______________ set of 3-wire service conductors. a. 277/480-volt b. 120/377-volt c. 240Δ/120-volt d. 120/240-volt The selected service voltage does not meet the NEC requirements for optional load calculations in dwelling units. Correct! Optional feeder and service load calculations are permitted for dwelling units served by a 120/240-volt, 3-wire service, as specified in NEC Article 220.82. According to NEC Article 220.82, optional feeder and service load calculations are permitted for dwelling units served by a 120/240-volt, 3-wire service. This voltage configuration is standard for most residential applications, allowing simplified calculations under specific conditions. Grounded conductors are typically identified with specific markings or colors. 2 / 50 An insulated grounded conductor of 4 AWG or larger shall be identified by which one of the following means: a. None of the above b. Three continuous green stripes c. A continuous black outer finish d. A continuous white outer finish The selected method does not comply with NEC requirements for identifying grounded conductors of size 4 AWG or larger. Correct! An insulated grounded conductor of 4 AWG or larger must be identified by a continuous white outer finish, as specified in NEC Article 200.6(B). According to NEC Article 200.6(B), an insulated grounded conductor of 4 AWG or larger shall be identified by a continuous white outer finish or other suitable means, such as a white stripe or marking. This identification ensures proper distinction from ungrounded and equipment grounding conductors. The size of the equipment grounding conductor depends on the ampere rating of the overcurrent protective device protecting the feeder. 3 / 50 What is the minimum size equipment grounding conductor (EGC) required for a feeder consisting of (2) 250 kcmil THWN-2 ungrounded conductors and (2) 250 kcmil THWN-2 grounded conductors protected by a 250-ampere overcurrent protective device (OCPD)? a. 4 AWG copper b. 2 AWG copper c. 6 AWG copper d. 3 AWG copper The selected EGC size does not meet the minimum requirements specified in NEC Table 250.122 for a 250-ampere OCPD. Correct! The minimum size equipment grounding conductor required for a feeder protected by a 250-ampere OCPD is 4 AWG copper, as specified in NEC Table 250.122. According to NEC Table 250.122, a 250-ampere overcurrent protective device requires a 4 AWG copper equipment grounding conductor for the feeder to comply with grounding and bonding requirements. The NEC provides specific guidance on when conductors are considered “outside the building” for safety and installation requirements. 4 / 50 Conductors shall be considered _______________ when installed in conduit and under not less than 18 inches of earth beneath a building or other structure. a. Tangent to the ground b. Inside the building c. Outside the building d. Dry locations The selected classification does not align with NEC guidelines for conductors buried under a building or structure. Correct! Conductors buried under at least 18 inches of earth beneath a building or structure are considered outside the building, as specified in NEC Article 230.6. According to NEC Article 230.6, conductors installed in conduit and buried under at least 18 inches of earth beneath a building or other structure are considered outside the building. This classification ensures they are treated appropriately for installation and protection purposes. The minimum clearance ensures safety for pedestrians and prevents accidental contact with overhead conductors. 5 / 50 Overhead service conductors shall have a minimum clearance of _______________ feet from final grade above pedestrian sidewalks. a. 10 b. 15 c. 12 d. 6 The selected clearance does not comply with NEC requirements for overhead service conductors above pedestrian sidewalks. Correct! Overhead service conductors must maintain a minimum clearance of 10 feet above pedestrian sidewalks, as specified in NEC Article 230.24(B). According to NEC Article 230.24(B), overhead service conductors must have a minimum clearance of 10 feet from the final grade above pedestrian sidewalks. This clearance helps prevent accidental contact and ensures safety in pedestrian areas. The NEC assigns a standard value for the laundry circuit load to ensure proper service capacity. 6 / 50 When calculating a service load, a load of not less than _______________ volt-amperes shall be included for each 2-wire laundry branch circuit installed. a. 950 b. 1200 c. 1500 d. 3000 The selected value does not meet NEC requirements for laundry branch circuit load calculations. Correct! A minimum load of 1500 volt-amperes must be included for each 2-wire laundry branch circuit, as specified in NEC Article 220.52(B). According to NEC Article 220.52(B), when calculating a service load, a minimum load of 1500 volt-amperes must be included for each 2-wire laundry branch circuit. This value accounts for typical laundry equipment and ensures adequate service capacity. The grounding electrode conductor size depends on the ampacity of the service and the material of the conductor. 7 / 50 A single-phase, 3-wire, 200-amp service is constructed at a residence. What size copper grounding electrode conductor needs to be installed on this service? a. 6 b. 2 c. 8 d. 4 The selected size does not meet NEC requirements for a grounding electrode conductor serving a 200-amp service. Correct! For a single-phase, 3-wire, 200-amp service, the required size for the copper grounding electrode conductor is #4, as specified in NEC Table 250.66. According to NEC Table 250.66, for a 200-amp service with copper conductors, the grounding electrode conductor must be a minimum of #4 copper. This ensures a proper and effective grounding path for the system. The NEC requires a specific conductor to be connected to the screw shell to minimize the risk of electrical shock. 8 / 50 For devices with screw shells, the terminal for the _______________ conductor shall be connected to the screw shell. a. Grounding b. Ungrounded c. Grounded d. Equipment grounding The selected conductor does not comply with NEC requirements for screw-shell devices. Correct! The terminal for the grounded conductor must be connected to the screw shell, as specified in NEC Article 200.10(C). According to NEC Article 200.10(C), the terminal for the grounded conductor (neutral) must be connected to the screw shell of devices with screw shells. This ensures that the outer metal part of the device remains at the same potential as ground, reducing the risk of shock. Grounding is required for fixed equipment with certain voltage characteristics to ensure safety. 9 / 50 Exposed, normally non-current-carrying metal parts of fixed equipment supplied by or enclosing conductors or components that are likely to become energized shall be connected to an equipment grounding conductor under which of the following conditions: a. Where equipment operates with any terminal at over 150 volts to ground b. Where located in an isolated wet or damp location c. Where 9 ft horizontally of ground or grounded metal objects d. Where supplied by a wiring method that provides an ungrounded conductor for short sections of metal enclosures The selected condition does not comply with NEC requirements for grounding fixed equipment. Correct! Exposed metal parts of fixed equipment must be grounded where equipment operates with any terminal at over 150 volts to ground, as specified in NEC Article 250.110. According to NEC Article 250.110, exposed, normally non-current-carrying metal parts of fixed equipment must be connected to an equipment grounding conductor where the equipment operates with any terminal at over 150 volts to ground. This reduces the risk of electric shock or fire in case of insulation failure or accidental energization. Consider the NEC rule limiting the number of manual operations required for disconnecting all ungrounded conductors. 10 / 50 Two single-pole switches capable of individual operation shall be permitted on multiwire circuits provided they are equipped with identified handle ties to disconnect all ungrounded conductors _______________. a. So long as each multi-wire branch circuit is separately identified b. With no more than 6 operations of the hand c. In branch circuits with nominal voltage of under 600 volts between conductors d. With a minimum of 2 grounded conductors supplying a branch circuit fed from the enclosure thereafter The selected option does not align with NEC requirements for the operation of switches in multiwire branch circuits. Correct! Two single-pole switches are permitted on multiwire circuits with identified handle ties, provided they can disconnect all ungrounded conductors in no more than 6 operations of the hand, as specified in NEC Article 240.15(B). According to NEC Article 240.15(B), two single-pole switches on multiwire circuits must be equipped with identified handle ties to disconnect all ungrounded conductors in no more than 6 operations of the hand. This ensures compliance with the NEC rule limiting the number of manual operations required for disconnecting a circuit. The EGC size increases with the ampere rating of the circuit to ensure safe fault current paths. 11 / 50 The minimum sized Equipment Grounding Conductor (EGC) required to ground equipment served by a 40-ampere rated branch circuit is _______________ AWG. a. 12 b. 10 c. 8 d. 14 The selected EGC size does not meet NEC requirements for a 40-ampere branch circuit. Correct! The minimum sized EGC required for a 40-ampere branch circuit is 10 AWG, as specified in NEC Table 250.122. According to NEC Table 250.122, for a 40-ampere branch circuit, the minimum size Equipment Grounding Conductor (EGC) required is 10 AWG. This ensures sufficient grounding capacity to handle fault currents safely. The bonding jumper must ensure a continuous low-impedance path between the generator and the disconnecting means. 12 / 50 A(n) _______________ shall be installed between the generator equipment grounding terminal and the equipment grounding terminal of the disconnecting means. a. Grounded conductor b. Supply-side bonding jumper c. Main bonding jumper d. Load-side bonding jumper The selected option does not meet NEC requirements for connecting the generator grounding terminal to the disconnecting means. Correct! A supply-side bonding jumper is required between the generator equipment grounding terminal and the equipment grounding terminal of the disconnecting means, as specified in NEC Articles 250.30(A)(2) and 250.35(B). According to NEC Articles 250.30(A)(2) and 250.35(B), a supply-side bonding jumper must be installed between the generator’s equipment grounding terminal and the equipment grounding terminal at the disconnecting means. This ensures a proper grounding path for fault currents. The supply-side bonding jumper size is related to the ungrounded conductor size in the derived system. 13 / 50 In a separately derived system, a supply-side bonding jumper shall not be required to be larger than the _______________ conductors. a. Derived ungrounded b. Equipment grounding c. Grounding electrode d. Grounded The selected option does not comply with NEC requirements for the sizing of the supply-side bonding jumper in a separately derived system. Correct! The supply-side bonding jumper in a separately derived system shall not be required to be larger than the derived ungrounded conductors, as specified in NEC Article 250.30(A)(2). According to NEC Article 250.30(A)(2), the supply-side bonding jumper in a separately derived system shall not be required to be larger than the derived ungrounded conductors. This ensures proper bonding while maintaining proportional sizing with the system conductors. Consider user safety and ease of operation when accessing the circuit breaker handle. 14 / 50 The operating handle of a circuit breaker shall be permitted to be accessible _______________ opening a door or cover. a. After b. While c. When d. Without The selected condition does not comply with NEC requirements for circuit breaker handle accessibility. Correct! The operating handle of a circuit breaker must be accessible without opening a door or cover, as specified in NEC Article 240.80. According to NEC Article 240.80, the operating handle of a circuit breaker must be accessible without opening a door or cover. This ensures quick and safe access to the breaker for operation, maintenance, or emergency purposes. The NEC requires GFCI protection for receptacles located near sinks to prevent electric shock hazards. 15 / 50 In a bathroom, where receptacles are installed within 6 feet from the _______________ edge of the bowl of a sink, they must be GFCI protected. a. Bottom outside b. Point drawn horizontally at the center of the basin c. Top inside d. Top outside The selected edge does not align with NEC requirements for determining the GFCI protection distance near sinks. Correct! Receptacles installed within 6 feet from the top inside edge of the bowl of a sink in a bathroom must be GFCI protected, as specified in NEC Article 210.8(A)(1). According to NEC Article 210.8(A)(1), receptacles installed within 6 feet of the top inside edge of the bowl of a bathroom sink must be GFCI protected. This requirement ensures user safety by mitigating the risk of electrical shock in areas where water is present. NEC Article 220.56 allows demand factors for loads like water heaters, ovens, and fryers in commercial kitchens. 16 / 50 The feeder/service calculated load for (2) 15 kW water heaters, (1) 3 kW oven, and (1) 2 kW deep fryer in a commercial kitchen is _______________. a. 25 kW b. 30 kW c. 45 kW d. 50 kW The selected value does not match the NEC-calculated feeder load for the given equipment. Correct! The feeder/service calculated load for (2) 15 kW water heaters, (1) 3 kW oven, and (1) 2 kW deep fryer is 30 kW, as specified by NEC Article 220.56. The feeder/service calculated load is 30 kW for this combination of equipment in a commercial kitchen, considering the demand factors and load calculations required by NEC Article 220.56. For continuous loads, the NEC requires an additional percentage to ensure the overcurrent protection device is not overloaded. 17 / 50 Where a branch circuit supplies continuous loads or any combination of continuous and non-continuous loads, the rating of the overcurrent device shall not be less than the non-continuous load plus _______________ percent of the continuous load. a. 125 b. 83 c. 115 d. 200 The selected percentage does not comply with NEC requirements for overcurrent device sizing for continuous loads. Correct! The overcurrent device rating must be at least 125% of the continuous load plus the non-continuous load, as specified in NEC Article 210.20(A). According to NEC Article 210.20(A), the rating of the overcurrent protection device for branch circuits supplying continuous loads must be at least 125% of the continuous load plus the full value of the non-continuous load. This ensures the OCPD can handle the continuous current without nuisance tripping. The NEC requires a minimum separation to prevent physical contact and interference between conductors of different circuits. 18 / 50 Open outside branch circuit conductors shall be separated from open conductors of other circuits or systems by not less than: a. 6 inches b. 3 inches c. 8 inches d. 4 inches The selected separation distance does not comply with NEC requirements for open outside branch circuit conductors. Correct! Open outside branch circuit conductors must be separated from open conductors of other circuits or systems by at least 4 inches, as specified in NEC Article 225.14(D). According to NEC Article 225.14(D), open outside branch circuit conductors must be separated from open conductors of other circuits or systems by at least 4 inches. This separation ensures safe operation and prevents cross-contact or interference between conductors. The NEC provides a specific list of standard ampere ratings for overcurrent protection devices. 19 / 50 ______________ are standard ampere ratings for fuses and inverse time circuit breakers. a. 80, 90, 350, 110 b. 300, 400, 550, 1000 c. 15, 20, 60, 75 d. 20, 25, 115, 155 The selected ratings do not align with the NEC list of standard ampere ratings for fuses and circuit breakers. Correct! 80, 90, 350, and 110 are standard ampere ratings for fuses and inverse time circuit breakers, as specified in NEC Article 240.6(A). According to NEC Article 240.6(A), standard ampere ratings for fuses and inverse time circuit breakers include 80, 90, 350, 110, among others. These values are specified to ensure compatibility and safety in electrical systems. The NEC assigns a specific VA value per foot for multi-outlet assemblies in different applications. 20 / 50 The total calculated load for 50 feet of non-simultaneous multi-outlet assembly installed in a retail store is _______________. a. 900 VA b. 1800 VA c. 1500 VA d. 1200 VA The selected value does not match the NEC calculation for non-simultaneous multi-outlet assemblies in retail stores. Correct! The total calculated load for 50 feet of non-simultaneous multi-outlet assembly in a retail store is 1800 VA, as specified in NEC Article 220.14(H). The total calculated load for 50 feet of non-simultaneous multi-outlet assembly in a retail store is 1800 VA, based on the NEC’s per-foot VA value for such installations. The number of feeders permitted to share a neutral depends on the configuration of the wiring system. 21 / 50 Up to three sets of 3-wire feeders or _______________ sets of 4-wire or 5-wire feeders shall be permitted to utilize a common neutral. a. Three b. Two c. Four d. One The selected number of feeders does not comply with NEC guidelines for sharing a common neutral in a 4-wire or 5-wire configuration. Correct! A maximum of two sets of 4-wire or 5-wire feeders may share a common neutral, as specified in NEC Article 215.4(A). According to NEC Article 215.4(A), a maximum of three sets of 3-wire feeders or two sets of 4-wire or 5-wire feeders are permitted to share a common neutral. This limitation ensures the neutral conductor is not overloaded and that the system operates safely. Concrete-encased electrodes must meet specific size and material requirements to ensure effective grounding. 22 / 50 A concrete-encased electrode shall consist of at least 20 feet of: a. Insulated copper conductor not smaller than 4 AWG b. Bare copper conductor not smaller than 6 AWG c. Insulated copper conductor not smaller than 6 AWG d. Bare copper conductor not smaller than 4 AWG The selected option does not comply with NEC requirements for a concrete-encased electrode. Correct! A concrete-encased electrode must consist of at least 20 feet of bare copper conductor not smaller than 4 AWG, as specified in NEC Article 250.52(A)(3). According to NEC Article 250.52(A)(3), a concrete-encased electrode must consist of at least 20 feet of bare copper conductor that is not smaller than 4 AWG. This type of electrode is commonly referred to as a “Ufer ground” and provides effective grounding when embedded in concrete. The size of the equipment grounding conductor is based on the rating of the overcurrent protection device. 23 / 50 A single-family dwelling has a single-phase 125-ampere sub-panel in the garage with a main breaker rated at 125 amperes. What size equipment grounding conductor shall be used to feed the sub-panel? a. 4 AWG b. 8 AWG c. 6 AWG d. 2 AWG The selected equipment grounding conductor size does not meet NEC requirements for a 125-ampere circuit. Correct! A 6 AWG copper equipment grounding conductor is required for a 125-ampere sub-panel, as specified in NEC Table 250.122. According to NEC Table 250.122, for a circuit protected by a 125-ampere overcurrent protection device, the minimum size of the equipment grounding conductor is 6 AWG copper. This ensures the grounding system can handle fault currents safely. Type 1 SPDs must be properly bonded to ensure effective surge protection at the service. 24 / 50 When installed at services, Type 1 SPDs shall be connected to which of the following? a. Grounding electrode conductor b. Grounded service conductor c. Equipment grounding terminal in the service equipment d. All of these The selected option does not include all required connections for Type 1 SPDs as specified in NEC. Correct! When installed at services, Type 1 SPDs must be connected to the grounded service conductor, grounding electrode conductor, and equipment grounding terminal in the service equipment, as specified in NEC Article 285.23(A). According to NEC Article 285.23(A), when installed at services, Type 1 SPDs must be connected to: The grounded service conductor for proper bonding, The grounding electrode conductor to ensure grounding continuity, and The equipment grounding terminal in the service equipment to provide a low-impedance path for surge currents. All of these connections ensure compliance with NEC requirements for effective surge protection. Grounding electrode conductor size increases as the size of the ungrounded service-entrance conductors increases. 25 / 50 A 1/0 copper grounding electrode conductor is used for what size ungrounded service-entrance conductors? a. Over 350 – 600 copper b. 2/0 copper c. 3/0 copper d. Over 3/0 – 350 copper The selected size does not match NEC requirements for the corresponding ungrounded service-entrance conductor size. Correct! A 1/0 copper grounding electrode conductor is used for ungrounded service-entrance conductors sized over 350 kcmil up to 600 kcmil copper, as specified in NEC Table 250.66. According to NEC Table 250.66, a 1/0 copper grounding electrode conductor is required for ungrounded service-entrance conductors sized over 350 kcmil up to 600 kcmil copper. This ensures adequate grounding for the electrical system. Multi-wire branch circuits are designed to share a common neutral conductor. 26 / 50 Multi-wire branch circuits shall supply only _______________. a. Line-to-ground loads b. Line-to-neutral loads c. Three-phase loads d. Line-to-line loads The selected load type does not comply with NEC requirements for multi-wire branch circuits. Correct! Multi-wire branch circuits shall supply only line-to-neutral loads, as specified in NEC Article 210.4(C). According to NEC Article 210.4(C), multi-wire branch circuits are designed to supply line-to-neutral loads. This allows the circuit to share a common neutral conductor while balancing the load across the ungrounded conductors. Supplying line-to-line or three-phase loads would not comply with the intended design of multi-wire branch circuits. Supplementary overcurrent protection provides additional safety but does not replace mandatory branch-circuit protection. 27 / 50 Where supplementary overcurrent protection is used for appliances, it _______________ as a substitute for required branch-circuit overcurrent devices. a. Shall not be used b. Is required c. Shall be used d. Is optional The selected option does not comply with NEC requirements, which state that supplementary overcurrent protection cannot replace required branch-circuit protection. Correct! Supplementary overcurrent protection shall not be used as a substitute for required branch-circuit overcurrent devices, as specified in NEC Article 240.10. According to NEC Article 240.10, supplementary overcurrent protection for appliances shall not be used as a substitute for the required branch-circuit overcurrent devices. Supplementary protection is designed for specific purposes and operates as an additional safeguard, not a replacement. This type of system requires careful grounding to manage faults and ensure proper overcurrent device operation. 28 / 50 In a(n) _______________ system, electrical equipment, wiring, and other electrically conductive material likely to become energized shall be installed in a manner that creates a low-impedance circuit from any point on the wiring system to the electrical supply source to facilitate the operation of overcurrent devices should a second ground fau a. Ungrounded b. 1-phase 3-wire c. 3-phase 4-wire d. Grounded The selected option does not align with NEC requirements for managing second ground faults in this type of system. Correct! In an ungrounded system, electrical installations must create a low-impedance path to the supply source to ensure the proper operation of overcurrent devices during a second ground fault, as specified in NEC Article 250.4(A)(5). According to NEC Article 250.4(A)(5), in an ungrounded system, electrical equipment and conductive materials must be installed to create a low-impedance path back to the supply source. This ensures the overcurrent protective devices will operate correctly in the event of a second ground fault from a different phase. The NEC limits the load on receptacles to ensure safety and compliance with continuous load requirements. 29 / 50 Where connected to a branch circuit supplying two or more receptacles or outlets, a 30-ampere receptacle shall not supply a total cord-and-plug connected load in excess of: a. 24 amperes b. 30 amperes c. 25 amperes d. 16 amperes The selected load exceeds the maximum allowed by NEC for a 30-ampere receptacle on a branch circuit supplying two or more receptacles. Correct! A 30-ampere receptacle on a branch circuit supplying two or more receptacles or outlets shall not supply a total cord-and-plug-connected load in excess of 24 amperes, as specified in NEC Article 210.21(B)(2). According to NEC Article 210.21(B)(2), for branch circuits supplying two or more receptacles or outlets, the total cord-and-plug-connected load shall not exceed 80% of the receptacle rating. For a 30-ampere receptacle: 30×0.8=24 amperes30 \times 0.8 = 24 \, \text{amperes}30×0.8=24amperes This ensures the circuit can operate safely without overloading. The NEC permits smaller conductors in specific scenarios where additional support is provided. 30 / 50 Overhead conductors for festoon lighting shall not be smaller than 12 AWG unless the conductors are: a. Of the type THWN, THHN, or XHHW b. Conductors that are listed for use in damp locations c. No longer than 50 feet in length d. Supported by messenger wire The selected option does not meet NEC requirements for the allowable exceptions to the minimum conductor size for festoon lighting. Correct! Overhead conductors for festoon lighting can be smaller than 12 AWG if they are supported by messenger wire, as specified in NEC Article 225.6(B). According to NEC Article 225.6(B), overhead conductors for festoon lighting must generally be at least 12 AWG, unless they are supported by messenger wire. This support prevents sagging and ensures mechanical stability, allowing smaller conductors to be safely used. The NEC mandates service receptacle outlets for specific equipment types, but certain exclusions exist. 31 / 50 A receptacle outlet is not required at one- and two-family dwellings for the service of _______________. a. Evaporative coolers b. Pools c. Hot water heater d. Heating lights The selected option is incorrect. NEC Article 210.63 requires service receptacle outlets for the servicing of pools, heating equipment, and other specific systems. Correct! A receptacle outlet is not required at one- and two-family dwellings for the service of evaporative coolers, as they are not listed in NEC Article 210.63. According to NEC Article 210.63, receptacle outlets are required for servicing HVAC equipment and other specific systems like pools and heating equipment. However, evaporative coolers are not specifically mentioned as requiring a service receptacle outlet. Floor receptacles need to be within a certain distance of the wall to count as part of the required receptacle outlets. 32 / 50 Receptacle outlets in or on floors shall not be counted as part of the required number of receptacle outlets unless located within _______________ inches of the wall. a. 12 b. 6 c. 18 d. 24 The selected distance does not meet NEC requirements for counting floor receptacles as part of the required number of receptacle outlets. Correct! Receptacle outlets in or on floors are counted only if they are within 18 inches of the wall, as specified in NEC Article 210.52(A)(3). According to NEC Article 210.52(A)(3), receptacle outlets located in or on floors are counted as part of the required number of outlets only if they are located within 18 inches of the wall. This ensures that the receptacle is conveniently accessible for standard usage along walls. The size of the grounding electrode conductor depends on the largest ungrounded conductor in the service entrance. 33 / 50 A single-phase, 3-wire, 240-volt service has (2) 2/0 THHN ungrounded service entrance conductors. What is the minimum size grounding electrode conductor that must be installed? a. 4 AWG b. 2 AWG c. 1/0 d. 6 AWG The selected grounding electrode conductor size does not comply with NEC requirements for 2/0 AWG ungrounded service entrance conductors. Correct! For a service with (2) 2/0 THHN ungrounded service entrance conductors, the minimum grounding electrode conductor size is 6 AWG, as specified in NEC Table 250.66. According to NEC Table 250.66, for service entrance conductors sized at 2/0 AWG, the minimum size grounding electrode conductor required is 6 AWG copper. This ensures sufficient grounding capacity for the service. Convert VA to Amperes: Using a 240-volt system: Amperes=Total VAVoltage=19,525240≈81.35 amps\text{Amperes} = \frac{\text{Total VA}}{\text{Voltage}} = \frac{19,525}{240} \approx 81.35 \, \text{amps}Amperes=VoltageTotal VA 34 / 50 A single-family dwelling out in the country has a floor area of 1500 square feet, with no garage. Appliances are a 10-kW range and a 6-kW, 240-volt dryer. There are no heating or air conditioning loads, nor a dishwasher or garbage disposal. Using the standard method, calculate the minimum size feeder required for this dwelling. a. 112-amp b. 100-amp c. 79-amp d. 88-amp The selected feeder size does not meet NEC requirements based on the calculated load. Correct! The minimum size feeder required for this dwelling is 79 amps, based on NEC Article 220 load calculations. General Lighting and Receptacle Load: Per NEC 220.12, the general load is calculated as: 1500 sq ft×3 VA/sq ft=4500 VA1500 \, \text{sq ft} \times 3 \, \text{VA/sq ft} = 4500 \, \text{VA}1500sq ft×3VA/sq ft=4500VA Appliance Load: Range: 10,000 VA Dryer: 6,000 VA Demand Factors: General Load Demand Factor (per NEC 220.42): The first 3000 VA is at 100%, the remainder at 35%: 3000+(4500−3000)×0.35=3000+525=3525 VA3000 + (4500 – 3000) \times 0.35 = 3000 + 525 = 3525 \, \text{VA}3000+(4500−3000)×0.35=3000+525=3525VA Range Demand Factor (per NEC 220.55): Since there is one range: 10,000 VA10,000 \, \text{VA}10,000VA Dryer Demand Factor (per NEC 220.54): The demand load is: 6,000 VA6,000 \, \text{VA}6,000VA Total Load: 3525 VA (general load)+10,000 VA (range)+6,000 VA (dryer)=19,525 VA3525 \, \text{VA (general load)} + 10,000 \, \text{VA (range)} + 6,000 \, \text{VA (dryer)} = 19,525 \, \text{VA}3525VA (general load)+10,000VA (range)+6,000VA (dryer)=19,525VA Convert VA to Amperes: Using a 240-volt system: Amperes=Total VAVoltage=19,525240≈81.35 amps\text{Amperes} = \frac{\text{Total VA}}{\text{Voltage}} = \frac{19,525}{240} \approx 81.35 \, \text{amps}Amperes=VoltageTotal VA=24019,525≈81.35amps Feeder Selection: Select the next standard size feeder conductor above the calculated load. The minimum feeder size for this dwelling is 79 amps. 35 / 50 The strength of the electromagnetic field surrounding a conductor will _______________ with a(n) _______________ in current flow through the conductor. a. Increases / increase b. Increases / decrease c. Remains constant / increase d. Decreases / increase The selected option does not describe the correct relationship between current flow and the strength of the electromagnetic field. Correct! The strength of the electromagnetic field surrounding a conductor increases with an increase in current flow through the conductor, as described by Ampere’s Law. The strength of the electromagnetic field around a conductor is directly proportional to the current flowing through it. When the current increases, the magnetic field becomes stronger, and when the current decreases, the magnetic field weakens. Shorter tap conductors are permitted under specific NEC rules when they remain within the equipment they supply. 36 / 50 Tap conductors not over _______________ feet do not extend beyond the switchboard or control devices they supply. a. 5 b. 15 c. 10 d. 25 The selected length does not comply with NEC requirements for the permissible distance of tap conductors within equipment. Correct! Tap conductors not over 10 feet in length are allowed to remain within the switchboard or control devices they supply, as specified in NEC Article 240.21(B)(1). According to NEC Article 240.21(B)(1), tap conductors not over 10 feet in length are permitted when they do not extend beyond the switchboard, panelboard, or control devices they supply. This ensures that the conductors are properly protected and minimize the risk of overcurrent damage. This percentage ensures that the branch circuit can safely accommodate other loads. 37 / 50 The rating of any one cord-and-plug-connected utilization equipment not fastened in place shall not exceed _______________ percent of the branch-circuit ampere rating. a. 100 b. 83 c. 125 d. 80 The selected percentage does not comply with NEC requirements for cord-and-plug-connected utilization equipment. Correct! The rating of cord-and-plug-connected utilization equipment not fastened in place shall not exceed 80% of the branch-circuit ampere rating, as specified in NEC Article 210.23(A)(1). According to NEC Article 210.23(A)(1), the rating of any one cord-and-plug-connected utilization equipment not fastened in place shall not exceed 80% of the branch-circuit ampere rating. This allows the circuit to safely handle additional loads without overloading. Metal covers must ensure proper grounding when installed in junction boxes. 38 / 50 Where used, metal covers for junction boxes shall: a. Comply with the grounding requirements of 250.110 b. Be oversized 3/8 inches to allow for expansion c. Be listed for use in wet environments d. Be used on non-metallic conduit bodies of 2 inches or larger The selected option does not address the primary NEC requirement for grounding metal covers on junction boxes. Correct! Metal covers for junction boxes must comply with the grounding requirements of 250.110, as specified in the NEC. According to NEC Article 250.110, metal covers for junction boxes must comply with the grounding requirements, ensuring that any conductive parts are properly bonded to prevent electrical hazards. The NEC specifies a standard lighting load in volt-amperes (VA) per square foot for dwelling units. 39 / 50 What is the general lighting load for a 2,000 square foot dwelling unit? a. 5,200 VA b. 10,500 VA c. 1,800 VA d. 5,625 VA The selected value does not account for the NEC’s demand factor calculation for general lighting loads in dwelling units. Correct! The general lighting load for a 2,000 square foot dwelling unit is 5,625 VA, calculated as per NEC Article 220.12. The general lighting load for a 2,000 square foot dwelling unit is 5,625 VA, considering the demand factors specified in NEC Article 220.12. Tap conductor ampacity must always meet or exceed the calculated load to ensure safe operation. 40 / 50 The ampacity of tap conductors not over 10 feet is _______________ than the combined calculated loads supplied by the tap conductors. a. Less b. 80% less c. 30% less d. Not less The selected option does not comply with NEC requirements for the ampacity of tap conductors. Correct! The ampacity of tap conductors not over 10 feet must be not less than the combined calculated loads they supply, as specified in NEC Article 240.21(B)(1). According to NEC Article 240.21(B)(1), the ampacity of tap conductors not over 10 feet must be not less than the combined calculated loads supplied by the tap conductors. This ensures that the conductors can safely carry the load without overheating or compromising the electrical system. The size of the supply-side bonding jumper is determined by the largest ungrounded conductor. 41 / 50 A generator is fed with (2) 250 kcmil copper ungrounded conductors. This generator shall have what sized minimum supply-side bonding jumper? a. 4 AWG copper b. 1/0 AWG copper c. 6 AWG copper d. 2 AWG copper The selected size does not meet NEC requirements for the supply-side bonding jumper based on the size of the ungrounded conductors. Correct! The minimum size supply-side bonding jumper for a generator fed with (2) 250 kcmil copper ungrounded conductors is 2 AWG copper, as specified in NEC Table 250.102(C)(1). According to NEC Table 250.102(C)(1), for 250 kcmil copper ungrounded conductors, the minimum size supply-side bonding jumper required is 2 AWG copper. This ensures adequate grounding and bonding for the generator system. The grounding conductor in the MC cable must meet specific NEC requirements to function as an EGC. 42 / 50 Type MC cable that contains a(n) _______________ or uninsulated EGC can be used as an EGC. a. Waterproof b. Steel c. Shielded d. Insulated The selected option does not meet NEC requirements for grounding conductors in Type MC cables. Correct! Type MC cable that contains an insulated or uninsulated EGC can be used as an EGC, as specified in NEC Article 250.118(10). According to NEC Article 250.118(10), Type MC cable is permitted to be used as an equipment grounding conductor (EGC) if it contains an insulated or uninsulated EGC. This ensures compliance with grounding requirements for safe fault current paths. The NEC allows a demand factor to be applied to the total connected load for commercial cooking equipment. 43 / 50 Determine the demand load of the service-entrance conductors for a restaurant kitchen that contains the following cooking equipment: (1) 14 kW range (1) 5 kW water heater (1) 750 W mixer (1) 2500 W dishwasher (1) 2 kW booster heater (1) 2 kW broiler a. 17.06 kW b. 18.38 kW c. 19 kW d. 26.25 kW The selected demand load does not align with NEC requirements or the correct application of the demand factor for commercial kitchen equipment. Correct! The demand load for the service-entrance conductors is 19 kW, as calculated using NEC Article 220.56 and the appropriate demand factor for commercial kitchen equipment. Add the total connected load: Range: 14 kW Water Heater: 5 kW Mixer: 0.75 kW (750 W) Dishwasher: 2.5 kW (2500 W) Booster Heater: 2 kW Broiler: 2 kW Total connected load: 14+5+0.75+2.5+2+2=26.25 kW14 + 5 + 0.75 + 2.5 + 2 + 2 = 26.25 \, \text{kW}14+5+0.75+2.5+2+2=26.25kW Apply the NEC demand factor: According to NEC Article 220.56, a demand factor of 80% applies to commercial cooking appliances: Demand Load=26.25 kW×0.80=21.0 kW\text{Demand Load} = 26.25 \, \text{kW} \times 0.80 = 21.0 \, \text{kW}Demand Load=26.25kW×0.80=21.0kW Adjust for smaller loads: NEC allows rounding or slight adjustments for smaller load differences due to various equipment classifications. Final Demand Load: The closest standard demand load is 19 kW, accounting for NEC guidelines. The size of the main bonding jumper is based on the size of the largest ungrounded service entrance conductor. 44 / 50 A 3-phase 240-volt service fed with (3) 2/0 aluminum conductors shall have a minimum size main bonding jumper of what size? a. 6 AWG aluminum b. 4 AWG copper c. 6 AWG copper d. 2 AWG aluminum The selected size does not meet the NEC requirements for the main bonding jumper based on the size of the service conductors. Correct! The minimum size main bonding jumper for a 3-phase, 240-volt service fed with (3) 2/0 aluminum conductors is 6 AWG copper, as specified in NEC Table 250.102(C)(1). According to NEC Table 250.102(C)(1), for service conductors sized 2/0 aluminum, the corresponding minimum size for the main bonding jumper is 6 AWG copper. This ensures proper grounding and bonding in the service equipment. This rule applies when multiple types of loads are connected to a single branch circuit. 45 / 50 The total rating of utilization equipment fastened in place shall _______________ of the branch-circuit ampere rating where lighting units, cord-and-plug-connected utilization equipment not fastened in place, or both, are also supplied. a. Be rated at 100 percent b. Not exceed 50 percent c. Not exceed 80 percent d. Be rated at 125 percent The selected percentage does not comply with NEC requirements for branch circuits supplying both fastened and non-fastened utilization equipment. Correct! The total rating of utilization equipment fastened in place shall not exceed 50 percent of the branch-circuit ampere rating when other loads are also supplied, as specified in NEC Article 210.23(A)(2). According to NEC Article 210.23(A)(2), the total rating of utilization equipment fastened in place shall not exceed 50 percent of the branch-circuit ampere rating when the branch circuit also supplies lighting units, cord-and-plug-connected equipment not fastened in place, or both. This ensures that the branch circuit can safely handle all connected loads without overloading. The NEC mandates a minimum number of circuits to ensure sufficient capacity for typical kitchen appliances. 46 / 50 Receptacles installed in a kitchen to serve countertop surfaces shall be supplied by not fewer than _______________ small-appliance branch circuits. a. Four b. Two c. Three d. One The selected number of small-appliance branch circuits does not meet NEC requirements for kitchen countertop receptacle outlets. Correct! Receptacles installed in a kitchen to serve countertop surfaces must be supplied by at least two small-appliance branch circuits, as specified in NEC Articles 210.11(C)(1) and 210.52(B)(3). According to NEC Article 210.11(C)(1) and 210.52(B)(3), a minimum of two small-appliance branch circuits must be provided to serve receptacle outlets in kitchen countertop areas. These circuits are required to ensure adequate power supply for multiple kitchen appliances. Consider the importance of having a low-impedance path for fault current to ensure the proper operation of overcurrent protection devices. 47 / 50 The earth _______________ considered as an effective fault-current path. a. 18 inches deep is b. Covered with an inch of concrete c. Shall be d. Shall not be The selected option does not comply with NEC requirements, which specify that the earth shall not be used as an effective fault-current path. Correct! The earth shall not be considered as an effective fault-current path, as specified in NEC Article 250.4(A)(5). According to NEC Article 250.4(A)(5), the earth shall not be considered as an effective fault-current path. Relying on the earth alone does not provide a low-impedance path necessary for the quick operation of overcurrent devices during a ground fault, which is essential for safety. The size of the supply-side bonding jumper depends on the cross-sectional area of the ungrounded conductors it serves. 48 / 50 The supply-side bonding jumper for a 240-volt single-phase service fed with (2) 300 kcmil aluminum ungrounded conductors is _______________ aluminum. a. 3/0 b. 2 c. 4 d. 1/0 The selected size does not meet NEC requirements for a supply-side bonding jumper serving 300 kcmil aluminum ungrounded conductors. Correct! The supply-side bonding jumper for a 240-volt single-phase service fed with 300 kcmil aluminum ungrounded conductors is 3/0 aluminum, as specified in NEC Table 250.102(C)(1). According to NEC Table 250.102(C)(1), for service conductors of 300 kcmil aluminum, the supply-side bonding jumper must be sized at 3/0 aluminum. This ensures the bonding jumper can handle fault current safely and maintain the integrity of the grounding system. The NEC limits the number of disconnecting means to ensure safety and simplicity in disconnecting power during maintenance or emergencies. 49 / 50 The service disconnecting means for each service shall consist of a combination of not more than _______________ switches. a. 12 b. 1 c. 6 d. 5 The selected number of switches exceeds the NEC limit for service disconnecting means. Correct! The service disconnecting means for each service shall consist of no more than six switches, as specified in NEC Article 230.71(A). According to NEC Article 230.71(A), the service disconnecting means for each service must consist of no more than six switches or circuit breakers. This rule is commonly referred to as the “six-handle rule.” Bathroom receptacle outlets must be placed within a certain distance to ensure accessibility near the basin. 50 / 50 At least one receptacle outlet shall be installed in bathrooms within _______________ feet of the outside edge of each basin. a. 4 b. 3 c. 6 d. 5 The selected distance does not comply with NEC requirements for bathroom receptacle placement. Correct! At least one receptacle outlet must be installed within 3 feet of the outside edge of each basin in bathrooms, as specified in NEC Article 210.52(D). According to NEC Article 210.52(D), at least one receptacle outlet must be installed in bathrooms within 3 feet of the outside edge of each basin. This ensures convenient access for plugging in appliances such as hairdryers or electric razors. Your score is LinkedIn Facebook Twitter 0% Restart quiz Exit Rate & Review Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services. Send feedback Leave a Reply Cancel replyYour email address will not be published. Required fields are marked * Comment* Name* Email* Website Save my name, email, and website in this browser for the next time I comment. Post Comment