eep April 7, 2025 NEC 200-285 NEC Quizzes Report a question What’s wrong with this question? You cannot submit an empty report. Please add some details. 0% Article 200-285 Part06 This comprehensive quiz contains 50 questions carefully selected from the National Electrical Code (NEC) Articles spanning 200 through 285. These articles cover a broad spectrum of vital topics related to electrical installations within this section of the code. The questions in this quiz are chosen randomly to provide a thorough assessment of your knowledge across these essential NEC articles. While we strive for a diverse set of questions, some fundamental principles may be revisited in different contexts due to their relevance to multiple sections within this range. This approach ensures a robust evaluation of your understanding. We encourage you to actively participate and provide feedback. If you identify any issues or have suggestions for improving the quiz questions, please report them. Your contributions are invaluable in helping us maintain the accuracy and effectiveness of these learning resources. Think about the NEC guidelines regarding the bonding of grounded conductors and their sizing based on ungrounded conductors. 1 / 50 The grounded conductor of each separately derived system shall be bonded to the nearest available point of the metal water piping system(s) in the area served by each separately derived system, and each bonding jumper shall be sized in accordance with Table 250.102(C)(1) based on the largest ungrounded conductor of the separately derived system. a. True b. False Incorrect. The correct answer is True. The requirements for bonding grounded conductors and sizing bonding jumpers are specified in the NEC. Correct! The grounded conductor of each separately derived system must be bonded to the nearest available point of the metal water piping system(s), and bonding jumpers must be sized according to Table 250.102(C)(1), as stated in NEC Article 250.104(D). According to NEC Article 250.104(D), the grounded conductor of each separately derived system must be bonded to the nearest available point of the metal water piping system(s) in the area served by the system. Additionally, each bonding jumper must be sized in accordance with Table 250.102(C)(1) based on the largest ungrounded conductor of the separately derived system. Thus, the statement is True. Consider the minimum cover depth that provides sufficient isolation for metal components to avoid grounding requirements. 2 / 50 Metal components in a run of underground nonmetallic raceway and isolated from possible contact by a minimum cover of ____ in. to all parts of the metal components shall not be required to be connected to the grounded system conductor, supply-side bonding jumper, or grounding electrode conductor. a. 18 b. 24 c. 6 d. 12 Incorrect. The correct answer is 18 inches. This cover depth provides the necessary isolation from grounding requirements. Correct! Metal components in a run of underground nonmetallic raceway that are isolated by a minimum cover of 18 inches do not need to be connected to the grounded system conductor, as specified in NEC Article 250.86. According to NEC Article 250.86, metal components in a run of underground nonmetallic raceway that are isolated from possible contact and have a minimum cover of 18 inches to all parts of the metal components are not required to be connected to the grounded system conductor, supply-side bonding jumper, or grounding electrode conductor. Consider the specific conditions under which FMC and LFMC are required to include an equipment grounding conductor. 3 / 50 Listed FMC and LFMC shall contain an equipment grounding conductor if the raceway is installed for the reason of ____. a. b or c b. flexibility after installation c. physical protection d. minimizing transmission of vibration from equipment Incorrect. The correct answer is b or c. FMC and LFMC must include an equipment grounding conductor if installed for flexibility or vibration minimization. Correct! Listed FMC and LFMC shall contain an equipment grounding conductor if the raceway is installed for the reason of b or c, as specified in NEC Article 250.118. According to NEC Article 250.118, listed FMC and LFMC must contain an equipment grounding conductor if the raceway is installed for the purpose of flexibility after installation or minimizing the transmission of vibration from equipment. Therefore, the correct answer is b or c. Consider the NEC guidelines regarding the installation of grounded conductors in relation to lighting circuits in areas used for human occupancy. 4 / 50 As a general rule, the grounded circuit conductor for the controlled lighting circuit must be installed at the location where switches control lighting loads supplied by a grounded general-purpose branch circuit serving bathrooms, hallways, stairways, or rooms suitable for human habitation or occupancy, as defined in the applicable building code. a. False b. True That’s not correct. Remember, the NEC specifies the requirements for grounded conductors in relation to controlled lighting circuits in habitable spaces. Correct! The grounded circuit conductor for the controlled lighting circuit must be installed where switches control lighting loads supplied by a grounded general-purpose branch circuit in areas suitable for human occupancy. Great job! According to NEC Article 250.140, the grounded circuit conductor for the controlled lighting circuit is required to be installed at the location where switches control lighting loads supplied by a grounded general-purpose branch circuit. This requirement is particularly relevant in bathrooms, hallways, stairways, and other rooms suitable for human habitation, as defined in the applicable building code, to ensure safety and compliance with electrical standards. Consider the minimum depth requirement for grounding electrodes that ensure proper electrical grounding. 5 / 50 One or more metal in-ground support structure(s) in direct contact with the earth vertically for ______ ft or more, with or without concrete encasement, is permitted to be a grounding electrode in accordance with 250.52. a. 8 b. 4 c. 6 d. 10 Incorrect. The correct answer is 10 ft. This is the minimum depth required for metal in-ground support structures to serve as grounding electrodes. Correct! One or more metal in-ground support structures in direct contact with the earth for 10 ft or more is permitted to be a grounding electrode, as specified in NEC Article 250.52(A)(3). According to NEC Article 250.52(A)(3), one or more metal in-ground support structures in direct contact with the earth vertically for 10 ft or more, with or without concrete encasement, is permitted to be a grounding electrode. Consider the provisions in the NEC that allow the structural frame of a building to serve as part of the grounding system. 6 / 50 The metal structural frame of a building shall be permitted to be used as a conductor to interconnect electrodes that are part of the grounding electrode system, or as a grounding electrode conductor. Hold-down bolts securing the structural steel column that are connected to a concrete-encased electrode that complies with 250.52(A)(3) and is located in the support footing or foundation shall be permitted to connect the metal structural frame of a building or structure to the concrete-encased grounding electrode. a. True b. False Incorrect. The correct answer is True. The NEC allows for this configuration regarding grounding and bonding. Correct! The metal structural frame of a building can be used to interconnect electrodes and connect to concrete-encased grounding electrodes, as specified in NEC Article 250.68. According to NEC Article 250.68, the metal structural frame of a building is permitted to be used as a conductor to interconnect electrodes that are part of the grounding electrode system. Additionally, hold-down bolts securing the structural steel column that connect to a concrete-encased electrode located in the support footing or foundation are allowed to connect the structural frame to the grounding electrode. Consider the gauge limit below which grounding electrode conductors must be protected due to potential physical damage. 7 / 50 Grounding electrode conductors smaller than ____ AWG shall be protected in rigid metal conduit, IMC, PVC conduit, electrical metallic tubing, or cable armor. a. 6 b. 10 c. No answer text provided. d. 8 Incorrect. The correct answer is 6 AWG. Grounding electrode conductors smaller than this size require protection from physical damage. Correct! Grounding electrode conductors smaller than 6 AWG shall be protected in rigid metal conduit, IMC, PVC conduit, electrical metallic tubing, or cable armor, as specified in NEC Article 250.64. According to NEC Article 250.64, grounding electrode conductors smaller than 6 AWG must be protected in rigid metal conduit, IMC, PVC conduit, electrical metallic tubing, or cable armor to ensure their safety and integrity. Consider the minimum size requirements for grounding electrode conductors based on the type of electrodes used. 8 / 50 If the grounding electrode conductor or bonding jumper connected to a single or multiple rod, pipe, or plate electrode(s), or any combination thereof, as described in 250.52(A)(5) or (A)(7), does not extend on to other types of electrodes that require a larger size conductor, the grounding electrode conductor shall not be required to be larger than _____ AWG copper wire. a. 10 b. 6 c. 4 d. 8 Incorrect. The correct answer is 6 AWG. This size is sufficient for the specified grounding electrode configurations. Correct! The grounding electrode conductor connected to a single or multiple rod, pipe, or plate electrode(s) shall not be required to be larger than 6 AWG copper wire, as specified in NEC Article 250.66. According to NEC Article 250.66, if the grounding electrode conductor or bonding jumper is connected to a single or multiple rod, pipe, or plate electrode(s), and does not connect to other types of electrodes that require a larger conductor size, it shall not be required to be larger than 6 AWG copper wire. Consider the different components to which metal water piping systems can be bonded for effective grounding. 9 / 50 The metal water piping system(s) installed in or attached to a building structure [250.104(A)(3)] shall be bonded to ________. a. One or more grounding electrodes used b. any of these c. the equipment grounding conductor run with the supply conductors d. the building structure disconnecting means enclosure where located at the building or structure Incorrect. The correct answer is any of these. The bonding requirements allow for flexibility in connecting to different grounding components. Correct! Metal water piping systems installed in or attached to a building structure must be bonded to any of these components, as specified in NEC Article 250.104(A)(3). According to NEC Article 250.104(A)(3), the metal water piping systems installed in or attached to a building structure must be bonded to any of these options: the building structure disconnecting means enclosure, the equipment grounding conductor run with the supply conductors, or one or more grounding electrodes used. Consider the different components that can serve as bonding points for exposed structural metal in a building. 10 / 50 Exposed structural metal interconnected to form a metal building frame that is not intentionally grounded or bonded and is likely to become energized shall be bonded to the __ . a. service equipment enclosure or building disconnecting means b. grounded conductor at the service c. grounding electrode where of sufficient size d. any of these Incorrect. The correct answer is any of these. The bonding requirements allow flexibility in connecting to different grounding components. Correct! Exposed structural metal that is not intentionally grounded or bonded and is likely to become energized shall be bonded to any of these components, as specified in NEC Article 250.104. According to NEC Article 250.104, exposed structural metal that is interconnected to form a metal building frame, which is not intentionally grounded or bonded and is likely to become energized, shall be bonded to any of these options: the service equipment enclosure or building disconnecting means, the grounded conductor at the service, or a grounding electrode of sufficient size. Consider the two conditions that provide sufficient isolation for metal components in nonmetallic raceways. 11 / 50 Metal components shall not be required to be connected to the equipment grounding conductor or supply-side bonding jumper where the metal components are __. a. none of these b. a or b c. part of an installation of nonmetallic raceway(s) and are isolated from possible contact to any part of the metal components by being encased in not less than 2 in. of concrete d. installed in a run of nonmetallic raceway(s) and isolated from possible contact by a minimum cover of 18 in. to any part of the metal components Incorrect. The correct answer is a or b. Both conditions allow for the isolation of metal components from grounding requirements. Correct! Metal components are not required to be connected to the equipment grounding conductor or supply-side bonding jumper when they are either in a run of nonmetallic raceway with a minimum cover of 18 inches or encased in not less than 2 inches of concrete, as specified in NEC Article 250.86. According to NEC Article 250.86, metal components do not need to be connected to the equipment grounding conductor or supply-side bonding jumper if they are either installed in a run of nonmetallic raceway with a minimum cover of 18 inches or encased in not less than 2 inches of concrete. Therefore, the correct answer is a or b. 12 / 50 The bonding jumper used to bond the metal water piping system shall be sized in accordance with _____ except as permitted in 250.104(A)(2) and 250.104(A)(3). a. table 250.122 b. table 250.102(c)(1) c. table 310.15(B) d. table 310.15(B)(6) Incorrect. The correct answer is table 250.102(c)(1). This table outlines the proper sizing for bonding jumpers in electrical systems. Correct! The bonding jumper used to bond the metal water piping system shall be sized in accordance with Table 250.102(c)(1), as specified in NEC Article 250.102. According to NEC Article 250.102, the bonding jumper used to bond the metal water piping system shall be sized in accordance with Table 250.102(c)(1), except as permitted in 250.104(A)(2) and 250.104(A)(3), which provide specific exceptions for certain situations. Consider the materials that are commonly used for grounding connections in electrical installations. 13 / 50 The common grounding electrode conductor installed for multiple separately derived systems shall be permitted to be a _____ pipe that complies with 250.68(C)(1). a. metal gas b. any of these c. metal water d. PVC water Incorrect. The correct answer is metal water. This type of pipe is compliant with the NEC requirements for grounding electrode conductors. Correct! The common grounding electrode conductor installed for multiple separately derived systems may be a metal water pipe that complies with NEC Article 250.68(C)(1). According to NEC Article 250.68(C)(1), the common grounding electrode conductor for multiple separately derived systems is permitted to be a metal water pipe, which is recognized for its effective grounding capabilities. Consider the maximum trade size limitations for FMC when used as an equipment grounding conductor according to NEC standards. 14 / 50 Listed FMC can be used as the equipment grounding conductor if the conduit does not exceed trade size ____. a. 2¼ b. 1 ¼ c. 2 d. 1½ Incorrect. The correct answer is 1 ¼. Listed FMC can only be used as an equipment grounding conductor if the conduit size does not exceed this measurement. Correct! Listed FMC can be used as the equipment grounding conductor if the conduit does not exceed trade size 1 ¼, as specified in NEC Article 250.118. According to NEC Article 250.118, listed FMC can be used as the equipment grounding conductor if the conduit does not exceed a trade size of 1 ¼. Therefore, the correct answer is 1 ¼. Consider the NEC guidelines regarding the installation of equipment grounding conductors in parallel with circuit conductors. 15 / 50 Where circuit conductors are installed in parallel in multiple raceways or cables and include an EGC of the wire type, the equipment grounding conductor shall be installed in parallel in each raceway or cable, sized in compliance with 250.122 based on the overcurrent protective device for the feeder or branch circuit. a. False b. True Incorrect. The correct answer is True. The NEC requires that the equipment grounding conductor be installed in parallel with the circuit conductors and sized accordingly. Correct! The equipment grounding conductor must be installed in parallel in each raceway or cable and sized in compliance with NEC Article 250.122 based on the overcurrent protective device for the feeder or branch circuit. According to NEC Article 250.122, when circuit conductors are installed in parallel in multiple raceways or cables, the equipment grounding conductor must also be installed in parallel in each raceway or cable. The sizing of the EGC must comply with the requirements based on the overcurrent protective device for either the feeder or branch circuit. Therefore, the statement is True. Consider the specific requirements for grounding electrode conductors when associated with concrete-encased electrodes. 16 / 50 In an AC system, if the size of the grounding electrode conductor or bonding jumper connected to a concrete-encased electrode does not extend on to other types of electrodes that require a larger size of conductor, the grounding electrode conductor shall not be required to be larger than ______ AWG copper. a. 4 b. 6 c. 8 d. 10 Incorrect. The correct answer is 4 AWG. This size is the maximum allowed for the specified application without needing a larger conductor. Correct! In an AC system, the grounding electrode conductor connected to a concrete-encased electrode shall not be required to be larger than 4 AWG copper, as specified in NEC Article 250.66. According to NEC Article 250.66, if the grounding electrode conductor or bonding jumper connected to a concrete-encased electrode does not connect to other types of electrodes that require a larger conductor size, it shall not be required to be larger than 4 AWG copper. Consider the requirements for continuity in grounding systems to ensure effective grounding and bonding. 17 / 50 Ferrous metal raceways and enclosures for grounding electrode conductors shall be electrically continuous from the point of attachment to the cabinet or equipment to the grounding electrode. a. True b. False Incorrect. The correct answer is True. Ferrous metal raceways and enclosures must be electrically continuous to ensure proper grounding. Correct! Ferrous metal raceways and enclosures for grounding electrode conductors must be electrically continuous from the point of attachment to the cabinet or equipment to the grounding electrode, as specified in NEC Article 250.64(B). According to NEC Article 250.64(B), ferrous metal raceways and enclosures for grounding electrode conductors must indeed be electrically continuous from the point of attachment to the cabinet or equipment all the way to the grounding electrode to maintain an effective grounding system. Think about the typical minimum thickness specified for grounding electrodes to ensure they are durable and effective. 18 / 50 Grounding electrodes of bare or electrically conductive coated iron or steel plates must be at least how many inches thick? a. 30 in b. 18 in c. 8 ft d. 18 in Incorrect. The correct answer is 30 in. This thickness is essential for grounding electrodes to ensure their reliability and effectiveness. Correct! Grounding electrodes of bare or electrically conductive coated iron or steel plates must be at least 30 inches thick, as specified in NEC Article 250.52(A)(2). According to NEC Article 250.52(A)(2), grounding electrodes made of bare or electrically conductive coated iron or steel plates must be at least 30 inches thick to ensure proper functionality and resistance to corrosion. Consider the minimum size requirements for grounded conductors when installed alongside parallel ungrounded conductors. 19 / 50 Where service-entrance conductors are installed in parallel in two or more raceways or cables, the size of the grounded conductor in each raceway or cable shall be based on the total circular mil area of the parallel ungrounded service-entrance conductors in the raceway or cable, sized in accordance with 250.24(C)(1), but not smaller than ________ AWG. a. 2/0 b. 1/0 c. 4/0 d. 3/0 Incorrect. The correct answer is 1/0 AWG. This is the minimum size for the grounded conductor in this configuration. Correct! The size of the grounded conductor in each raceway or cable shall not be smaller than 1/0 AWG when service-entrance conductors are installed in parallel, as specified in NEC Article 250.24(C)(1). According to NEC Article 250.24(C)(1), when service-entrance conductors are installed in parallel, the grounded conductor must be sized based on the total circular mil area of the parallel ungrounded conductors, but it shall not be smaller than 1/0 AWG. Consider the environmental factors that might affect the integrity and functionality of grounding connections. 20 / 50 A rebar-type concrete-encased electrode installed in accordance with 250.52(A)(3) with an additional rebar section extended from its location within the concrete to an accessible location that is not subject to _____ shall be permitted for connection of grounding electrode conductors and bonding jumpers. a. any of these b. moisture c. physical damage d. corrosion Incorrect. The correct answer is corrosion. This condition must be met to ensure the effectiveness of the grounding connection. Correct! A rebar-type concrete-encased electrode with an additional rebar section must not be subject to corrosion to be permitted for connecting grounding electrode conductors and bonding jumpers, as specified in NEC Article 250.52(A)(3). According to NEC Article 250.52(A)(3), a rebar-type concrete-encased electrode with an additional rebar section that extends to an accessible location must not be subject to corrosion for it to be used for the connection of grounding electrode conductors and bonding jumpers. Think about the maximum number of auxiliary equipment grounding conductors allowed when multiconductor cables are used in parallel. 21 / 50 If multiconductor cables are installed in parallel in the same raceway, auxiliary gutter, or cable tray, _____ equipment grounding conductor(s) that is(are) sized in accordance with 250.122 shall be permitted in combination with the equipment grounding conductors provided within the multiconductor cables and shall all be connected together. a. two b. one c. three d. four Incorrect. The correct answer is one. Only one auxiliary equipment grounding conductor is allowed in combination with the multiconductor cables. Correct! If multiconductor cables are installed in parallel, one equipment grounding conductor sized in accordance with NEC Article 250.122 is permitted in combination with the existing grounding conductors within the cables. According to NEC Article 250.122, if multiconductor cables are installed in parallel within the same raceway, auxiliary grounding conductors may be used. Specifically, one equipment grounding conductor that is sized in accordance with the article is permitted in combination with the equipment grounding conductors provided within the multiconductor cables, and all must be connected together. Therefore, the correct answer is one. Think about the types of circuits that the equipment grounding conductor can be based on when conductors are installed in parallel. 22 / 50 If circuit conductors are installed in parallel in the same raceway or cable tray, a single wire-type conductor shall be permitted as the equipment grounding conductor and sized in accordance with 250.122, based on the overcurrent protective device for the ____. a. feeder b. a or b c. none of these d. branch circuit Incorrect. The correct answer is a or b. The equipment grounding conductor can be sized based on either the feeder or branch circuit overcurrent protective device. Correct! A single wire-type conductor used as the equipment grounding conductor can be sized in accordance with NEC Article 250.122, based on the overcurrent protective device for either the feeder or the branch circuit. According to NEC Article 250.122, if circuit conductors are installed in parallel in the same raceway or cable tray, a single wire-type conductor may be used as the equipment grounding conductor. This conductor must be sized according to the requirements based on the overcurrent protective device for either the feeder or the branch circuit. Thus, the correct answer is a or b. Consider the NEC provisions regarding the use of building frames as grounding electrodes and the requirements for bonding jumpers. 23 / 50 A separate water piping bonding jumper shall be required if the metal frame of a building or structure is used as the grounding electrode for a separately derived system and is bonded to the metal water piping in the area served by the separately derived system. a. False b. True Incorrect. The correct answer is False. A separate water piping bonding jumper is not needed in this scenario as specified in the NEC. Correct! A separate water piping bonding jumper is not required if the metal frame of the building is used as the grounding electrode and is already bonded to the metal water piping, as stated in NEC Article 250.104. According to NEC Article 250.104, if the metal frame of a building or structure is used as the grounding electrode for a separately derived system and is already bonded to the metal water piping in the area served, a separate water piping bonding jumper is not required. Therefore, the statement is False. Consider the minimum dimensions necessary for effective grounding and bonding in electrical installations. 24 / 50 Bonding jumper(s) from grounding electrode(s) shall be permitted to be connected to an aluminum or copper busbar not less than _____ and of sufficient length to accommodate the number of terminations necessary for the installation in accordance with 250.64(F). a. ¼ in. thick x 2 in. wide b. 1/8 in. thick x 1 in. wide c. ¼ in. thick x 1 in. wide d. 1/8 in. thick x 2 in. wide Incorrect. The correct answer is ¼ in. thick x 2 in. wide. This dimension ensures that the busbar is adequate for grounding connections. Correct! Bonding jumper(s) from grounding electrode(s) may be connected to an aluminum or copper busbar not less than ¼ in. thick x 2 in. wide, as specified in NEC Article 250.64(F). According to NEC Article 250.64(F), bonding jumper(s) from grounding electrode(s) may be connected to an aluminum or copper busbar that is not less than ¼ in. thick x 2 in. wide and of sufficient length to accommodate the necessary terminations for the installation. Think about the maximum overcurrent device ratings that allow for the use of FMC as an equipment grounding conductor in compliance with the NEC. 25 / 50 Listed FMC can be used as the equipment grounding conductor if the length in any ground return path does not exceed 6 ft and the circuit conductors contained in the conduit are protected by overcurrent devices rated at ____ or less. a. 60A b. 20A c. 30A d. 15A Incorrect. The correct answer is 20A. FMC can only be used as an equipment grounding conductor if the overcurrent devices are rated at this value or less. Correct! Listed FMC can be used as the equipment grounding conductor if the length in any ground return path does not exceed 6 ft and the circuit conductors are protected by overcurrent devices rated at 20A or less, as specified in NEC Article 250.118. According to NEC Article 250.118, listed FMC can be used as the equipment grounding conductor if the length in any ground return path does not exceed 6 ft and the circuit conductors contained in the conduit are protected by overcurrent devices rated at 20A or less. Thus, the correct answer is 20A. Consider the minimum gauge requirement for grounding electrode conductors that necessitate protection due to potential physical damage. 26 / 50 A(n) __ ___AWG or larger copper or aluminum grounding electrode conductor exposed to physical damage shall be protected in rigid metal conduit, IMC, PVC conduit, reinforced thermosetting resin conduit Type XW (RTRC-XW), EMT, or cable armor. a. 6 b. 4 c. 8 d. 10 Incorrect. The correct answer is 6 AWG. This gauge requires protection when the grounding electrode conductor is exposed to physical damage. Correct! A(n) 6 AWG or larger copper or aluminum grounding electrode conductor exposed to physical damage must be protected, as specified in NEC Article 250.64. According to NEC Article 250.64, a copper or aluminum grounding electrode conductor that is 6 AWG or larger and exposed to physical damage must be protected using rigid metal conduit, IMC, PVC conduit, reinforced thermosetting resin conduit Type XW (RTRC-XW), EMT, or cable armor. Consider the minimum size requirements for grounding conductors in the context of multiconductor cables. 27 / 50 Sectioned equipment grounding conductors smaller than ____ AWG shall be permitted in multiconductor cables, if the combined circular mil area of the sectioned equipment grounding conductors in each cable complies with 250.122. a. 1 b. 1/0 c. 2 d. 3 Incorrect. The correct answer is 1/0. Sectioned equipment grounding conductors smaller than this size can be used if the combined area meets the requirements. Correct! Sectioned equipment grounding conductors smaller than 1/0 AWG are permitted in multiconductor cables, provided the combined circular mil area complies with NEC Article 250.122. According to NEC Article 250.122, sectioned equipment grounding conductors smaller than 1/0 AWG are permitted in multiconductor cables as long as the combined circular mil area of the sectioned conductors in each cable complies with the specified requirements. Therefore, the correct answer is 1/0. Think about the accessibility requirements for bonding jumpers in electrical installations. 28 / 50 The bonding jumper used to bond the metal shall be installed in accordance with 250.64(A), 250.64(B), and 250.64(E) and the points of attachment of the bonding jumper(s) shall be _______. a. accessible b. readily accessible c. none of these d. a or b Incorrect. The correct answer is a or b. Both “readily accessible” and “accessible” apply to the points of attachment for bonding jumpers. Correct! The bonding jumper must be installed in accordance with NEC Article 250.64, and the points of attachment of the bonding jumper(s) shall be accessible. According to NEC Article 250.64, the bonding jumper must be installed as specified in subsections (A), (B), and (E), and the points of attachment of the bonding jumper(s) must be accessible. Therefore, the correct answer is a or b, as both terms imply accessibility. Think about the minimum number of terminations needed for proper bonding connections in communications systems. 29 / 50 Communications system bonding termination connections to an aluminum or copper busbar shall not be less than ¼ in. thick x 2 in. wide and of sufficient length to accommodate at least ____ terminations for communications systems in addition to other connections. a. 3 b. 5 c. 2 d. 4 Incorrect. The correct answer is three. This number ensures that the busbar can accommodate the necessary terminations for communications systems. Correct! Communications system bonding termination connections must accommodate at least three terminations for communications systems, as specified in NEC Article 250.94. According to NEC Article 250.94, communications system bonding termination connections to an aluminum or copper busbar must be at least ¼ in. thick x 2 in. wide and of sufficient length to accommodate at least three terminations for communications systems, in addition to other connections. Consider the conditions under which certain grounding components are exempt from specific installation requirements. 30 / 50 Grounding electrode conductors and grounding electrode bonding jumpers in contact with ______ shall not be required to comply with 300.5, but shall be buried or otherwise protected if subject to physical damage. a. the earth b. water c. metal d. all of these Incorrect. The correct answer is the earth. Grounding components in contact with the earth are not subject to the same installation requirements. Correct! Grounding electrode conductors and grounding electrode bonding jumpers in contact with the earth are not required to comply with 300.5, as specified in NEC Article 250.64. According to NEC Article 250.64, grounding electrode conductors and grounding electrode bonding jumpers in contact with the earth are not required to comply with 300.5 but must be buried or otherwise protected if they are subject to physical damage. Consider the minimum gauge requirements for grounding electrode conductors that allow for surface installation without additional protection. 31 / 50 Grounding electrode conductors ______ AWG and larger that are not exposed to physical damage can be run along the surface of the building construction without metal covering or protection. a. 6 b. 10 c. 8 d. 4 Incorrect. The correct answer is 6 AWG. This gauge allows grounding electrode conductors to be installed without additional protection when not exposed to physical damage. Correct! Grounding electrode conductors 6 AWG and larger that are not exposed to physical damage can be run along the surface of the building construction without metal covering or protection, as specified in NEC Article 250.64. According to NEC Article 250.64, grounding electrode conductors that are 6 AWG and larger, when not exposed to physical damage, can be run along the surface of the building construction without the need for metal covering or additional protection. Think about which table in the NEC provides the appropriate sizing for bonding conductors specifically for metal water piping systems. 32 / 50 A building or structure shall have the interior metal water piping system bonded with an equipment grounding conductor sized in accordance with __________. a. Table 310.15(B)(16) b. Table 250.122 c. Table 250.102(C)(1) d. none of these Incorrect. The correct answer is Table 250.102(C)(1). This table is specifically designated for sizing equipment grounding conductors for metal water piping systems. Correct! The interior metal water piping system in a building or structure shall be bonded with an equipment grounding conductor sized in accordance with Table 250.102(C)(1), as specified in NEC Article 250.102. According to NEC Article 250.102, a building or structure must have the interior metal water piping system bonded with an equipment grounding conductor sized in accordance with Table 250.102(C)(1). This table specifies the sizing based on the size of the supply conductors. Think about which component’s rating determines the sizing of bonding jumpers for the water piping system in a building with multiple occupancies. 33 / 50 Where isolated metal water piping systems are installed in a multiple-occupancy building, the water pipes can be bonded with bonding jumpers sized in accordance with Table 250.122, based on the size of the _______. a. rating of the service equipment devices b. feeder conductors c. service entrance conductors d. rating of the largest overcurrent device supplying the occupancy Incorrect. The correct answer is rating of the largest overcurrent device supplying the occupancy. This rating is used to size the bonding jumpers for isolated metal water piping systems. Correct! The bonding jumpers for isolated metal water piping systems in a multiple-occupancy building can be sized according to Table 250.122, based on the rating of the largest overcurrent device supplying the occupancy, as specified in NEC Article 250.104. According to NEC Article 250.104, where isolated metal water piping systems are installed in a multiple-occupancy building, the bonding jumpers can be sized in accordance with Table 250.122, based on the rating of the largest overcurrent device supplying the occupancy. This ensures that the bonding jumper is appropriately sized for the electrical load and safety requirements. Think about the acceptable minimum sizes for conductors used for grounding in various materials. 34 / 50 The common grounding electrode conductor installed for multiple separately derived systems shall be permitted to be the metal structural frame of the building or structure that complies with 250.68(C)(2) or is connected to the grounding electrode system by a conductor not smaller than __. a. a or b b. none of these c. 3/0 copper d. 250 kcmil aluminum Incorrect. The correct answer is a or b. The conductor connected to the grounding electrode system must meet the specified minimum size requirements. Correct! The common grounding electrode conductor installed for multiple separately derived systems may be connected using a conductor not smaller than either 3/0 copper or 250 kcmil aluminum, as stated in NEC Article 250.68(C)(2). According to NEC Article 250.68(C)(2), the common grounding electrode conductor can be connected to the metal structural frame of the building, and the conductor must not be smaller than either 3/0 copper or 250 kcmil aluminum, making the correct answer a or b. Consider the scenarios where bonding conductors are necessary based on the usage of communications systems. 35 / 50 Means for connecting intersystem bonding conductors are not required where communications systems are not likely to be used. a. True b. False Incorrect. The correct answer is True. Inactive communications systems do not necessitate bonding connections. Correct! Means for connecting intersystem bonding conductors are not required where communications systems are not likely to be used, as specified in NEC Article 250.94. According to NEC Article 250.94, means for connecting intersystem bonding conductors are not required in situations where communications systems are not likely to be used, indicating that bonding requirements are contingent upon the presence of such systems. Think about the role of grounding electrodes in establishing a safe electrical system. 36 / 50 The building or structure grounding electrode system shall be used as the _____ electrode for the separately derived system. a. bonded b. grounded c. grounding d. bonding Incorrect. The correct answer is grounding. This establishes the necessary grounding connection for the separately derived system. Correct! The building or structure grounding electrode system shall be used as the grounding electrode for the separately derived system, as specified in NEC Article 250.30. According to NEC Article 250.30, the building or structure grounding electrode system must be used as the grounding electrode for the separately derived system, ensuring effective grounding and safety. Consider the conditions under which metal gas piping can be considered bonded in relation to grounding electrodes. 37 / 50 Metal gas piping installed in or attached to a building shall be considered bonded when one or more grounding electrodes are used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size. a. False b. True Incorrect. The correct answer is True. Metal gas piping is considered bonded when connected to grounding electrodes with appropriately sized conductors. Correct! Metal gas piping installed in or attached to a building is considered bonded when one or more grounding electrodes are used, as specified in NEC Article 250.104(B). According to NEC Article 250.104(B), metal gas piping that is installed in or attached to a building is considered bonded when one or more grounding electrodes are utilized, provided that the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size. Thus, the statement is True. Consider the maximum distance allowed for interior metal water piping to effectively connect to grounding electrodes. 38 / 50 Interior metal water piping that is electrically continuous with a metal underground water pipe electrode and is located not more than __ ___ ft from the point of entrance to the building shall be permitted to extend the connection to an electrode(s). a. 6 b. 4 c. 2 d. 5 Incorrect. The correct answer is 5 ft. This distance is the maximum allowed for the connection to be made effectively. Correct! Interior metal water piping that is electrically continuous with a metal underground water pipe electrode and located not more than 5 ft from the point of entrance to the building is permitted to extend the connection to an electrode(s), as specified in NEC Article 250.68(A). According to NEC Article 250.68(A), interior metal water piping that is electrically continuous with a metal underground water pipe electrode and is located not more than 5 ft from the point of entrance to the building may be used to extend the connection to grounding electrodes. Think about the minimum surface area needed for effective grounding in soil. 39 / 50 A buried iron or steel plate used as a grounding electrode shall expose not less than _______ sq ft of surface area to exterior soil. a. 9 b. 10 c. 4 d. 2 Incorrect. The correct answer is 2 sq ft. This is the minimum surface area required for buried iron or steel plates to function effectively as grounding electrodes. Correct! A buried iron or steel plate used as a grounding electrode must expose not less than 2 sq ft of surface area to exterior soil, as specified in NEC Article 250.52(A)(2). According to NEC Article 250.52(A)(2), a buried iron or steel plate used as a grounding electrode must expose not less than 2 sq ft of surface area to the exterior soil to ensure proper grounding effectiveness. Think about the materials that are typically used for bonding jumpers to ensure effective grounding and bonding. 40 / 50 Equipment bonding jumpers shall be of copper, aluminum, copper-clad aluminum, or other corrosion-resistant material. a. True b. False Incorrect. The correct answer is True. Bonding jumpers must be made from these specified materials to meet safety requirements. Correct! Equipment bonding jumpers must be made of copper, aluminum, copper-clad aluminum, or other corrosion-resistant materials, as specified in NEC Article 250.102. According to NEC Article 250.102, equipment bonding jumpers must be made of copper, aluminum, copper-clad aluminum, or other corrosion-resistant materials to ensure reliability and longevity in grounding applications. Consider the various components to which metal water piping systems can be bonded for effective grounding. 41 / 50 Metal water piping system(s) shall be bonded to the ____________, or to one or more grounding electrodes used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size. a. service equipment enclosure b. grounded conductor at the service c. grounding electrode if of sufficient size d. any of these Incorrect. The correct answer is any of these. Metal water piping systems can be bonded to any of the specified components to ensure effective grounding. Correct! Metal water piping systems shall be bonded to the grounded conductor at the service, the service equipment enclosure, or to the grounding electrode if of sufficient size, as specified in NEC Article 250.104. According to NEC Article 250.104, metal water piping systems must be bonded to the grounded conductor at the service, the service equipment enclosure, or the grounding electrode, provided that the grounding electrode conductor or bonding jumper is of sufficient size. Therefore, the correct answer is any of these. Consider the specific NEC requirements for bonding between metal systems and separately derived systems. 42 / 50 Metal water piping systems and structural metal that is interconnected to form a building frame shall be bonded to separately derived systems in accordance with 250.104(D)(1) through 250.104(D)(3). a. True b. False Incorrect. The correct answer is True. Metal water piping systems and structural metal must be bonded to separately derived systems per NEC requirements. Correct! Metal water piping systems and structural metal that is interconnected to form a building frame shall be bonded to separately derived systems as specified in NEC Article 250.104(D). According to NEC Article 250.104(D), metal water piping systems and structural metal that forms a building frame must be bonded to separately derived systems in accordance with the provisions outlined in sections 250.104(D)(1) through 250.104(D)(3). Therefore, the statement is True. Consider the NEC guidelines for bonding exposed structural metal to grounded conductors in separately derived systems. 43 / 50 If exposed structural metal that is interconnected to form the building frame exists in the area served by the separately derived system, it shall be bonded to the grounded conductor of each separately derived system, and each bonding jumper shall be sized in accordance with Table 250.102(C)(1) based on the largest ungrounded conductor of the separately derived system. a. True b. False Incorrect. The correct answer is True. The NEC requires bonding of exposed structural metal to grounded conductors based on specified sizing. Correct! Exposed structural metal that is interconnected to form the building frame must be bonded to the grounded conductor of each separately derived system, as specified in NEC Article 250.104. According to NEC Article 250.104, if exposed structural metal that is interconnected to form the building frame exists in the area served by the separately derived system, it must be bonded to the grounded conductor of each separately derived system. Additionally, each bonding jumper must be sized according to Table 250.102(C)(1) based on the largest ungrounded conductor of the separately derived system. Therefore, the statement is True. Consider the primary factor that dictates the size of the equipment grounding conductor for multiconductor cables as per NEC guidelines. 44 / 50 Except as provided in 250.122(F)(2)(b) for raceway or cable tray installations, the equipment grounding conductor in each multiconductor cable shall be sized in accordance with 250.122 based on the ____. a. overcurrent protective device for the feeder or branch circuit b. smallest branch circuit conductor c. largest circuit conductor d. overcurrent protective device for the service Incorrect. The correct answer is overcurrent protective device for the feeder or branch circuit. The sizing of the equipment grounding conductor is based on this parameter. Correct! The equipment grounding conductor in each multiconductor cable shall be sized according to the overcurrent protective device for the feeder or branch circuit, as specified in NEC Article 250.122. According to NEC Article 250.122, the equipment grounding conductor in each multiconductor cable must be sized based on the overcurrent protective device for the feeder or branch circuit, except as provided in 250.122(F)(2)(b) for raceway or cable tray installations. Therefore, the correct answer is overcurrent protective device for the feeder or branch circuit. Think about the minimum dimensions that ensure effective electrical connections and mechanical stability. 45 / 50 Tap connections to a common grounding electrode conductor for multiple separately derived systems may be made to a copper or aluminum busbar that is _______ and of sufficient length to accommodate the number of terminations necessary for the installation. a. smaller than ¼ in. thick x 4 in. wide b. none of these c. not smaller than ½ in. thick x 2 in. wide d. not smaller than ¼ in. thick x 2 in. wide Incorrect. The correct answer is not smaller than ¼ in. thick x 2 in. wide. This specification ensures the busbar can accommodate the necessary terminations. Correct! Tap connections to a common grounding electrode conductor may be made to a copper or aluminum busbar that is not smaller than ¼ in. thick x 2 in. wide, as specified in NEC Article 250.68(D). According to NEC Article 250.68(D), tap connections to a common grounding electrode conductor for multiple separately derived systems may be made to a copper or aluminum busbar that is not smaller than ¼ in. thick x 2 in. wide to ensure proper function and safety. Think about the maximum distance allowed for using interior metal water piping in grounding electrode systems. 46 / 50 Interior metal water piping that is electrically continuous with a metal underground water pipe electrode and is located more than ____ ft from the point of entrance to the building shall not be used as a conductor to interconnect electrodes of the grounding electrode system. a. 4 b. 6 c. 5 d. 2 Incorrect. The correct answer is 5 ft. This distance defines the limitation for using the interior metal water piping in grounding systems. Correct! Interior metal water piping that is electrically continuous with a metal underground water pipe electrode and located more than 5 ft from the point of entrance to the building shall not be used as a conductor to interconnect electrodes of the grounding electrode system, as specified in NEC Article 250.68(A). According to NEC Article 250.68(A), interior metal water piping that is electrically continuous with a metal underground water pipe electrode and is located more than 5 ft from the point of entrance to the building shall not be used as a conductor to interconnect electrodes of the grounding electrode system. Think about the minimum number of disconnecting means that triggers specific grounding requirements. 47 / 50 If a building or structure is supplied by a service or feeder with _____ or more disconnecting means in separate enclosures, the grounding electrode connections shall be made in accordance with 250.64(D)(1), 250.64(D)(2), or 250.64(D)(3). a. two b. three c. one d. four Incorrect. The correct answer is two. This is the minimum number of disconnecting means that require adherence to specific grounding electrode connection rules. Correct! If a building or structure is supplied by a service or feeder with two or more disconnecting means in separate enclosures, the grounding electrode connections must comply with NEC Article 250.64(D). According to NEC Article 250.64(D), if a building or structure is supplied by a service or feeder with two or more disconnecting means in separate enclosures, the grounding electrode connections must be made in accordance with the specified subsections. Consider the thickness necessary to ensure durability and effectiveness as a grounding electrode. 48 / 50 Grounding electrodes of bare or electrically conductive coated iron or steel plates shall be at least __ in. thick. a. 3/4 b. 1/2 c. 1/4 d. 1/8 Incorrect. The correct answer is 1/4 inch. This thickness is necessary for grounding electrodes to ensure reliability and effectiveness. Correct! Grounding electrodes of bare or electrically conductive coated iron or steel plates must be at least 1/4 inch thick, as specified in NEC Article 250.52(A)(2). According to NEC Article 250.52(A)(2), grounding electrodes made of bare or electrically conductive coated iron or steel plates must be at least 1/4 inch thick to ensure proper functionality and resistance to corrosion. Think about the conditions under which structural metal can be deemed bonded in relation to grounding electrodes. 49 / 50 Exposed structural metal interconnected to form a metal building frame that is not intentionally grounded or bonded and is likely to become energized shall be considered bonded when one or more grounding electrodes are used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size. a. True b. False Incorrect. The correct answer is True. Exposed structural metal is considered bonded when connected to grounding electrodes with appropriately sized conductors. Correct! Exposed structural metal interconnected to form a metal building frame is considered bonded when one or more grounding electrodes are used, as specified in NEC Article 250.104(B). According to NEC Article 250.104(B), exposed structural metal that is interconnected and likely to become energized is considered bonded when it is connected to one or more grounding electrodes, provided that the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size. Thus, the statement is True. Think about the implications of how bonding jumpers can affect the grounding system. 50 / 50 If a building or structure is supplied by a feeder from an outdoor separately derived system, a system bonding jumper at both the source and the first disconnecting means shall be permitted if doing so does not establish a __ path for the grounded conductor. a. series b. parallel c. series-parallel d. none of these Incorrect. The correct answer is parallel. Establishing a parallel path for the grounded conductor can create issues in the grounding system. Correct! A system bonding jumper at both the source and the first disconnecting means shall be permitted if it does not establish a parallel path for the grounded conductor, as specified in NEC Article 250.30. According to NEC Article 250.30, when a building or structure is supplied by a feeder from an outdoor separately derived system, establishing a bonding jumper at both the source and the first disconnecting means is allowed only if it does not create a parallel path for the grounded conductor, which could lead to unwanted current flow. Your score is LinkedIn Facebook Twitter 0% Restart quiz Exit Rate & Review Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services. Send feedback Leave a Reply Cancel replyYour email address will not be published. Required fields are marked * Comment* Name* Email* Website Save my name, email, and website in this browser for the next time I comment. Post Comment