eep April 7, 2025 NEC 200-285 NEC Quizzes Report a question What’s wrong with this question? You cannot submit an empty report. Please add some details. 0% Article 200-285 Part09 This comprehensive quiz contains 50 questions carefully selected from the National Electrical Code (NEC) Articles spanning 200 through 285. These articles cover a broad spectrum of vital topics related to electrical installations within this section of the code. The questions in this quiz are chosen randomly to provide a thorough assessment of your knowledge across these essential NEC articles. While we strive for a diverse set of questions, some fundamental principles may be revisited in different contexts due to their relevance to multiple sections within this range. This approach ensures a robust evaluation of your understanding. We encourage you to actively participate and provide feedback. If you identify any issues or have suggestions for improving the quiz questions, please report them. Your contributions are invaluable in helping us maintain the accuracy and effectiveness of these learning resources. Access to overcurrent protection is essential for safety and maintenance. 1 / 50 The occupants of the various businesses in the commercial building must have access to the overcurrent devices for their branch circuits, 240.24(B). a. False b. True Incorrect. Access to overcurrent devices is necessary for safety. Correct! Occupants must have access to these devices. NEC mandates that occupants have access to overcurrent devices for their specific branch circuits to ensure safety and enable maintenance. Look for the standard ampere ratings commonly used in electrical systems. 2 / 50 Select all the standard ampere ratings for fuses and nonadjustable circuit breakers. a. 30 b. 10 c. 25 d. 35 e. 20 f. 15 Incorrect. This value is not a standard ampere rating according to the NEC. Correct! These are standard ampere ratings as per NEC Table 240.6(A). NEC Table 240.6(A) lists the standard ampere ratings for fuses and nonadjustable circuit breakers, including 15, 20, 25, 30, and 35 amperes. Consider the function specified for the main bonding jumper according to NEC 250.28(D). 3 / 50 What is the purpose of the main bonding jumper according to NEC 250.28(D)? a. To connect equipment grounding conductors b. To bond grounding electrodes c. To bond equipment enclosures d. To connect the neutral bus bar to the service equipment enclosure This choice doesn’t accurately reflect the function specified for the main bonding jumper according to NEC 250.28(D). Right! The main bonding jumper connects the neutral bus bar to the service equipment enclosure, as per NEC 250.28(D). The main bonding jumper connects the neutral bus bar to the service equipment enclosure, as per NEC 250.28(D). Consider the function of the grounding electrode conductor and its sizing as specified in the NEC. 4 / 50 What is the purpose of sizing the grounding electrode conductor according to NEC Table 250.66? a. To determine ampacity b. To measure voltage c. To connect the grounding electrode to the system grounded (neutral) conductor d. To calculate resistance This choice doesn’t accurately reflect the purpose of sizing the grounding electrode conductor according to NEC Table 250.66. Correct! Sizing the grounding electrode conductor is primarily to connect the grounding electrode to the system grounded (neutral) conductor, as per NEC requirements. Sizing the grounding electrode conductor according to NEC Table 250.66 is primarily to connect the grounding electrode to the system grounded (neutral) conductor. Consider the criterion specified in NEC Table 250.122 for selecting equipment grounding conductors. 5 / 50 How are equipment grounding conductors selected when there is overcurrent protection ahead of the equipment according to NEC Table 250.122? a. By the current setting or rating of the overcurrent device b. By the phase c. By the type of equipment d. By conductor length This choice doesn’t accurately reflect the criterion specified in NEC Table 250.122 for selecting equipment grounding conductors. Correct! Equipment grounding conductors are selected based on the current setting or rating of the overcurrent device ahead of the equipment, as per NEC Table 250.122. Equipment grounding conductors are selected based on the current setting or rating of the overcurrent device ahead of the equipment, as per NEC Table 250.122. Continuous loads have specific NEC guidelines regarding breaker loading. 6 / 50 A circuit breaker is not permitted to be loaded to more than 80% of its current rating for loads that are likely to be on for _ hours or more. a. 2 b. 3 c. 1 d. 4 Incorrect. NEC specifies a 3-hour minimum for this rule. Correct! This rule applies to loads expected to be on for 3 hours or more. For continuous loads, circuit breakers should not be loaded beyond 80% of their rating to ensure safe and reliable operation. Look for the section of the NEC that specifically addresses the requirements for multiwire branch circuits. 7 / 50 NEC _______ contains the requirements for multiwire branch circuits. a. 260.8 b. 210.65 c. 410.65 d. 210.4 Incorrect. The correct answer is 210.4. Great job! NEC 210.4 covers the requirements for multiwire branch circuits. The correct answer is 210.4. This section of the NEC contains the requirements for multiwire branch circuits, including their installation and safety considerations. Consider the requirement specified in NEC 250.70 regarding the connection of grounding electrode conductors. 8 / 50 What is required for the connection of grounding electrode conductors according to NEC 250.70? a. Twisting b. Soldering c. Proper lugs, connectors, clamps, or other approved means d. Welding This method isn’t typically used for the connection of grounding electrode conductors as specified in NEC 250.70. Right! The connection of grounding electrode conductors must be made using proper lugs, connectors, clamps, or other approved means, as per NEC 250.70. The connection of grounding electrode conductors must be made using proper lugs, connectors, clamps, or other approved means, as per NEC 250.70. Consider the purpose of an effective ground-fault current path as stated in the text. 9 / 50 What is an effective ground-fault current path intended to do? a. Reduce electrical resistance b. Discharge static electricity c. Prevent overcurrent d. Carry current under ground-fault conditions This answer doesn’t align with the function of an effective ground-fault current path as described in the NEC. Right! An effective ground-fault current path is designed to carry current under ground-fault conditions, as explained in the NEC. An effective ground-fault current path is designed to carry current under ground-fault conditions, facilitating the operation of overcurrent protective devices or ground-fault detectors. 10 / 50 Noncontinuous loads are calculated for 125% of the load. a. True b. False In electrical wiring calculations, we differentiate between continuous and noncontinuous loads. This distinction is important when determining the minimum allowable ampacity (current-carrying capacity) of conductors and overcurrent protection devices (like circuit breakers). Continuous Loads: These are loads that operate for extended periods or are expected to be on for a significant portion of the time. Examples include lighting in commercial buildings, electric heaters, and continuously running motors. Noncontinuous Loads: These are loads that operate for shorter durations or are not expected to be on for a large portion of the time. Examples include kitchen appliances, air conditioners, and bathroom exhaust fans. When sizing conductors and selecting circuit breakers, the NEC (National Electrical Code) requires applying a 125% demand factor to continuous loads. This means the continuous load is multiplied by 1.25 to account for potential starting surges or unexpected increases in current draw. On the other hand, noncontinuous loads are simply added at their actual rated loads without any additional multiplication factor. This is because they are not expected to be operating simultaneously with all the other loads on the circuit. 11 / 50 Branch circuit, Appliance: a. Supplies receptacles or outlets for lighting and appliances b. Ungrounded conductors that have voltage and a grounded conductor that has equal voltage; connected to the neutral or grounded conductor of the system c. Supplies only one utilization equipment d. Supplies outlets to appliances A branch circuit specifically designated as an appliance branch circuit is designed to supply power to one or more appliances through outlets or receptacles. Here's a breakdown of the key points: Focus: Appliance branch circuits prioritize powering appliances, as opposed to general lighting or a mix of both. Number of Outlets: While they can have multiple outlets, these outlets are intended for appliances, not necessarily a combination of appliances and lighting fixtures. Dedicated Circuit: Appliance circuits are often dedicated circuits, meaning they supply power to a single appliance to avoid overloading the circuit. This is especially important for appliances with high current draw. 12 / 50 What is the maximum rating or setting of a dual element (time-Delay) fuse for a single-phase motor? a. 125% b. 150% c. 175% The maximum rating for a dual element (time-delay) fuse for a single-phase motor is 175%. However, it's important to understand the context: This is not a universal rule. The National Electrical Code (NEC) typically recommends a maximum of 125% of the motor's full-load current (FLA) for such fuses. The 175% allowance applies under specific conditions, such as: Certain motor types known for starting current surges within the 175% limit. The motor manufacturer's specific instructions, if they recommend a 175% fuse rating. Pay attention to the conditions specified in NEC 250.104(B) for bonding metal gas piping. 13 / 50 What is the condition under which metal gas piping must be bonded according to NEC 250.104(B)? a. Always b. Never c. When likely to become energized d. When there's a gas leak Metal gas piping isn’t required to be bonded under all conditions; there’s a specific condition outlined in the NEC. Right! Metal gas piping must be bonded when likely to become energized, as per NEC 250.104(B). Metal gas piping must be bonded when it is likely to become energized, as stated in NEC 250.104(B). Consider the requirement specified in the NEC regarding bonding when sections of electrical equipment are bolted together. 14 / 50 What must be done to ensure effective bonding when sections of electrical equipment are bolted together? a. Tighten securely b. Remove nonconductive paint, enamel, or similar coating c. Insulate contact points d. Apply conductive paint This action doesn’t align with the requirement specified in the NEC for effective bonding when sections of electrical equipment are bolted together. Right! To ensure effective bonding, nonconductive paint, enamel, or similar coating must be removed at contact points when sections of electrical equipment are bolted together, as specified in the NEC. To ensure effective bonding when sections of electrical equipment are bolted together, nonconductive paint, enamel, or similar coating must be removed at contact points. Consider the function of bonding as described in the text. 15 / 50 What is the primary purpose of bonding in electrical systems? a. Prevent overcurrent b. Establish electrical continuity and conductivity c. Isolate electrical components d. Reduce voltage fluctuations This answer doesn’t accurately reflect the primary purpose of bonding as defined in the NEC. Correct! The primary purpose of bonding is to establish electrical continuity and conductivity between metal parts, as described in the NEC. Bonding is primarily aimed at establishing electrical continuity and conductivity between metal parts required to be electrically connected. Consider the function specified for NEC Table 250.122 according to the NEC. 16 / 50 What is the purpose of NEC Table 250.122? a. To size grounding electrode conductors b. To determine conductor resistance c. To select equipment grounding conductors d. To calculate impedance This choice doesn’t accurately reflect the purpose specified for NEC Table 250.122 in the NEC. Correct! NEC Table 250.122 is referred to for selecting equipment grounding conductors, as per NEC requirements. NEC Table 250.122 is referred to for selecting equipment grounding conductors when there is overcurrent protection ahead of the conductor supplying the equipment. Consider the requirement specified in NEC 250.68(B) regarding the length of bonding conductors. 17 / 50 What must be ensured about the length of bonding conductors according to NEC 250.68(B)? a. Measure it precisely b. Vary the length c. Make it long enough to remain in place if the equipment is removed d. Keep it short This choice doesn’t accurately reflect the requirement specified in NEC 250.68(B) regarding the length of bonding conductors. Correct! The length of bonding conductors must be long enough to remain in place if the equipment is removed, as per NEC 250.68(B). The length of bonding conductors must be long enough to remain in place if the equipment is removed, as per NEC 250.68(B). Consider the requirement mentioned in the NEC regarding the removal of certain materials for effective bonding. 18 / 50 What is required to be removed at contact points to ensure effective bonding of electrical equipment sections? a. Insulation b. Nonconductive paint, enamel, or similar coating c. Rust d. Corrosion This material isn’t typically a concern for bonding electrical equipment sections as per NEC requirements. Right! Nonconductive paint, enamel, or similar coating must be removed at contact points for effective bonding, as specified in the NEC. Nonconductive paint, enamel, or similar coating must be removed at contact points to ensure that sections of electrical equipment are effectively bonded, as per NEC requirements. Think about the devices designed to protect electrical circuits from overcurrent. 19 / 50 Two types of overcurrent protective devices are commonly used:____________________________ a. Circuit Breakers b. Transformers c. Fuses d. Panelboards Incorrect. These are not overcurrent protective devices. Correct! Fuses and circuit breakers are standard overcurrent protective devices. Fuses and circuit breakers are the primary devices used to protect electrical circuits by interrupting excessive currents. Consider the materials permitted for the grounding electrode conductor as specified in NEC 250.62. 20 / 50 What is the permitted material for the grounding electrode conductor according to NEC 250.62? a. Brass b. Copper, aluminum, or copper-clad aluminum c. Steel d. Silver This choice doesn’t accurately reflect the permitted materials specified in NEC 250.62 for the grounding electrode conductor. Right! The grounding electrode conductor is permitted to be copper, aluminum, or copper-clad aluminum, as per NEC 250.62. The grounding electrode conductor is permitted to be copper, aluminum, or copper-clad aluminum, according to NEC 250.62. 21 / 50 Metal raceways not properly grounded could become live and present a shock hazard. a. False b. True Proper grounding is a fundamental principle of electrical safety. It establishes a low-impedance path for fault current to return to the source, preventing dangerous voltage buildup on metal enclosures or raceways. Here's why metal raceways not properly grounded can be hazardous: Faulty Wiring: If a hot wire (carrying current) comes into contact with the metal raceway due to damaged insulation or faulty connections, the raceway can become energized. Shock Hazard: Anyone touching the ungrounded, energized raceway can complete the circuit and be subjected to a potentially lethal electric shock. Importance of Grounding: Grounding ensures that any fault current is diverted away from the raceway and safely channeled back to the source. This protects people and equipment from the dangers of accidental contact with energized metal components. Here are some additional points to consider: The National Electrical Code (NEC) has specific requirements for grounding electrical systems and equipment, including metal raceways. Proper grounding practices involve using grounding conductors and connecting them to designated grounding points within the electrical panel. By understanding the importance of grounding and following NEC guidelines, electricians can help ensure the safety of electrical installations. The definition provided in NEC Article 100 clarifies the meaning of “grounded.” 22 / 50 What is the definition of “grounded” according to NEC Article 100? a. Intentionally disconnected from ground b. Connected to any conductive body c. Connected to ground or to a conductive body that extends the ground connection d. Not connected to ground This definition doesn’t match the NEC’s definition provided in Article 100. Right! “Grounded” means connected to ground or to a conductive body that extends the ground connection, as defined in NEC Article 100. According to NEC Article 100, “grounded” means connected to ground or to a conductive body that extends the ground connection. Consider whether NEC regulations allow branch circuit wiring to pass through outlet boxes of incandescent luminaires. 23 / 50 Branch circuit wiring is not permitted to be passed through an outlet box that is an integral part of an incandescent luminaire unless the luminaire is identified for use. a. True b. False Incorrect. The correct answer is True. You’re correct! It is indeed true that branch circuit wiring cannot pass through such outlet boxes. True. According to NEC regulations, branch circuit wiring cannot pass through an outlet box integral to an incandescent luminaire unless identified for such use, ensuring safety and proper installation practices. 24 / 50 _____________or other fittings exposed to physical damage shall be enclosed in metal, wood, or equivalent protective covering. a. Ground rods b. Threaded Screws c. Ground Clamps d. Ground Rings The National Electrical Code (NEC) focuses on electrical safety, and grounding components are crucial for preventing electrical hazards. According to Section 250.10(C) of the NEC, ground clamps or other fittings exposed to physical damage shall be enclosed in metal, wood, or equivalent protective covering. Ground clamps: These metal devices connect grounding conductors to electrodes like ground rods or water pipes. They can be exposed during maintenance or accidental contact, so protection is necessary. Threaded screws: While used in grounding systems, they are not typically exposed elements requiring protection from physical damage. Ground rings: These are usually buried underground and not susceptible to physical damage. Ground rods: Though driven into the earth, they are typically below the surface and not exposed. Therefore, based on the NEC, ground clamps are the most likely element requiring protection from physical damage. 25 / 50 Branch circuit, general-purpose: a. Supplies outlets to appliances b. Supplies receptacles or outlets for lighting and appliances c. Supplies only one utilization equipment d. Ungrounded conductors that have voltage and a grounded conductor that has equal voltage; connected to the neutral or grounded conductor of the system A general-purpose branch circuit is the workhorse of electrical systems in homes and buildings. It offers the flexibility to power various devices through outlets or receptacles. Here's a breakdown of its key features: Multiple Receptacles/Outlets: A general-purpose circuit supplies power to multiple outlets or receptacles within a room or area, allowing you to plug in lamps, appliances, and other equipment as needed. Lighting and Appliances: These circuits can be used for both lighting fixtures and small appliances. You can connect a table lamp, a TV, a phone charger, or other portable equipment to a general-purpose outlet. Voltage: General-purpose circuits in North America are typically 120-volt circuits. 26 / 50 What Percent load factor must be applied for continuous loads? a. 100% b. 125% c. 80% The correct load factor to be applied for continuous loads is 125%. This is in accordance with the National Electrical Code (NEC). Continuous loads are those where the maximum current is expected to continue for 3 hours or more. The 125% factor is used to ensure that the system can handle the additional heat generated by the continuous load. 27 / 50 For general lighting in a commercial building use NEC Table _____ a. 310.16 b. 310.4 c. 220.12 The most appropriate NEC table for determining general lighting loads in commercial buildings is 220.12 – Lighting Load for Non-Dwelling Occupancies. Here's a breakdown of why: Article 220: This article covers branch circuit requirements. Section 220.12 specifically focuses on lighting load calculations for various types of occupancies, excluding dwellings. Table 220.12: This table provides unit load values in volt-amperes (VA) per square foot for different occupancy types. These values serve as a minimum baseline for calculating the required lighting load for a specific area in a commercial building. Other Tables: While other sections you mentioned might be relevant for electrical installations: 310.4: Covers derating factors for ampacity (current-carrying capacity) of conductors, not directly related to lighting loads. 310.16: Provides ampacity tables for various cable types and sizes, used for conductor selection based on ampacity requirements. 310.15(B)(1): Deals with ambient temperature correction factors for ampacity tables, not specifically for lighting load calculations. Consider the requirement specified in NEC 250.68(B) regarding insulating joints or sections of metal piping systems. 28 / 50 What is required around all insulating joints or sections of a metal piping system according to NEC 250.68(B)? a. Conductive tape b. Insulation c. Bonding d. Grounding paint This choice doesn’t accurately reflect the requirement specified in NEC 250.68(B) for insulating joints or sections of metal piping systems. Right! Bonding is required around all insulating joints or sections of a metal piping system, as outlined in NEC 250.68(B). Bonding is required around all insulating joints or sections of a metal piping system, as per NEC 250.68(B). 29 / 50 Which Article/Section Covers Small Conductors? {blank_1} a. 240.4(D) NEC Section 240.4(D) outlines requirements for protecting conductors against overcurrent, emphasizing the importance of ensuring that conductors are adequately sized and protected to handle the current load without overheating. This section specifies that conductors, except for flexible cords, flexible cables, and fixture wires, should be protected in accordance with their ampacities as specified in Table 310.16, unless otherwise permitted or required in other sections of the NEC. Therefore, while Section 240.4(D) addresses overcurrent protection, the specific guidelines for conductor ampacity are found in Article 310, particularly Table 310.16, which provides ampacity ratings for conductors based on various factors such as insulation type, ambient temperature, and the number of current-carrying conductors. Consider the NEC regulations regarding the installation of branch circuits from normal and emergency systems in the same conduit. 30 / 50 Branch circuits from a normal system are permitted to be installed in the same conduit with circuits from an emergency system. a. False b. True Incorrect. The correct answer is False. Well done! The correct answer is indeed False. Correct! According to NEC regulations, branch circuits from a normal system are not permitted to be installed in the same conduit with circuits from an emergency system, ensuring proper operation and safety during emergencies. 31 / 50 Branch circuit, multiwire: a. Supplies receptacles or outlets for lighting and appliances b. Supplies only one utilization equipment c. Ungrounded conductors that have voltage and a grounded conductor that has equal voltage; connected to the neutral or grounded conductor of the system d. Supplies outlets to appliances A multiwire branch circuit is characterized by having multiple ungrounded (hot) conductors sharing a common grounded (neutral) conductor. This wiring configuration allows for the simultaneous supply of multiple circuits while utilizing fewer conductors. Each ungrounded conductor has voltage, and the grounded conductor (neutral) has equal voltage, ensuring a balanced electrical system. Multiwire branch circuits are commonly used to supply outlets for appliances and other electrical devices. Consider whether NEC regulations require specific insulation for branch circuit conductors terminating in luminaires. 32 / 50 Branch circuit conductors that terminate in luminaires have an insulation suitable for the temperature encountered. a. True b. False Incorrect. The correct answer is True. ou got it! It’s true that branch circuit conductors must have suitable insulation. True. NEC regulations mandate that branch circuit conductors terminating in luminaires must have insulation suitable for the encountered temperature, ensuring safety and proper functioning. These devices provide quick protection by limiting current and preventing damage. 33 / 50 Fast-Acting, Current Limiting Fuses and circuit breakers are generally used for feeders and branch circuits. a. False b. True Incorrect. These devices are typically used in such applications. Correct! They are standard for feeders and branch circuits. Fast-acting, current-limiting fuses and circuit breakers protect electrical systems by quickly interrupting excessive currents in feeders and branch circuits. Grounding and bonding requirements are primarily addressed in a specific section of the NEC. 34 / 50 What is the primary coverage area for grounding and bonding in the NEC? a. Article 200 b. Article 300 c. Article 250 d. Article 100 Partially may cover but it’s not the primary coverage area for grounding and bonding. Correct! Article 250 of the NEC covers grounding and bonding requirements. Grounding and bonding requirements are primarily addressed in Article 250 of the NEC. Consider the article that specifically deals with overcurrent protection. 35 / 50 NEC Article ___ sets forth the requirements for overcurrent protection of conductors and for overcurrent devices. a. 200 b. 210 c. 220 d. 240 Incorrect. This article does not address overcurrent protection. Correct! Article 240 covers the requirements for overcurrent protection. NEC Article 240 provides comprehensive requirements for the protection of conductors and devices against overcurrent, ensuring safe electrical system operation. Multiwire branch circuits have specific requirements detailed in the NEC. 36 / 50 NEC _______ contains the requirements for multiwire branch circuits. a. 210.4 b. 210.65 c. 410.65 d. 260.8 Incorrect. This section does not address multiwire branch circuits. Correct! NEC 210.4 contains the necessary requirements for multiwire branch circuits. NEC 210.4 details the requirements for multiwire branch circuits, including their proper installation and safety considerations. The neutral conductor serves a specific function in electrical systems. 37 / 50 Which conductor is most often referred to as the neutral conductor? a. Green conductor b. Red conductor c. Black conductor d. White conductor The neutral conductor typically carries current and is commonly referred to as the neutral, not the white conductor. Correct! The neutral conductor, often white, is commonly referred to as the neutral in electrical systems. In most wiring, the neutral conductor, which is most often white, is intentionally grounded and is commonly referred to as the neutral. Standard circuit breaker ratings follow specific increments. 38 / 50 A 55A circuit breaker is a standard ampere rating. a. False b. True Incorrect. 55A is not a standard rating for circuit breakers. Correct! 55A is not a standard ampere rating for circuit breakers. Standard ampere ratings for circuit breakers do not include 55A, but follow specific standard values. Continuous loads have specific NEC limits unless the equipment is rated for full load. 39 / 50 Unless the overcurrent device and the equipment that encloses it such as a panelboard or enclosure is rated for operation at 100% of its rating, continuous loads (operating for three hours or more) are limited to not more than __% of the rating. a. 90 b. 75 c. 100 d. 80 Incorrect. This value does not meet NEC limits for continuous loads. Correct! 80% is the limit for continuous loads unless otherwise rated. Continuous loads should not exceed 80% of the overcurrent device’s rating unless specifically rated for 100% to prevent overheating and ensure safety. Consider the maximum height for accessibility and safety of disconnect switches. 40 / 50 The center of the grip of a disconnect switch handle in its highest position must be not more than _________ above the floor or working platform. a. 6 ft 7 in b. 6 ft 11 in c. 6 ft d. 6 ft 4 in Incorrect. This height does not meet NEC accessibility requirements. Correct! 6 ft 7 in is the maximum height for disconnect switch handles. NEC 240.24(A) specifies that the center of the grip of a disconnect switch handle in its highest position must be no more than 6 feet 7 inches above the floor or working platform to ensure accessibility and ease of use. Pay attention to the function specified for a main bonding jumper according to the NEC. 41 / 50 What is the function of a main bonding jumper according to NEC 250.28(D)? a. Connect the neutral bus bar to the service equipment enclosure b. Connect grounding electrodes c. Bond metal water piping d. Size bonding jumpers This function isn’t attributed to a main bonding jumper as described in the NEC. Right! A main bonding jumper connects the neutral bus bar to the service equipment enclosure, as outlined in the NEC. A main bonding jumper connects the neutral bus bar to the service equipment enclosure, as specified in NEC 250.28(D). Consider the reference provided in the NEC for sizing bonding jumpers on the supply side of the service. 42 / 50 How are bonding jumpers on the supply side of the service sized? a. According to conductor material b. According to wire gauge c. According to insulation type d. According to NEC Table 250.102(C)(1) This choice doesn’t accurately reflect the method specified in the NEC for sizing bonding jumpers. Correct! Bonding jumpers on the supply side of the service are sized according to NEC Table 250.102(C)(1). Bonding jumpers on the supply side of the service are sized according to NEC Table 250.102(C)(1). Consider access requirements for overcurrent protection in commercial buildings. 43 / 50 As long as a qualified electrician has access to the overcurrent devices to the branch circuit, it does not matter if the commercial building’s tenant has access to it. a. True b. False Incorrect. Tenants must have access to the overcurrent devices. Correct! Tenants need access to these devices for safety and convenience. NEC 240.24(B) requires that tenants in commercial buildings have access to the overcurrent devices for their branch circuits to ensure safety and convenience. 44 / 50 The SPD shall be marked with a short-circuit current rating and shall not be installed at a point on the system where the available fault current in excess of that rating. This marking requirement shall not apply to _____________________. a. receptacles b. AFCI circuits c. lighting d. GFCI circuits The National Electrical Code (NEC) Section 285.7 addresses Surge-Protective Devices (SPDs). This section requires SPDs to be marked with a short-circuit current rating. This rating specifies the maximum fault current the SPD can safely handle without failing. Installing an SPD with a rating lower than the available fault current at the installation point could lead to the SPD malfunctioning or even exploding during a surge event. However, the marking requirement for short-circuit current rating does not apply to receptacles. This is because receptacles are not intended to interrupt fault currents. Their primary function is to provide a safe connection point for appliances and other electrical loads. The overcurrent protection for branch circuits feeding receptacles comes from circuit breakers or fuses located upstream in the electrical panel. 45 / 50 How much VA per duplex receptacle? a. 240 b. 180 c. 120 In accordance with the National Electrical Code (NEC), a duplex receptacle (a single outlet with two slots) is assigned a value of 180 VA (volt-amperes) for load calculation purposes. This means that when planning the electrical load on a branch circuit, you should consider each duplex receptacle as contributing 180 VA. Overcurrent devices must be placed in safe and accessible locations. 46 / 50 Additional major concerns relating to the location of overcurrent devices include that they are not permitted to: a. be installed in bathrooms b. be installed in clothes closets. c. be installed over the steps of a stairway d. be exposed to physical damage. e. be installed in the vicinity of easily ignitable material. Incorrect. This is a significant safety concern outlined by the NEC. Correct! These are key safety requirements for overcurrent device locations. NEC provides strict guidelines on the placement of overcurrent devices to prevent physical damage, avoid fire hazards, and ensure accessibility. Consider the limitations outlined in NEC 250.64(C) regarding splicing of conductors. 47 / 50 Which type of conductor is generally not permitted to be spliced according to NEC 250.64(C)? a. Neutral conductor b. Grounding electrode conductor c. Equipment grounding conductor d. Grounding electrode conductor This answer contradicts the requirements specified in NEC 250.64(C) Correct! Grounding electrode conductors are generally not permitted to be spliced, as outlined in NEC 250.64(C). Generally, grounding electrode conductors are not permitted to be spliced, as stated in NEC 250.64(C). Consider the requirement specified in NEC 250.68(B) regarding bonding around insulating joints or sections of a metal piping system. 48 / 50 What is required for bonding around all insulating joints or sections of a metal piping system according to NEC 250.68(B)? a. Bonding tape b. Bonding c. Grounding d. Insulation This choice doesn’t accurately reflect the requirement specified in NEC 250.68(B) for bonding around insulating joints or sections of a metal piping system. Correct! Bonding is required around all insulating joints or sections of a metal piping system, as per NEC 250.68(B). Bonding is required around all insulating joints or sections of a metal piping system, as per NEC 250.68(B). 49 / 50 Branch circuit, individual: a. Supplies receptacles or outlets for lighting and appliances b. Supplies outlets to appliances c. Supplies only one utilization equipment d. Ungrounded conductors that have voltage and a grounded conductor that has equal voltage; connected to the neutral or grounded conductor of the system An individual branch circuit is specifically designed to supply power to one utilization equipment. This means it has a dedicated circuit breaker or fuse protecting a single appliance or device, like: Electric Range: Ovens and ranges typically require a high current capacity, and an individual circuit ensures they have a dedicated source of power and adequate overcurrent protection. Clothes Dryer: Similar to ranges, dryers have high power demands and benefit from an individual circuit to prevent overloading other circuits. Air Conditioner: Air conditioners also have high current requirements, and an individual circuit ensures efficient operation and proper overload protection. Disposal: Garbage disposals can draw significant current, and an individual circuit prevents them from tripping breakers or affecting other appliances on the same circuit. 50 / 50 8 AWG, Copper conductor, 60 feet away from panel, 32 ampere single phase load What is the voltage drop? {blank_1} a. 3%%%3.1%%%3.2%%%3.3%%%3.4%%%3.5 Several factors influence voltage drop in a circuit: Conductor size: Larger conductors (lower AWG numbers) have lower resistance, resulting in less voltage drop. Conductor length: Longer conductors have higher resistance, leading to a greater voltage drop. Conductor material: Copper offers better conductivity than aluminum, resulting in less voltage drop for the same size conductor. Load current: Higher currents cause a larger voltage drop due to increased resistance losses. Calculating Voltage Drop: Look up conductor resistance: Based on the information provided: Conductor size: 8 AWG Material: Copper (assumed) You can find the resistance per unit length (e.g., resistance per foot) in electrical reference tables or manufacturer data for copper conductors. Calculate total conductor length: Since the current travels to and from the load, the total length of the conductor is the distance from the panel to the load multiplied by two (round trip). Distance: 60 feet Total length = 60 feet * 2 = 120 feet Apply Ohm's Law: Once you have the resistance per foot and total length, you can calculate the voltage drop using Ohm's Law: Voltage drop = Current x Resistance Here's why the answer is between 3 and 3.5 volts (approximate): Without the exact resistance value per foot for 8 AWG copper wire, we can't give a definitive answer. However, considering typical resistance values for 8 AWG copper conductors and applying Ohm's Law, the voltage drop will likely fall between 3 and 3.5 volts for the given scenario. Important Note: While a voltage drop between 3 and 3.5 volts might be acceptable in some cases, the National Electrical Code (NEC) recommends keeping voltage drop below a certain percentage (usually 3% or 5%) to ensure proper equipment operation and avoid efficiency losses. It's always recommended to consult the NEC and electrical engineering practices for specific voltage drop limitations in your application. Vd = 2*K*I*D / C*A Your score is LinkedIn Facebook Twitter 0% Restart quiz Exit Rate & Review Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services. Send feedback Leave a Reply Cancel replyYour email address will not be published. Required fields are marked * Comment* Name* Email* Website Save my name, email, and website in this browser for the next time I comment. Post Comment