Report a question

You cannot submit an empty report. Please add some details.
0%

Article 200-285 Part10

This comprehensive quiz contains 50 questions carefully selected from the National Electrical Code (NEC) Articles spanning 200 through 285. These articles cover a broad spectrum of vital topics related to electrical installations within this section of the code.

The questions in this quiz are chosen randomly to provide a thorough assessment of your knowledge across these essential NEC articles. While we strive for a diverse set of questions, some fundamental principles may be revisited in different contexts due to their relevance to multiple sections within this range. This approach ensures a robust evaluation of your understanding.

We encourage you to actively participate and provide feedback. If you identify any issues or have suggestions for improving the quiz questions, please report them. Your contributions are invaluable in helping us maintain the accuracy and effectiveness of these learning resources.

1 / 37

Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates.

2 / 37

Where do you have to use a raised cover?

3 / 37

The code makes it very clear that the white conductor can be used as a return conductor from the switch to the switched outlet.

4 / 37

Equipment grounding conductors and isolated equipment grounding conductors are the same thing.

5 / 37

If a lighting load is considered to be continuous, as is the case in commercial buildings, a load factor of ____ percent must be applied.

6 / 37

Isolated ground receptacles installed in nonmetallic boxes shall be covered with either a metal or nonmetallic faceplate.

7 / 37

Minimum size equipment grounding conductor for a 60 ampere branch circuit is ______ AWG.

8 / 37

A 3000 square foot store has 30 ft of show window. There are a total of 80 duplex receptacles. The
serviceis 120/240 V, single-phase 3-wire service. The actual connected lighting load is 8,500 VA.
Calculate the minimum size overcurrent protection for the service.

9 / 37

What does the letter T stand for in THHN?

10 / 37

Indicate the general lighting unit load that would be included in the branch-circuit calculations as set forth in NEC Table 220.12 for a:

Schoolroom: _____ VA/ft2“>2.

11 / 37

To determine a reasonable minimum size for a neutral conductor, two types of loads must be considered—____.

12 / 37

There is more Volt-Amperes for duplex receptacles for HVAC equipment.

13 / 37

What is the minimum size equipment grounding conductor for grounding raceway and equipment for a 60 ampere circuit breaker.

14 / 37

An isolated ground conductor is connected with the rest of the grounding conductors in a box

15 / 37

Indicate the general lighting unit load that would be included in the branch-circuit calculations as set forth in NEC Table 220.12 for a:

A hallway in a dwelling: _____ VA/ft2“>2.

16 / 37

Where in the code book can you find the volt-amperes per square foot?

17 / 37

The ground fault protection system shall operate to cause the service disconnect to open all
ungrounded conductors of the fault circuit. The maximum setting of the ground-fault protection shall
be____________________ amperes, and the maximum time delay shall be one second for ground-fault currents equal to or greater than _________________________ amperes.

18 / 37

The load to be included for an outlet for a specific appliance or load is ________

19 / 37

Noncontinuous loads are calculated for 125% of the load.

20 / 37

Equipment grounding conductor connections to isolated ground receptacles are covered in _____.

21 / 37

Indicate the general lighting unit load that would be included in the branch-circuit calculations as set forth in NEC Table 220.12 for a:

Restaurant: _____ VA/ft2“>2

22 / 37

If the ampacity of a feeder does not match a standard OCPD rating, then ____ be used.

23 / 37

Permission is given in NEC 250.146(D) to install a separate green insulated equipment grounding conductor from the green hexagonal screw on the receptacle all the way back to the main service disconnect or the source of a separately derived system.

24 / 37

A separate insulated isolated equipment grounding conductors is sized according to NEC Table _______.

25 / 37

One receptacle outlet installed above each __ ft. section of show window: NEC 210.62

26 / 37

When doing calculations for branch circuits, calculations shall be permitted to be rounded to the nearest whole ampere, with decimal fractions smaller than _____ dropped.

27 / 37

Indicate the general lighting unit load that would be included in the branch-circuit calculations as set forth in NEC Table 220.12 for a:

Corridor in a school: _____ VA/ft2“>2.

28 / 37

An isolated ground conductors are permitted to pass though panelboards without being connected to the panelboards grounding terminal bar.

29 / 37

The use of an isolated equipment grounding conductor does not relieve the requirement for connecting the raceway system and outlet box to an equipment grounding conductor

30 / 37

The demand load for a dryer in a single-family dwelling unit, rate at 6,000 VA is ________________.

31 / 37

Volt-Amperes for sign outlets are _____.

32 / 37

The unit load for a Library when calculating out a lighting load is ______VA/ft2“>2

33 / 37

The receptacle is required to be at the same level as the HVAC equipment and within 25 feet of the equipment.

34 / 37

The load to be included for general-purpose convenience receptacles is ___________ VA.

35 / 37

Type S fuse-holders and adaptors shall be ________________ so that either the fuse-holder itself or the fuse-holder with a Type S adaptor inserted cannot be used for any fuse other than a Type S fuse.

36 / 37

What is the calculated service load for a 1500 square feet dwelling with the following:
two 20-A small appliance circuits
20-A laundry circuit
two 4-kW wall-mounted ovens
5.1-kW counter-mounted cooking unit
4.5-kW water heater, a 1.2 kW
dishwasher 5-kW clothes washer and dryer
six 7-A, 230-V room air-conditioning units
1.5-KW permanently installed bathroom space heater

37 / 37

In the first phase of the installation of a telephone system in a commercial building, the ____ will install an empty conduit system according to specifications for the commercial building and in the locations indicated on the working drawings.

Your score is

0%

Exit

Rate & Review

Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services.

Leave a Reply

Your email address will not be published. Required fields are marked *