eep April 7, 2025 NEC 300-399 NEC Quizzes Report a question What’s wrong with this question? You cannot submit an empty report. Please add some details. 0% Article 300-399 Part12 This comprehensive quiz contains 50 questions carefully selected from the National Electrical Code (NEC) Articles spanning 300 through 399. This section of the NEC addresses crucial aspects of wiring methods, materials, and general requirements for electrical installations within this portion of the code. The questions in this quiz are chosen randomly to provide a thorough assessment of your knowledge across these essential NEC articles. While we strive for a diverse set of questions, some fundamental principles may be revisited in different contexts due to their relevance to multiple sections within this range. This approach ensures a robust evaluation of your understanding. We encourage you to actively participate and provide feedback. If you identify any issues or have suggestions for improving the quiz questions, please report them. Your contributions are invaluable in helping us maintain the accuracy and effectiveness of these learning resources. Consider the integrity of the wireway when passing through a barrier. 1 / 50 Metal wireways can pass transversely through a wall ___________. a. if the wall is of fire-rated construction b. if the length passing through the wall is unbroken c. in hazardous (classified) locations d. if the wall is not of fire-rated construction This option does not correctly describe the NEC allowance for metal wireways passing through walls. Correct! An unbroken length is a key condition for wireways passing through walls. Per NEC 376.10(4), metal wireways are allowed to pass transversely through a wall if the length passing through the wall is unbroken. Consider the standard requirements for making secure electrical connections. 2 / 50 Joints between lengths of ENT, couplings, fittings, and boxes shall be made by __________. a. set screw fittings b. exothermic welding c. a qualified person d. an approved method This option does not meet the NEC’s requirement for making joints in ENT installations. Correct! Approved methods ensure that the joints are secure and compliant with NEC standards. According to NEC 362.48, joints between lengths of ENT, couplings, fittings, and boxes must be made by an approved method to ensure the integrity and safety of the installation. Think about the versatility of UF cable regarding installation environments. 3 / 50 Type UF cable is permitted to be used for inside wiring. a. False b. True This statement is incorrect; Type UF cable can indeed be used for interior wiring. Correct! Type UF cable is allowed for interior wiring according to the NEC. According to NEC 340.10(3), Type UF cable is permitted for interior wiring if installed according to NEC requirements. 4 / 50 Give the raceway size required for the following conductor combinations: Three, 250 kcmil conductors with XHHW insulation. a. 1 1/2 inch b. 1 inch c. 2 inch d. 2 1/2 inch The National Electrical Code (NEC) specifies requirements for determining the appropriate raceway size for electrical conductors. Article 310.15(B)(16) covers fill calculations for conductors in enclosures or raceways. For this scenario, we're considering three XHHW conductors, each sized at 250 kcmil. We need to find a raceway that complies with the fill limitations set by the NEC. The NEC tables (Chapter 9, Table 310.15(B)(16)) provide fill percentages for various types of conduit and conductor insulations. For three current-carrying conductors with XHHW insulation (without derating factors applied), the maximum fill percentage is 40%. Think about environments that could potentially damage or deteriorate electrical assemblies. 5 / 50 A multioutlet assembly shall not be installed __________. a. in hoist ways b. where subject to corrosive vapors c. all of these d. where subject to severe physical damage This option alone does not cover all the prohibitions specified by the NEC for multioutlet assemblies. Correct! All these conditions are prohibited for the installation of multioutlet assemblies according to the NEC. NEC 380.12(2), (4), and (5) prohibits the installation of multioutlet assemblies in hoistways, areas subject to severe physical damage, and where exposed to corrosive vapors to prevent hazards and ensure safety. Consider the design and capacity specifications of wireways. 6 / 50 Conductors larger than that for which the metal wireway is designed can be installed in any wireway. a. False b. True This statement is incorrect as it would violate NEC design specifications for wireways. Correct! The NEC prohibits using conductors larger than the wireway design. NEC 376.21 prohibits installing conductors larger than the wireway is designed for, ensuring the integrity and safety of the wiring system. Think about the most common types of raceways used in electrical installations. 7 / 50 ____________ is a thin wall raceway of circular cross-section designed for the routing and physical protection of electrical conductors and cables when joined together with listed fittings. a. NUCC b. EMT c. RTRC d. LFNC This option does not describe EMT, which is the NEC-specified raceway for this application. Correct! EMT is designed as a thin wall raceway for electrical conductors and cables According to NEC 358.2, Electrical Metallic Tubing (EMT) is a thin wall raceway of circular cross-section designed for the routing and physical protection of electrical conductors and cables when joined together with listed fittings. 8 / 50 What is the ampacity of 400 kcmil copper conductors with 90°C insulation? a. 380 b. 360 c. 400 The ampacity of a 400 kcmil copper conductor with 90°C insulation is 380 Amps. Ampacity refers to the maximum amount of electric current a conductor or device can carry before sustaining immediate or progressive deterioration. Please note that the actual ampacity may vary depending on the installation and environmental conditions. Always refer to the National Electrical Code (NEC) and local codes for precise information. 9 / 50 Give the raceway size required for the following conductor combinations: Five, 10 AWG, Type THW in Schedule 80 PVC a. 1 inch b. 1/2 inch c. 1 1/4 inch d. 3/4 inch The National Electrical Code (NEC) Article 310.15(B)(1)(a) sets limitations on the maximum number of conductors permitted in a raceway (conduit) based on their cross-sectional area and derating factors. To determine the appropriate raceway size for the given scenario, we'll need to: Calculate the total conductor area: Five 10 AWG THW conductors have an individual area of 5.26 mm² (refer to an AWG conductor table). Total area = 5 conductors * 5.26 mm² = 26.3 mm² Consider derating factors (if applicable): Ambient temperature exceeding 30°C More than three current-carrying conductors in the same raceway Consult NEC Table C.10 for Schedule 80 PVC Conduit Fill: Locate the column for 10 AWG THW conductors (or THWN, which has the same dimensions). Find a row with a value equal to or greater than the calculated total area (26.3 mm²) while accounting for derating if needed. 10 / 50 What the ampacity of 400 kcmil copper conductors, With 60°C insulation? a. 290 b. 280 c. 270 A 400 kcmil copper conductor with 60°C insulation has an ampacity of 280 Amps. This means it can carry a maximum electric current of 280 Amps before it starts to degrade immediately or over time. However, the actual ampacity can change based on the conditions of installation and the environment. For accurate information, it’s always best to consult the National Electrical Code (NEC) and any local codes. 11 / 50 Give the raceway size required for the following conductor combinations: One, 4 AWG conductor with XHHW insulation. a. 1 1/2 inch b. 1/2 inch c. 3/4 inch d. 1 inch The NEC, in Article 310.15(B)(1)(a), specifies the maximum permitted fill for raceways with conductors. For most types of raceways (EMT, IMC, RMC), the fill cannot exceed 40% if there are more than three conductors in the raceway. In this case, we only have one conductor. However, we still need to consider the cross-sectional area of the 4 AWG XHHW conductor and compare it to the available area within the different raceway sizes. You can find tables in the NEC or electrical references that provide the cross-sectional area of various conductor sizes. Similarly, tables exist that show the internal area of different conduit sizes. By comparing these values and ensuring the conductor area stays within 40% of the available raceway area, you can determine the minimum required raceway size. 12 / 50 You do not have to select the proper insulation for the type of installation. a. False b. True Selecting the proper insulation for the type of installation is absolutely crucial for electrical work. Here's why: Safety: Different insulation materials have varying properties regarding temperature resistance, moisture resistance, and mechanical strength. Using the wrong insulation can lead to overheating, electrical shorts, and even fires. Performance: Insulation plays a vital role in ensuring the proper functioning of electrical systems. The wrong insulation type might not adequately prevent current leakage, leading to inefficiency and potential damage to equipment. Code compliance: The National Electrical Code (NEC) has specific requirements for insulation types based on application and location. Using non-compliant insulation can lead to code violations and potential project rejection by inspectors. Therefore, choosing the right insulation for your specific installation is essential for safety, performance, and code compliance. Consider the durability and rating of PVC conduit for exposed installations. 13 / 50 PVC conduit shall be permitted for exposed work where subject to physical damage if identified for such use. a. False b. True This statement is incorrect; PVC conduit can be used in such conditions if appropriately identified. Correct! PVC conduit is suitable for exposed work where subject to physical damage if identified for that purpose. According to NEC 352.10(F), PVC conduit is permitted for exposed work in areas subject to physical damage if it is identified for such use, ensuring it can withstand the conditions. 14 / 50 For most all the work we do, we use the ampacities from Table ______ in the NEC. a. 310.15(B)(1) b. 310.15(B)(16) c. 310.16 310.16: Ampacity Tables for Listed Cable (This table directly gives ampacities for various cable types and sizes at 30°C ambient temperature) 310.15(B)(1): Ambient Temperature Correction Factors (This table is similar to 310.15(B)(16) but based on a different reference temperature) 310.15(C)(1): Adjustment Factors for More Than Three Current-Carrying Conductors (This table provides adjustment factors to reduce ampacities when more than three current-carrying conductors are bundled together) 310.15(B)(16): Ambient Temperature Correction Factors Based on 30°C (86°F) Think about the flexibility and installation limits of PVC conduits. 15 / 50 Bends in PVC conduits shall be limited to _______ degrees between pull points. a. not be limited in degrees b. not be made c. limited to 360 degrees d. be limited to 180 degrees This option does not comply with the NEC’s specified limit on the degrees of bends in PVC conduits. Correct! The NEC limits bends in PVC conduits to 360 degrees between pull points. According to NEC 352.26, bends in PVC conduits between pull points are limited to 360 degrees to ensure ease of pulling conductors and maintaining conduit integrity. 16 / 50 If nine current-carrying conductors are installed in one raceway for a length greater than 24 in., What is the reduced percentage of the ampacity? a. 80% b. 70% c. 60% When more than three current-carrying conductors are installed together in a single raceway, the ampacity of each conductor must be reduced according to the applicable adjustment factor. For nine current-carrying conductors in one raceway, the ampacity from the table must be adjusted based on the values found in NEC Table 310.15(B)(3)(a) / Table 310.15(C)(1). The adjustment factor for nine conductors is 70%. This means the ampacity of each conductor should be reduced to 70% of its original value. Please consult the NEC tables 17 / 50 Type MV cable (Medium Voltage) shall be permitted for use on power systems rated up to and including 35,000 volts, nominal, in which of these circumstances: a. all of the above b. direct buried c. In wet or dry locations d. in messenger-supported wire The National Electrical Code (NEC) covers the use of MV cables in Article 311. According to this article, MV cables with a voltage rating up to 35,000 volts can be installed in: Wet or dry locations: MV cables are insulated to withstand exposure to moisture. Direct buried applications: NEC permits direct burial of MV cables if they are listed and rated for underground use. Messenger-supported installations: MV cables can be strung overhead with the support of a messenger wire, which is a separate cable providing mechanical strength. Therefore, based on the NEC, all of the above circumstances are permitted for Type MV cable installation. 18 / 50 Which raceway(s) may be used in wet locations? a. electrical nonmetallic tubing b. intermediate metal conduit c. rigid nonmetallic conduit d. flexible metallic tubing e. rigid metal conduit f. electrical metallic tubing The National Electrical Code (NEC) dictates specific types of raceways allowed in wet locations to ensure electrical safety and prevent circuit malfunctions. Here's a breakdown based on NEC Articles: Electrical Metallic Tubing (EMT): NEC Article 358 permits EMT use in wet locations when listed for such applications and with appropriate fittings. Electrical Nonmetallic Tubing (ENT): NEC Article 362 allows ENT in wet places when listed and installed according to specific requirements. Flexible Metallic Tubing (FMC): NEC Article 360 restricts FMC use in wet locations due to concerns about moisture ingress and potential corrosion. Rigid Metal Conduit (RMC): NEC Article 347 approves RMC for wet locations as it provides excellent protection against moisture and physical damage. Intermediate Metal Conduit (IMC): Similar to RMC, NEC Article 346 allows IMC in wet areas due to its robust metallic construction. Rigid Nonmetallic Conduit (RNC): NEC Article 352 permits RNC in wet locations when listed for wet use and installed per code guidelines. 19 / 50 How do you prevent oxidization of aluminum conductors? a. Brush an inhibitor on the conductor b. Install in PVC only c. Install in an Weatherproof panel only Aluminum readily reacts with oxygen to form a thin layer of aluminum oxide (Al2O3) on its surface. This oxide layer acts as a barrier, preventing further significant oxidation of the bulk aluminum beneath. However, at connection points where the aluminum is exposed and potentially disturbed, additional protection can be beneficial. Here's a breakdown of the other options and why they are not the best choices for preventing aluminum conductor oxidation: Install in PVC only: While PVC conduit can offer some physical protection from the environment, it doesn't directly address aluminum oxidation. Install in an Weatherproof panel only: Weatherproof panels offer protection from rain and dust, but they don't necessarily prevent oxidation. The key is to minimize exposure of bare aluminum at connection points. Brushing an inhibitor on the conductor, particularly at connection points, provides a layer that can: Slow down the rate of oxidation: The inhibitor can act as a barrier, making it more difficult for oxygen to reach the aluminum surface. Improve connection quality: Some inhibitors can help create a cleaner and more reliable connection by reducing surface contaminants. Important Note: It's crucial to choose the appropriate inhibitor for the specific application and follow the manufacturer's instructions for proper application. Not all inhibitors are suitable for electrical applications. 20 / 50 Why would copper not be selected as the conductor? a. Price of aluminum is cheaper b. Copper has issues when installed c. Aluminum is a better conductor There are a few reasons why copper might not be selected as a conductor, even though it's the most popular choice: Price: As you mentioned, aluminum is significantly cheaper than copper. This can be a major factor in applications where cost is a primary concern, especially for large-scale projects. Weight: Aluminum is lighter than copper for the same conductivity. This can be crucial in situations where weight is a limiting factor, such as overhead power lines or aircraft wiring. Specific Applications: Some applications have specific requirements that might favor other materials. For example, aluminum might be preferred for welding due to its ability to form a stable oxide layer. Corrosion Resistance: While copper has good corrosion resistance overall, there are environments where it might not be suitable. In highly corrosive environments, materials like tinned copper or even aluminum might be chosen for better performance. Overall, while copper offers excellent conductivity and other advantages, the decision of conductor material often involves a trade-off between factors like cost, weight, specific application needs, and corrosion resistance. Consider the mechanical integrity of connections involving IMC. 21 / 50 Running threads shall not be used on IMC for connection at couplings. a. True b. False This statement is incorrect as running threads are not permitted for coupling connections. Correct! Running threads are not allowed for IMC couplings. Per NEC 342.42(B), running threads are prohibited for connections at couplings to ensure the integrity and security of the installation. Consider the maximum interval for securing and supporting MC cable as it passes through framing members. 22 / 50 Type MC cable installed horizontally through wood or metal framing members is considered secured and supported where such support does not exceed ____ feet intervals. a. 8 b. 6 c. 3 d. 4 This option does not match the NEC’s specified interval for securing and supporting MC cable. Correct! The NEC specifies a maximum of 6 feet intervals for securing and supporting MC cable. NEC 330.30(C) states that Type MC cable installed horizontally through wood or metal framing members is considered secured and supported if the intervals do not exceed 6 feet, ensuring proper support and compliance. Consider the bend radius specifications for RMC to ensure proper installation without damaging the conduit. 23 / 50 The minimum radius of a field bend on a trade size 1 1/4 RMC is ______ inches. a. 10 b. 7 c. 14 d. 8 This option does not meet the NEC-specified minimum radius for bending 1 1/4 RMC. Correct! The NEC specifies an 8-inch minimum radius for field bends on trade size 1 1/4 RMC. According to NEC 344.24 and Chapter 9, Table 2, the minimum radius of a field bend on a trade size 1 1/4 RMC is 8 inches, ensuring proper bending without compromising conduit integrity. Consider the NEC restrictions on using certain types of cables for specific purposes. 24 / 50 Type UF cable can be used for service conductors. a. False b. True This statement is incorrect; Type UF cable cannot be used for service conductors according to the NEC. Correct! The NEC prohibits the use of Type UF cable for service conductors. According to NEC 340.12(1), Type UF cable is not permitted to be used for service conductors to ensure compliance with NEC requirements and safety. Consider what is needed to prevent corrosion in wet environments. 25 / 50 Materials such as straps, bolts, screws, and so forth associated with the installation of IMC in wet locations shall be ___________. a. b or c b. protected against corrosion-resistant materials c. corrosion resistant d. weatherproof This option does not fully meet the NEC requirements for corrosion resistance in wet locations. Correct! Both corrosion resistance and protection against corrosion meet the NEC requirements. NEC 342.10(D) states that materials associated with the installation of IMC in wet locations must be either corrosion-resistant or protected against corrosion by corrosion-resistant materials. Consider the requirements to prevent corrosion of materials in wet environments. 26 / 50 Materials such as straps, bolts, and so forth associated with the installation of RMC in wet locations shall be ______. a. weatherproof b. b or c c. corrosion resistant d. protected against corrosion by corrosion-resistant materials This option does not fully meet the NEC requirements for corrosion protection in wet locations. Correct! Both corrosion resistance and protection against corrosion meet NEC requirements for wet locations. NEC 344.10(D) states that materials associated with the installation of RMC in wet locations must be either corrosion-resistant or protected against corrosion by corrosion-resistant materials to ensure durability and compliance. 27 / 50 What is the corrected ampacity of a 250 kcmil copper conductor that has Type THWN insulation that is installed in an ambient temperature of 96°F. a. 224 amperes b. 236 amperes c. 215 amperes Corrected Ampacity can be calculated using the formula: Corrected Ampacity = Base Ampacity x Correction Factor The corrected ampacity of a 250 kcmil copper conductor that has Type THWN insulation and is installed in an ambient temperature of 96°F is 224 amperes. This is based on the information you provided. Remember, always refer to the NEC tables 28 / 50 What is the correction factor for a conductor with 75°C insulation that is installed in a 104°F ambient temperature? a. 0.90 b. 0.88 c. 0.7 For a conductor with 75°C insulation installed in an environment with an ambient temperature of 104°F, the NEC specifies a correction factor of 0.88. This means that the ampacity of the conductor (the maximum amount of electric current it can carry without immediate or progressive deterioration) needs to be multiplied by this correction factor to prevent overheating and ensure safe operation. 29 / 50 Give the raceway size required for the following conductor combinations: Three, 1/0 AWG and one, 1 AWG, Type THW in EMT a. 1 inch b. 1 1/2 inch c. 2 inch d. 2 1/2 inch NEC Table C.1 in Chapter 9 specifies the maximum number of conductors permitted in electrical metallic tubing (EMT) based on their size and type. However, for calculations involving more than three current-carrying conductors, Article 314.16 of the NEC requires applying a fill percentage. The fill percentage considers the cross-sectional area of the conductors and the internal area of the EMT conduit. It ensures adequate space is available within the raceway for heat dissipation and proper bending of the conductors. According to NEC 314.16(A), the maximum raceway fill for more than three current-carrying conductors is 40%. There's an additional provision for two conductors with a fill of 31%. 30 / 50 It should also be noted that the higher the insulation rating, the ______ the ampacity for a given conductor size. a. Lower b. Higher The answer is Higher. Here's the reasoning: Ampacity refers to the maximum current a conductor can safely carry without exceeding its temperature rating. Insulation rating indicates the maximum temperature the insulation material can withstand. Imagine two conductors of the same size, one with a 60°C insulation rating and another with a 90°C rating. The 60°C insulation will start to degrade if the conductor temperature goes above 60°C. The 90°C insulation can handle higher temperatures before experiencing damage. Since the 90°C insulation allows the conductor to operate at a higher temperature before reaching its limit, it can safely carry more current (higher ampacity) compared to the 60°C conductor. Therefore, a higher insulation rating allows for a higher ampacity for a given conductor size. 31 / 50 Give the raceway size required for the following conductor combinations: Three, 1/0 AWG, Type THHN in EMT a. 1/2 inch b. 3/4 inch c. 1 inch d. 1 1/4 inch To determine the appropriate raceway size for conductors in EMT, we need to consider the following factors: Conductor size and type: The National Electrical Code (NEC) provides tables (Chapter 9) that list the area of different conductor sizes and types (e.g., THHN). Raceway type and size: The NEC also specifies the trade sizes of various raceway types (e.g., EMT) and their corresponding cross-sectional areas. Maximum fill percentage: The NEC defines the maximum allowable percentage of a raceway's cross-sectional area that can be occupied by conductors (typically 40%). This ensures proper heat dissipation and bending space. Steps for Calculating Raceway Size: Identify the total area of the conductors by looking up their individual areas in the NEC tables based on their size and type (THHN in this case). Find the cross-sectional area of the EMT conduit from the NEC tables based on its trade size. Multiply the EMT area by the maximum fill percentage (usually 40%) to determine the maximum usable area for conductors within the conduit. Compare the total conductor area (step 1) with the maximum usable area (step 3). Applying the NEC to this scenario: We need to accommodate three 1/0 AWG THHN conductors in EMT. Look up the area of a 1/0 AWG THHN conductor in the NEC tables. (Area of a 1/0 AWG THHN conductor = specific value based on NEC table) Multiply the area of a single 1/0 AWG THHN conductor by 3 (number of conductors) to find the total conductor area. Find the cross-sectional area of the available EMT sizes (1/2", 3/4", 1", 1 1/4") in the NEC tables. Calculate the maximum usable area for conductors in each EMT size by multiplying the EMT area by 40% (assuming the standard fill percentage). Only the 1 1/4" EMT will have a maximum usable area large enough to accommodate the total area of the three 1/0 AWG THHN conductors while complying with NEC fill limitations. 32 / 50 What does the letter T stand for in THHN stand for? a. Thermoset b. Thermoplastic The letter T in THHN stands for Thermoplastic. Here's a breakdown of the complete THHN designation: T: Thermoplastic – This indicates the type of insulation used, which is a plastic material that softens or melts when heated. HH: High-Heat Resistant – This signifies the insulation's ability to withstand high temperatures. N: Nylon Jacket – This refers to the outer jacket material surrounding the insulation, which is nylon in this case. So, THHN wire features thermoplastic insulation for high-heat resistance and a nylon jacket for added protection. 33 / 50 Give the raceway size required for the following conductor combinations: Twelve, 6 AWG conductors with THHN insulation. a. 1 inch b. 1 1/4 inch c. 1/2 inch d. 3/4 inch The National Electrical Code (NEC) Article 310.15(B)(1)(a) specifies the requirements for conductor fill in raceways. This article states that the cross-sectional area of the conductors installed in a raceway must not exceed a certain percentage of the raceway's cross-sectional area. This percentage is known as the fill ratio. For conductors with THHN insulation, Table C of Chapter 9 in the NEC provides the allowable fill ratios for different conduit types and sizes. Based on this table, you can determine the maximum number of conductors that can be placed in a specific conduit size. In this case, we have twelve 6 AWG THHN conductors. Consulting Table C of the NEC would reveal that a 1/2 inch or 3/4 inch conduit wouldn't suffice for this many conductors. A 1 inch conduit might be suitable depending on the specific table values, but a 1 1/4 inch conduit is most likely required to accommodate all twelve 6 AWG THHN conductors while complying with the fill ratio requirements. 34 / 50 Are the interior of raceways considered wet locations, when installed underground? a. No b. Yes The National Electrical Code (NEC) is a critical document that sets safety standards for electrical installations in the United States. Article 300.5 of the NEC specifically addresses raceways in wet locations: 300.5 Underground Installations. The interior of enclosures or raceways installed underground shall be considered to be a wet location. This means that even if the raceway itself is watertight, the interior is assumed to have the potential for moisture ingress. This is due to factors like: Ground water: Underground environments naturally have some level of moisture present. Condensation: Temperature fluctuations can cause condensation inside the raceway, especially if there are significant temperature differences between the underground environment and the above-ground location where the conductors enter or exit the raceway. Electrical Safety Implications: Since the interior of underground raceways is considered a wet location, the NEC requires using conductors and cables with appropriate insulation ratings for wet locations. These cables have a thicker or more robust insulation material designed to withstand moisture exposure without degradation. This helps to prevent electrical shorts, ground faults, and potential fires. Important Note: Even with properly rated conductors, it's still good practice to use best practices when installing underground raceways, such as sealing terminations and using watertight fittings where possible to minimize the risk of moisture ingress. 35 / 50 Ampacities of NEC Table 310.16 is based on not more than {blank_1} current-carrying conductors in a raceway, cable, or earth based on an ambient temperature of {blank_2} degrees F. (Fill in the blanks with the appropriate words.) a. 86 b. 3 The ampacities of NEC Table 310.16 are based on not more than **three** current-carrying conductors in a raceway, cable, or earth based on an ambient temperature of **86** degrees F. 36 / 50 What is the most popular choice of conductor material? a. Copper Clad Aluminum b. Aluminum c. Copper The most popular choice of conductor material is: Copper Here's why copper is widely used: High Conductivity: Copper offers excellent electrical conductivity, meaning it allows electricity to flow efficiently with minimal resistance. This translates to lower energy losses in electrical systems. Ductility and Malleability: Copper is highly ductile and malleable, making it easy to draw into thin wires and bend into various shapes during installation. Corrosion Resistance: Copper exhibits good resistance to corrosion, ensuring long-lasting performance in many environments. Cost-Effectiveness: While not the cheapest option, copper offers a good balance between cost and performance for most electrical applications. While aluminum has advantages like lower weight and cost in some situations, copper's superior conductivity and overall properties make it the most popular choice for conductors. Consider the various methods and conditions for securing IMC. 37 / 50 IMC shall be secured __________. a. any of these b. except when the IMC is within 3 feet of the service head for an above-the-roof termination of a mast. c. within 5 feet of a box or termination fitting when structural members do not readily permit the raceway to be secured within 3 feet of the termination. d. by fastening within 3 feet of each outlet box, junction box, device box, cabinet, conduit body, or other conduit termination. This option does not account for all the NEC-specified methods for securing IMC. Correct! The NEC provides multiple acceptable methods for securing IMC based on the installation conditions. NEC 342.30(A)(1), (2), and (3) provide different securing methods for IMC, including fastening within 3 feet of terminations, within 5 feet when structural members don’t allow for 3-foot fastening, and exceptions for above-roof terminations, ensuring flexibility in installation. 38 / 50 A grounding or bonding conductors shall be counted when applying the provisions 310.15(C)(1) a. False b. True The statement is False. According to the National Electrical Code (NEC), grounding or bonding conductors are not counted when applying the provisions of 310.15©(1). This section of the NEC deals with adjustment factors for more than three current-carrying conductors. Grounding or bonding conductors typically do not carry current during normal operation, so they are not included in this count Consider the versatility of metal wireways in various installation environments. 39 / 50 Metal wireways shall be permitted for __________. a. wet locations if listed for the purpose b. totally concealed work c. exposed work d. a and c This option does not encompass all the permitted uses of metal wireways as specified by the NEC. Correct! Metal wireways are versatile and can be used in exposed work and wet locations if listed. NEC 376.10(1) and (3) allows metal wireways to be used for exposed work and in wet locations if they are listed for that purpose, providing flexibility in different installation scenarios. 40 / 50 What table is for ambient temperature correction factors based on 40 degree Celsius? {blank_1} a. 310.15(B)(2) The table for ambient temperature correction factors based on 40 degrees Celsius is found in the National Electrical Code (NEC) under Table 310.15(B)(2). This table provides correction factors that must be applied to the ampacity of conductors when they are to be used in environments with an ambient temperature other than 30°C (86°F). 41 / 50 Give the raceway size required for the following conductor combinations: One, 3/0 AWG conductor with XHHW insulation. a. 3/4 inch b. 1 1/4 inch c. 1/2 inch d. 1 inch The National Electrical Code (NEC) provides tables to determine the minimum allowable raceway fill for various types of electrical conductors. For this question, we'll refer to Table C in Chapter 3 of the NEC which addresses raceway fill for conductors with various insulations. Here's a breakdown of the process: Identify Conductor Properties: We know we have one conductor with a size of 3/0 AWG and XHHW insulation. Reference NEC Table C: Look up XHHW in the "Conductor Type" column and 3/0 AWG in the "Size AWG/kcmil" column. Since there's only one conductor, we don't need to consider the number of conductors fill percentage. Apply Fill Requirements: According to Table C, for XHHW insulation and a conductor size of 3/0 AWG, the minimum allowable raceway fill is 40%. Selecting Raceway Size: Now that we know the minimum allowable fill is 40%, we can choose a raceway size that provides enough cross-sectional area to accommodate the conductor and meet the fill requirement. Manufacturers provide the cross-sectional area of their raceway products. You can find this information on the product specifications or data sheets. 1/2 inch conduit typically has a smaller cross-sectional area than what's required to meet the 40% fill for a 3/0 XHHW conductor. 3/4 inch conduit usually provides enough area to comply with the 40% fill requirement for a single 3/0 XHHW conductor. 1 inch and 1 1/4 inch conduit will likely be sufficient for a single 3/0 XHHW conductor based on their larger area but verifying the specific product's area is recommended for precise calculations. 42 / 50 What is the ampacity of 400 kcmil copper conductors with 75°C insulation? a. 300 b. 370 c. 335 The ampacity of a 400 kcmil copper conductor with 75°C insulation is 335 Amps. Ampacity refers to the maximum amount of electric current a conductor or device can carry before sustaining immediate or progressive deterioration. Please note that the actual ampacity may vary depending on the installation and environmental conditions. Always refer to the National Electrical Code (NEC) and local codes for precise information. Think about the relationship between conductor temperature ratings and the conduit they are installed in. 43 / 50 Conductors rated at a temperature _____ than the listed temperature rating of PVC conduit shall be permitted to be installed in PVC conduit provided the conductors are not operated at a temperature above the raceway’s listed temperature rating. a. lower b. the same as c. higher d. a or b This option does not align with the NEC allowance for conductors in PVC conduits. Correct! Conductors rated at a higher temperature are permitted in PVC conduit if they are not operated above the conduit’s listed temperature rating. NEC 352.10 allows for conductors rated at a higher temperature than the listed temperature rating of PVC conduit to be installed, provided the conductors are not operated above the raceway’s listed temperature rating to ensure safe operation. 44 / 50 Indicate whether the following conductor insulations that are installed in conduits or cables within ⅞ in. of a rooftop having sunlight exposure are required to have the correction factor applied: a. USE-2 b. THW c. XHHW-2 d. XHHW e. THWN-2 f. THWN 45 / 50 If nine current-carrying conductors are installed in a raceway that is installed in an ambient temperature of 104°F the following adjustment and correction factors must be applied: __________________ percent for the number of current-carrying conductors a. 70% b. 80% c. 60% The correct adjustment factor for the number of current-carrying conductors in this case is 70%. This factor is used to adjust the ampacity of the conductors due to the additional heat generated by the presence of multiple conductors in a raceway. The ambient temperature of 104°F may also require an additional correction factor to be applied. Think about areas in buildings where wiring might be hidden from view. 46 / 50 LFMC shall not be required to be secured or supported where fished between access points through ___________ spaces in finished buildings or structures and supporting is impractical. a. concealed b. hazardous c. completed d. exposed This choice does not match the NEC requirements for spaces where securing and supporting LFMC is impractical. Correct! LFMC does not need to be secured or supported when fished through concealed spaces in finished buildings. According to NEC 330.30(A) Exception 1, LFMC does not need to be secured or supported if it is fished between access points through concealed spaces in finished buildings or structures where supporting is impractical. 47 / 50 If nine current-carrying conductors are installed in a raceway that is installed in an ambient temperature of 104°F the following adjustment and correction factors must be applied: __________________ percent for the elevated ambient temperature a. 88% b. 90% c. 76% The correct adjustment factor for the elevated ambient temperature in this case is 88%. This factor is used to adjust the ampacity of the conductors due to the additional heat caused by the higher ambient temperature. The specific adjustment factor can vary depending on the type of insulation used on the conductors and the specific temperature rating of that insulation. 48 / 50 Which raceway(s) may be used for service entrances? a. electrical metallic tubing b. intermediate metal conduit c. rigid nonmetallic conduit d. rigid metal conduit e. electrical metallic tubing f. electrical metallic tubing The National Electrical Code (NEC) Article 230.7 restricts the types of raceways that can be used for service entrances. This regulation aims to ensure proper grounding and safety during fault conditions. According to NEC 230.7, only the following raceways are permitted for service entrances: Electrical Metallic Tubing (EMT): EMT is a steel raceway that provides a continuous grounding path. Rigid Metal Conduit (RMC): RMC is a threaded rigid steel conduit that offers excellent strength and grounding capabilities. Intermediate Metal Conduit (IMC): IMC is a thinner-walled steel conduit compared to RMC, but it still meets grounding requirements for service entrance use. Exceptionally, NEC allows one specific nonmetallic conduit for service entrance: Schedule 80 PVC Conduit: This particular PVC conduit type offers superior strength and durability compared to standard PVC. Additionally, it requires the use of a listed grounding kit to ensure proper grounding. 49 / 50 Which raceway(s) may be used where cinder fill is present? a. Electrical metallic tubing b. rigid nonmetallic conduit c. electrical nonmetallic tubing d. flexible metallic tubing e. intermediate metal conduit f. rigid metal conduit The National Electrical Code (NEC) covers the installation of electrical wiring and equipment. Cinder fill is a material historically used as land fill, and can be corrosive when wet. See NEC Section 300.5: insert citation for NEC section 300.5. Article 346 of the NEC covers rigid metal conduit (RMC). RMC is a durable option that resists corrosion. Article 347 of the NEC covers intermediate metal conduit (IMC). IMC is similar to RMC, but with a thinner wall. However, it is still appropriate for corrosive environments. Article 352 of the NEC covers rigid nonmetallic conduit (RNC). There are various types of RNC with different material properties, but some types are designed to resist corrosion. Consider common structural elements used to support conduit runs. 50 / 50 Horizontal runs of RMC supported by openings through _______ at intervals not exceeding 10 feet and securely fastened within 3 feet of termination points shall be permitted. a. walls b. trusses c. framing members d. rafters This option does not include the NEC-specified support intervals for horizontal runs of RMC. Correct! The NEC allows for horizontal runs of RMC supported by framing members at the specified intervals. NEC 344.30(B)(4) permits horizontal runs of RMC supported by openings through framing members at intervals not exceeding 10 feet and securely fastened within 3 feet of termination points to ensure proper support and installation. Your score is LinkedIn Facebook Twitter 0% Restart quiz Exit Rate & Review Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services. Send feedback Leave a Reply Cancel replyYour email address will not be published. Required fields are marked * Comment* Name* Email* Website Save my name, email, and website in this browser for the next time I comment. Post Comment