eep April 10, 2025 NEC 400-490 NEC Quizzes Report a question What’s wrong with this question? You cannot submit an empty report. Please add some details. 0% Article 400-490 Part05 This quiz consists of 50 carefully selected questions covering NEC Articles 400 through 490, which provide critical guidelines for flexible cords and cables (Article 400), switchgear and control equipment (Article 409), and installations operating above 1000 volts (Article 490). These sections of the National Electrical Code focus on safety, material specifications, and proper installation practices. The randomly generated questions ensure a thorough assessment of your understanding, reinforcing key principles related to permitted uses of flexible cords, ampacity ratings, industrial control panels, and high-voltage equipment requirements. Some topics may reappear in different contexts to strengthen comprehension and application. Your feedback is invaluable! If you notice any discrepancies or have suggestions for improvement, please report them. Your insights help maintain the accuracy and effectiveness of this learning tool. The NEC imposes a limit on medium-base incandescent lamps to prevent overheating and ensure safety. 1 / 50 An incandescent lamp for general use on lighting branch circuits shall not be equipped with a medium base if rated over _______________ watts. a. 150 b. 300 c. 200 d. 325 The selected wattage exceeds the NEC limit for medium-base incandescent lamps on lighting branch circuits. Correct! An incandescent lamp for general use on lighting branch circuits shall not be equipped with a medium base if rated over 300 watts, as specified in NEC Article 410.6. The NEC imposes a limit on medium-base incandescent lamps to prevent overheating and ensure safety. The “highest-rated” motor is determined by its full-load current rather than just its horsepower. 2 / 50 The “highest-rated” motor is: a. 3 hp 115 V 1-phase b. 5 hp 240 V DC c. 3 hp 208 V 1-phase d. 10 hp 208 V 3-phase The selected motor does not have the highest full-load current compared to the others. Correct! The “highest-rated” motor is the 3 hp 115 V 1-phase motor, as it has the highest full-load current rating (34 A). To determine the highest-rated motor, we calculate the full-load current (FLC) for each motor: 10 hp 208 V 3-phase: From NEC Table 430.250, FLC = 30.8 A. 3 hp 208 V 1-phase: Using the formula FLC=hp×746Voltage×Efficiency×Power Factor\text{FLC} = \frac{\text{hp} \times 746}{\text{Voltage} \times \text{Efficiency} \times \text{Power Factor}}FLC=Voltage×Efficiency×Power Factorhp×746, the FLC is approximately 18 A. 3 hp 115 V 1-phase: Using the same formula, FLC = 34 A (approximately). 5 hp 240 V DC: From NEC guidelines, FLC is approximately 20 A. The NEC sets a specific voltage threshold for lampholders used in infrared industrial heating equipment when operated in series. 3 / 50 Infrared industrial process heating equipment lampholders shall be permitted to be operated in series on circuits of _______________. a. Over 300 volts to ground b. Over 150 volts to ground c. Over 120 volts to ground d. Over 50 volts to ground The selected voltage does not meet the NEC requirements for lampholders in infrared industrial process heating equipment. Correct! Infrared industrial process heating equipment lampholders may be operated in series on circuits of over 150 volts to ground, as specified in NEC Article 425.55. According to NEC Article 425.55, lampholders for infrared industrial process heating equipment are permitted to be operated in series on circuits of over 150 volts to ground. This allowance ensures the equipment can function safely and efficiently in industrial settings with higher voltage requirements. For a 3-phase circuit, the voltage drop (VDVDVD) formula is: VD=3×I×R×L1000VD = \frac{\sqrt{3} \times I \times R \times L}{1000}VD=10003 4 / 50 A 3-phase, 208-volt, 10-HP motor has a voltage drop of 10 volts when started. The motor is fed by two #8 THHN conductors and one #10 THHN equipment grounding conductor (EGC). What is the distance from the motor to its source? a. 240 ft b. 118 ft c. 423.5 ft d. 765 ft The selected distance does not match the calculation for voltage drop and conductor resistance. Correct! The distance from the motor to its source is 240 feet, as calculated using the voltage drop formula. The distance from the motor to its source is approximately 240 feet, based on the given voltage drop, conductor size, and starting current. The NEC provides a specific percentage limit for ground-fault protection based on the motor-compressor’s rated-load current to ensure adequate protection. 5 / 50 The ground-fault protection for a hermetic motor-compressor shall have a rating NOT exceeding _______________ of the motor-compressor rated-load current. a. 125% b. 175% c. 150% d. 225% The selected percentage does not comply with NEC requirements for ground-fault protection for hermetic motor-compressors. Correct! The ground-fault protection for a hermetic motor-compressor must not exceed 175% of the rated-load current, as specified in NEC Article 440.22(A). According to NEC Article 440.22(A), the ground-fault protection for a hermetic motor-compressor must not exceed 175% of the rated-load current. This ensures the motor-compressor is protected without causing unnecessary tripping under normal operating conditions. Consider the nature of these loads, which typically operate for extended periods. 6 / 50 Fixed electric space heating equipment and motors shall be considered what type of load? a. Continuous b. Non-continuous c. Intermittent d. Inductive The selected option does not align with the NEC definition of a continuous load for fixed electric space heating equipment and motors. Correct! Fixed electric space heating equipment and motors are classified as continuous loads, as specified in NEC Article 424.3(B). According to NEC Article 424.3(B), fixed electric space heating equipment is considered a continuous load because it typically operates for periods of 3 hours or more. Motors, depending on their application, are often treated similarly in sizing and calculations. When a controller is part of another piece of equipment, the nameplate of that equipment can include the necessary information. 7 / 50 Where a controller is built in as an integral part of a(n) _______________, individual marking of the controller shall not be required if the necessary data are on the nameplate. a. Motor b. X-ray machine c. Elevator d. Appliance Correct! When a controller is built into a motor, individual marking of the controller is not required if the necessary data is included on the motor’s nameplate, as specified in NEC Article 430.8. The selected option does not align with NEC requirements. When a controller is integral to a motor, individual marking is not required if the data is on the motor’s nameplate. According to NEC Article 430.8, when a controller is built into a motor as an integral part, the individual marking of the controller is not required, provided that all necessary data is included on the motor’s nameplate. This reduces redundant marking and simplifies identification. To calculate the secondary current, divide the transformer’s kVA rating by the secondary voltage, and adjust for the phase configuration. 8 / 50 A 175 kVA, single-phase transformer with a secondary voltage of 120/240 has _______________ amperes available. a. 625 b. 329 c. 729 d. 421 The selected value does not match the calculated secondary current for the given transformer rating and voltage. Correct! The secondary current available from the transformer is 729 amperes, as calculated from the transformer’s kVA rating and secondary voltage. The secondary current available from a 175 kVA, single-phase transformer with a 120/240 V secondary is 729 amperes, calculated based on the transformer’s full load capacity. Think about the flexibility in the mounting orientation of double-throw knife switches as permitted by the NEC. 9 / 50 Double-throw knife switches shall be permitted to be mounted so that the throw is ____________________. a. Horizontal b. Vertical c. Either vertical or horizontal d. Lockable The selected mounting orientation does not align with NEC requirements for double-throw knife switches. Correct! Double-throw knife switches may be mounted so that the throw is either vertical or horizontal, as permitted by NEC Article 404.6(B). According to NEC Article 404.6(B), double-throw knife switches can be mounted with the throw in either a vertical or horizontal position, providing flexibility for installation based on the application. Proper documentation for overhead high-voltage conductors ensures safe clearances based on their physical and electrical characteristics. 10 / 50 Documentation for the spacing between overhead conductors rated over 1000 volts shall include _______________. a. Type of Construction Class b. Arc-Fault Protection c. Distance from Ground d. Conductor Size The selected option does not align with NEC requirements. Documentation must include conductor size to determine appropriate spacing for overhead conductors rated over 1000 volts. Correct! Documentation for spacing between overhead conductors rated over 1000 volts must include conductor size, as specified in NEC Article 490.30(A). According to NEC Article 490.30(A), documentation for the spacing between overhead conductors rated over 1000 volts must include factors such as conductor size, which determines the electrical and mechanical properties influencing spacing requirements. The NEC ensures that dimmers are properly protected against overcurrent to prevent damage or unsafe conditions. 11 / 50 Where dimmers are installed in ungrounded conductors, each dimmer shall have overcurrent protection not greater than _______________ of the dimmer rating and shall be disconnected from all ungrounded conductors when the master or individual switch or circuit breaker supplying such dimmer is in the open position. a. 115 percent b. 125 percent c. 110 percent d. 120 percent Incorrect! The NEC specifies that dimmers must have overcurrent protection not exceeding 125 percent of their rated load, per NEC Article 404.14(E). Correct! Overcurrent protection for dimmers installed in ungrounded conductors must not exceed 125 percent of the dimmer rating, as stated in NEC Article 404.14(E). 125 percent: According to NEC 404.14(E), overcurrent protection for dimmers must not exceed 125 percent of their rated load to ensure safety and compliance. Other percentages like 110%, 115%, and 120% are not aligned with the NEC requirements for dimmer overcurrent protection. Consider the ampacity rating for 3 current-carrying conductors in a flexible cord under NEC guidelines. 12 / 50 What is the allowable ampacity for a flexible Type SO cord with 3 current-carrying conductors? a. 25-amp b. 18-amp c. 30-amp d. 20-amp The selected ampacity does not align with NEC requirements for a flexible Type SO cord with 3 current-carrying conductors. Correct! The allowable ampacity for a flexible Type SO cord with 3 current-carrying conductors is 20 amperes, as specified in NEC Table 400.5(A)(1). According to NEC Table 400.5(A)(1), the allowable ampacity for a flexible Type SO cord with 3 current-carrying conductors is 20 amperes. This rating accounts for the heat dissipation limitations of the cord and ensures safe operation. The NEC mandates noncombustible material protection for large outlet boxes to ensure fire safety. 13 / 50 Any combustible wall exposed between the edge of a luminaire canopy and an outlet box having a surface area of _______________ shall be covered with noncombustible material. a. 120 inches squared or more b. 240 inches squared or more c. 90 inches squared or more d. 180 inches squared or more The selected surface area does not comply with NEC requirements. Outlet boxes with a surface area of 180 square inches or more require noncombustible material protection. Correct! Combustible walls exposed near outlet boxes with a surface area of 180 square inches or more must be covered with noncombustible material, as specified in NEC Article 410.23. According to NEC Article 410.23, any combustible wall exposed between the edge of a luminaire canopy and an outlet box with a surface area of 180 square inches or more must be covered with noncombustible material. This requirement minimizes the risk of fire in areas where luminaires are installed. The overcurrent protective device for the primary side of a transformer is sized based on the transformer’s primary full-load current and NEC rules. 14 / 50 A 75 kVA 3-phase 480-volt transformer is fed from a 3-phase 200-ampere fused disconnect. The transformer secondary feeds a 3-phase 120/208-volt panel less than 25 feet away from the transformer. Size the primary overcurrent protective device that must be installed at this panel, assuming no secondary overcurrent protection will be used. a. 200 amperes b. 300 amperes c. 225 amperes d. 350 amperes The selected size does not comply with NEC requirements for primary overcurrent protection of the transformer. Correct! The primary overcurrent protective device for the transformer must be sized at 200 amperes, as specified in NEC Article 450.3(B) and 240.6(A). Based on NEC Article 450.3(B) and 240.6(A), the primary overcurrent protective device must be sized at 200 amperes, as it is the closest standard size below the calculated maximum. The NEC specifies reduced ampacity requirements for light intermittent duty to account for reduced operational demands. 15 / 50 Where the secondary resistor of a wound-rotor AC motor is separate from the controller, and the motor is rated for light intermittent duty, the ampacity of the conductors between the controller and resistor shall not be less than: a. 75% b. 55% c. 65% d. 85% The selected percentage does not align with NEC requirements. For light intermittent duty, the conductors must have an ampacity of at least 75% of the motor’s full-load current. Correct! The ampacity of conductors between the controller and secondary resistor for a light intermittent duty motor must be at least 75% of the motor’s full-load current, as specified in NEC Article 430.23(A). According to NEC Article 430.23(A), for wound-rotor AC motors rated for light intermittent duty, the ampacity of conductors between the controller and secondary resistor must be at least 75% of the motor full-load current. This reduction accounts for the lower duty cycle and reduced heating effects during intermittent operation. This clearance ensures safe operation by minimizing the risk of overheating and fire hazards near combustible materials. 16 / 50 Resistors and reactors shall have a clearance of not less than _______________ from combustible materials. a. 12 inches b. 18 inches c. 6 inches d. 24 inches The selected clearance does not meet the NEC safety standards. Resistors and reactors must maintain a minimum of 12 inches of clearance from combustible materials. Correct! Resistors and reactors require a clearance of at least 12 inches from combustible materials, as stated in NEC Article 470.3(B). According to NEC Article 470.3(B), resistors and reactors must have a minimum clearance of 12 inches from combustible materials to allow for safe dissipation of heat and to prevent fire hazards. The size and capacity of heating panels/units determine the number required for a specific area. 17 / 50 A driveway has 1500 sq ft of heated area to cover with embedded snow-melting equipment. How many heating panels/units, minimum, will this application require? a. 12 b. 10 c. 11 d. 13 The selected number of units is insufficient to cover the 1500 sq ft heated area. A total of 13 units is needed, as each unit typically covers 120 sq ft. Correct! A minimum of 13 heating panels/units is required to cover a 1500 sq ft heated driveway area, based on standard coverage per unit. o determine the number of heating panels/units needed: Panel Capacity: Most snow-melting panels are rated to cover 120 sq ft per unit (standard rating). Total Area: Divide the total area by the coverage per unit: Units Required=Total AreaCoverage per Unit=1500 sq ft120 sq ft/unit=12.5 units\text{Units Required} = \frac{\text{Total Area}}{\text{Coverage per Unit}} = \frac{1500 \, \text{sq ft}}{120 \, \text{sq ft/unit}} = 12.5 \, \text{units}Units Required=Coverage per UnitTotal Area=120sq ft/unit1500sq ft=12.5units Rounding Up: Since partial units cannot be installed, round up to the next whole number, resulting in 13 units. Apparent power is calculated by multiplying the full-load current by the operating voltage. 18 / 50 What is the apparent power (in VA) of a 1HP, 115-volt motor that has a full-load current of 16 amperes? a. None of these b. 1840 VA c. 1920 VA d. 1773 VA The selected value does not match the calculated apparent power of 1840 VA for the given motor specifications. Correct! The apparent power for the motor is 1840 VA, calculated using the full-load current and voltage values. Formula for apparent power: S(Apparent Power in VA)=I(Current in A)×V(Voltage in V)S (\text{Apparent Power in VA}) = I (\text{Current in A}) \times V (\text{Voltage in V})S(Apparent Power in VA)=I(Current in A)×V(Voltage in V) Substitute the values: Current (III) = 16 A Voltage (VVV) = 115 V S=16 A×115 V=1840 VAS = 16 \, \text{A} \times 115 \, \text{V} = 1840 \, \text{VA}S=16A×115V=1840VA Final Value: The apparent power of the motor is 1840 VA. This requirement ensures that heat-generating equipment does not pose a fire hazard to nearby combustible materials. 19 / 50 Resistors and reactors shall have a clearance of not less than _______________ from combustible materials. a. 12 inches b. 24 inches c. 6 inches d. 18 inches The selected clearance does not meet the NEC requirements. Resistors and reactors require at least 12 inches of clearance from combustible materials. Correct! Resistors and reactors must have a clearance of at least 12 inches from combustible materials, as specified in NEC Article 470.3(B). According to NEC Article 470.3(B), resistors and reactors must maintain a clearance of at least 12 inches from combustible materials. This clearance helps to prevent overheating and potential fire hazards. Focus on the adjustment factor for resistance heating loads as required by the NEC for accurate overcurrent protection. 20 / 50 The rating of the overcurrent protective device for the circuit supplying the industrial control panel shall not be greater than the sum of the largest rating of the branch-circuit short-circuit and ground-fault protective device provided with the industrial control panel, ____________, plus the sum of the full-load currents of all other motors and apparatus that could be in operation at the same time. a. Plus 80% of the FLA rating of all resistance heating loads b. Plus 100% of the FLA rating of all resistance heating loads c. Plus 125% of the FLA rating of all resistance heating loads d. Plus 150% of the FLA rating of all resistance heating loads The selected option does not comply with NEC requirements for overcurrent protection of industrial control panels. Correct! The overcurrent protective device rating must include 125% of the FLA rating of all resistance heating loads, as specified in NEC Article 409.21. According to NEC Article 409.21, the overcurrent protective device for an industrial control panel circuit must account for the largest branch-circuit protective device plus 125% of the FLA rating of all resistance heating loads. This ensures adequate protection for both the control panel and the associated heating loads. This temperature limit is set to prevent the risk of fire from excessive heat produced by luminaires. 21 / 50 Luminaires shall be constructed, installed, or equipped with shades or guards so that combustible material is not subjected to temperatures in excess of _______________ degrees F. a. 104 b. 201 c. 194 d. 167 The selected temperature does not align with NEC requirements for preventing excessive heat exposure to combustible materials near luminaires. Correct! Luminaires must be installed to ensure that combustible materials are not subjected to temperatures exceeding 194 degrees F, as specified in NEC Article 410.11. According to NEC Article 410.11, luminaires must be designed, installed, or equipped with shades or guards to ensure that combustible materials are not exposed to temperatures exceeding 194 degrees F. This requirement minimizes the risk of fire due to excessive heat. This provision applies to small appliances with limited power ratings where additional disconnecting means might not be necessary. 22 / 50 For permanently connected appliances rated at not over _______________ or 1⁄8 hp, the branch-circuit overcurrent device shall be permitted to serve as the disconnecting means where the switch is within sight from the appliance. a. 150 volt-amperes b. 180 volt-amperes c. 300 volt-amperes d. 250 volt-amperes The selected value does not comply with NEC requirements. Appliances rated at 300 volt-amperes or less are permitted to use the branch-circuit overcurrent device as the disconnecting means when within sight. Correct! For permanently connected appliances rated at 300 volt-amperes or less, the branch-circuit overcurrent device may serve as the disconnecting means if within sight, as per NEC Article 422.31(A). According to NEC Article 422.31(A), for permanently connected appliances rated 300 volt-amperes or less or 1/8 hp or less, the branch-circuit overcurrent device (e.g., a circuit breaker) is permitted to serve as the disconnecting means, provided it is within sight of the appliance. The size of the circuit breaker is based on the motor’s full-load current (FLC) and the allowable percentage for inverse-time circuit breakers. 23 / 50 Motor Branch Circuit Protection: Calculate the inverse-time circuit breaker needed for a 3-phase, 208 V, 50 HP squirrel-cage motor. a. 450 amperes b. 400 amperes c. 350 amperes d. 500 amperes The selected circuit breaker size does not comply with NEC requirements for motor branch circuit protection. Correct! The inverse-time circuit breaker needed for this motor is 400 amperes, as calculated using NEC Table 430.52 and Table 430.250. The correct size for the inverse-time circuit breaker to protect a 3-phase, 208 V, 50 HP squirrel-cage motor is 400 amperes, based on the motor’s full-load current and NEC requirements. Consider the visibility requirement for the circuit breaker in relation to the appliance. 24 / 50 For permanently connected appliances rated over 300 VA, the circuit breaker must be ___________________ from the appliance. a. Accessible b. Remote c. Inaccessible d. Is within sight The selected option does not meet NEC requirements for the location of the circuit breaker in relation to permanently connected appliances. Correct! The circuit breaker for a permanently connected appliance rated over 300 VA must be within sight of the appliance, as per NEC Article 422.31(B). According to NEC Article 422.31(B), for permanently connected appliances rated over 300 VA, the circuit breaker must be within sight of the appliance. This ensures safety and accessibility during servicing or maintenance. The neutral load includes the unbalanced portion of line-to-neutral loads. For nonlinear loads, the neutral conductor must account for the full current of these loads due to harmonic currents. 25 / 50 What is the feeder/service neutral calculated load for the following service: 200 amps Line-to-Line loads 200 amps Line-to-Neutral Nonlinear Loads 200 amps Line-to-Neutral Linear Loads a. 225 amperes b. 400 amperes c. 275 amperes d. 300 amperes The selected value does not account for the full contribution of nonlinear and linear line-to-neutral loads. The correct answer is 400 amperes. Correct! The feeder/service neutral calculated load is 400 amperes, accounting for both the full nonlinear load and the linear unbalanced load. To calculate the feeder/service neutral load: Line-to-Line Loads: These do not contribute to the neutral load since the current flows between the phases. Line-to-Neutral Linear Loads: These contribute their unbalanced current directly to the neutral. Linear Load Contribution = 200 A. Line-to-Neutral Nonlinear Loads: These contribute the full current to the neutral due to harmonic currents. Nonlinear Load Contribution = 200 A. Total Neutral Load: Neutral Load=200 A (linear)+200 A (nonlinear)=400 A.\text{Neutral Load} = 200 \, \text{A (linear)} + 200 \, \text{A (nonlinear)} = 400 \, \text{A}.Neutral Load=200A (linear)+200A (nonlinear)=400A. To calculate the feeder conductor size, determine the total current using the largest motor’s full-load current at 125%, plus the sum of the full-load currents of the other motors. 26 / 50 Select the feeder conductor size for the following motor group (All motors have a Service Factor of 1.15 and a Marked Temperature Rise of 40 degrees C): Motor 1: 3-phase, 208 V, 50 HP motor Motor 2: 3-phase, 208 V, 30 HP motor Motor 3: 3-phase, 208 V, 20 HP motor Motor 4: 3-phase, 208 V, 10 HP motor a. 300 kcmil THW copper b. 500 kcmil THW copper c. 350 kcmil THW copper d. 600 kcmil THW copper The selected size does not meet the required ampacity for this motor group. The correct size is 500 kcmil THW copper, calculated according to NEC Article 430.24. Correct! The feeder conductor size is 500 kcmil THW copper, which satisfies the ampacity requirement of 348 A, as specified by NEC Article 430.24. Determine Full-Load Currents: Use NEC Table 430.250 for 3-phase motors operating at 208 volts: Motor 1 (50 HP): 136 A Motor 2 (30 HP): 88 A Motor 3 (20 HP): 58 A Motor 4 (10 HP): 32 A Apply NEC 430.24: The feeder conductor ampacity must be sized for: 1.25×Largest Motor Current+Sum of Other Motor Currents1.25 \times \text{Largest Motor Current} + \text{Sum of Other Motor Currents}1.25×Largest Motor Current+Sum of Other Motor Currents Largest Motor Current (Motor 1): 1.25×136=170 A1.25 \times 136 = 170 \, \text{A}1.25×136=170A Sum of Other Motors: 88+58+32=178 A88 + 58 + 32 = 178 \, \text{A}88+58+32=178A Total Feeder Ampacity: 170+178=348 A170 + 178 = 348 \, \text{A}170+178=348A Select Feeder Conductor Size: From NEC Table 310.16, 500 kcmil THW copper has an ampacity of 380 A at 75°C, which is sufficient for the calculated ampacity of 348 A. Think about the maximum load percentage allowed on a branch circuit for a single appliance like a room air conditioner. 27 / 50 The total marked rating of a cord- and attachment-plug-connected room air conditioner shall not exceed ____________________ of the rating of a branch circuit where no other loads are supplied. a. 125% b. 90% c. 80% d. 75% The selected value does not align with the NEC requirement for maximum load percentages on branch circuits. Correct! The total marked rating of a cord- and attachment-plug-connected room air conditioner must not exceed 80% of the branch circuit rating if no other loads are supplied, as specified in NEC Article 440.62(B). According to NEC Article 440.62(B), the total marked rating of a cord- and attachment-plug-connected room air conditioner shall not exceed 80% of the branch circuit rating if no other loads are supplied. This ensures the circuit is not overloaded and provides a margin for safe operation. The NEC sets a specific voltage threshold for lampholders used in infrared industrial heating equipment when operated in series. 28 / 50 Infrared industrial process heating equipment lampholders shall be permitted to be operated in series on circuits of _______________. a. Over 50 volts to ground b. Over 300 volts to ground c. Over 150 volts to ground d. Over 120 volts to ground The selected voltage does not meet the NEC requirements for lampholders in infrared industrial process heating equipment. Correct! Infrared industrial process heating equipment lampholders may be operated in series on circuits of over 150 volts to ground, as specified in NEC Article 425.55. According to NEC Article 425.55, lampholders for infrared industrial process heating equipment are permitted to be operated in series on circuits of over 150 volts to ground. This allowance ensures the equipment can function safely and efficiently in industrial settings with higher voltage requirements. Consider situations where tamper-resistant receptacles may not be necessary due to reduced accessibility. 29 / 50 All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles must be listed tamper-resistant receptacles, except in which of the following instances? a. Dwelling units b. Business offices, corridors, waiting rooms, and the like in clinics, medical, and dental offices and outpatient facilities c. Receptacles located more than 5 1/2 ft above the floor d. Child care facilities The selected option does not fall under the exceptions for tamper-resistant receptacle requirements in NEC Article 406.12. Correct! Tamper-resistant receptacles are not required for receptacles located more than 5 1/2 feet above the floor, as specified in NEC Article 406.12. According to NEC Article 406.12, tamper-resistant receptacles are generally required in specific occupancies to prevent tampering and improve safety. However, receptacles located more than 5 1/2 feet above the floor are exempt, as they are out of reach for children and less likely to be tampered with. Consider the NEC-specified minimum clearance required for heat-producing components near combustible materials. 30 / 50 A thermal barrier is required if the space between the resistors and reactors and any combustible material is less than __________________. a. 12 inches b. 6 inches c. 18 inches d. 24 inches The selected clearance does not comply with NEC requirements for resistors and reactors near combustible materials. Correct! A thermal barrier is required if the clearance between resistors, reactors, and combustible materials is less than 12 inches, as specified in NEC Article 470.3(B). According to NEC Article 470.3(B), a thermal barrier is required if the space between resistors and reactors and any combustible material is less than 12 inches. This ensures safety by reducing the risk of fire from heat generated by these components. The rotary-phase converter must be operational before supplying power to ensure proper functionality and load balance. 31 / 50 Power to the utilization equipment shall not be supplied until _______________. a. The installation is inspected by an electrical engineer b. The rotary-phase converter has been started c. The rotary-phase converter has been started d. The rotary-phase converter has been tested The selected option does not comply with NEC requirements. Power can only be supplied after the rotary-phase converter has been started, per NEC Article 455.8(A). Correct! Power to the utilization equipment cannot be supplied until the rotary-phase converter has been started, as required by NEC Article 455.8(A). Power to utilization equipment connected to a rotary-phase converter cannot be supplied until the converter is operational. This ensures that: The phase conversion is working correctly. The equipment receives appropriate voltage and phase balance. The system is safe for operation. NEC Article 455.8(A) ensures that this prerequisite is met to prevent damage or malfunction of the connected equipment. The overload protection percentage depends on the motor’s service factor. Use 125% of the full-load current for motors with a service factor of 1.15 or higher. 32 / 50 Determine the motor overload protection for a 25-hp, 460-V, 3-phase, squirrel-cage motor with a nameplate full-load current of 32 A, Design B, Service Factor 1.15. a. 40 amperes b. 53 amperes c. 63 amperes d. 55 amperes The selected overload protection size does not comply with NEC requirements for a motor with this service factor and full-load current. Correct! The motor overload protection for this motor is 40 amperes, as calculated using NEC Article 430.32(A)(1). According to NEC Article 430.32(A)(1), for a 25-hp motor with a full-load current of 32 A and a service factor of 1.15, the overload protection must be set to 40 amperes (125% of the full-load current). The NEC generally prohibits the disconnection of grounded conductors unless specific conditions are met. 33 / 50 Switches or circuit breakers _______________ disconnect the grounded conductor of a circuit. a. Shall not b. 1000 volts or more should c. Shall d. Rated less than 1000 volts shall The selected option does not comply with NEC requirements for disconnecting grounded conductors. Correct! Switches or circuit breakers shall not disconnect the grounded conductor of a circuit unless they disconnect all conductors simultaneously, as specified in NEC Article 404.2(B). According to NEC Article 404.2(B), switches or circuit breakers shall not disconnect the grounded conductor of a circuit unless they simultaneously disconnect all conductors of the circuit, including the ungrounded conductors. This prevents leaving ungrounded conductors energized while the grounded conductor is disconnected, which could create unsafe conditions. The NEC specifies that the screw shell must always be connected to the neutral conductor to ensure safety. 34 / 50 Luminaires shall be wired so that the screw shells of lampholders are connected to the same luminaire or circuit conductor or terminal. The ______________, where connected to a screw shell lampholder, shall be connected to the screw shell. a. Ungrounded conductor b. Equipment grounding conductor c. Grounded conductor d. Bonding jumper The selected option does not comply with NEC requirements for connecting the screw shell of lampholders. Correct! The grounded conductor must be connected to the screw shell of a lampholder, as specified in NEC Article 410.50. According to NEC Article 410.50, the grounded conductor (neutral) must be connected to the screw shell of the lampholder. This reduces the risk of electric shock when replacing lamps, as the outer shell is less likely to be energized. Look up the full-load current for a 5-HP, 3-phase motor operating at 230 volts in NEC Table 430.250. 35 / 50 What is the full-load current of a 3-phase, 230-volt, 5-HP AC wound-rotor motor? a. 22 amperes b. 7.6 amperes c. 9.6 amperes d. 15.2 amperes The selected value does not match the NEC Table 430.250 listing for the full-load current of a 5-HP, 3-phase, 230-volt motor. Correct! The full-load current of a 5-HP, 3-phase, 230-volt AC wound-rotor motor is 15.2 amperes, as listed in NEC Table 430.250. According to NEC Table 430.250, the full-load current (FLC) of a 5-HP, 3-phase, 230-volt wound-rotor motor is 15.2 amperes. This value is standardized for design, protection, and conductor sizing purposes. The NEC allows a specific type of connector to act as a disconnecting means for portable and cord-connected equipment. 36 / 50 For cord-connected equipment, a separable connector or a(n) _______________ shall be permitted to serve as the disconnecting means. a. None of these b. Weatherproof cord cap c. None of these d. Attachment plug and receptacle The selected option does not align with NEC requirements for disconnecting means for cord-connected equipment. Correct! An attachment plug and receptacle is permitted to serve as the disconnecting means for cord-connected equipment, as specified in NEC Article 400.7(A)(8) and Article 430.109(F). According to NEC Article 400.7(A)(8) and Article 430.109(F), an attachment plug and receptacle can serve as the disconnecting means for cord-connected equipment. This is permitted because the plug and receptacle can be quickly and safely separated to de-energize the equipment. Tamper-resistant receptacles are required in specific areas, including health care facilities and locations frequented by children. 37 / 50 All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles in dental offices shall be listed tamper-resistant receptacles. a. False b. True Incorrect! Dental offices require tamper-resistant receptacles for safety, as specified in NEC Article 406.12. Correct! All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles in dental offices must be tamper-resistant, as stated in NEC Article 406.12. True: As per NEC 406.12, tamper-resistant receptacles are required in dental offices, which are considered public or healthcare spaces. This ensures safety, especially in areas accessible to the public. False: This option is incorrect because dental offices fall under the NEC requirement for tamper-resistant receptacles for added safety. Conductor sizing for capacitors must account for the rated current of the capacitor to ensure safe operation. 38 / 50 Where capacitors are installed in motor circuits, conductors shall not be less than _____________ percent of the rated current of the capacitor. a. 80 b. 125 c. 135 d. 115 The selected percentage does not meet the NEC requirement for conductor sizing in capacitor motor circuits. Correct! Conductors for capacitors in motor circuits must be sized to at least 135% of the rated current of the capacitor, as specified in NEC Article 460.8(A). According to NEC Article 460.8(A), the conductors connected to capacitors in motor circuits must be sized to handle 135% of the rated current of the capacitor. This requirement ensures that the conductors can safely carry the current without overheating. This rule is meant to ensure safety by keeping luminaires out of reach and away from water sources in these areas. 39 / 50 No parts of cord-connected luminaires shall be located within a zone measuring horizontally _______________ feet and 8 feet vertically from the top of the bathtub rim or shower stall threshold. a. 4 b. 6 c. 5 d. 3 The selected distance does not comply with NEC requirements for the placement of cord-connected luminaires near bathtubs and shower stalls. Correct! Cord-connected luminaires must not be located within 3 feet horizontally and 8 feet vertically from the top of the bathtub rim or shower stall threshold, as specified in NEC Article 410.10(D). According to NEC Article 410.10(D), no parts of cord-connected luminaires are allowed within a zone extending 3 feet horizontally and 8 feet vertically from the top of the bathtub rim or shower stall threshold. This ensures that luminaires are kept at a safe distance to reduce the risk of electric shock. The NEC requires special markings to ensure compatibility and safety when using aluminum conductors. 40 / 50 Snap switches rated 20 amperes or less directly connected to aluminum conductors shall be listed and marked ______________. a. For use in wet environments b. Aluminum conductors only c. ALM/CU d. CO/ALR The selected marking does not comply with NEC requirements for snap switches connected to aluminum conductors. Correct! Snap switches rated 20 amperes or less directly connected to aluminum conductors must be listed and marked CO/ALR, as specified in NEC Article 404.14(C). According to NEC Article 404.14(C), snap switches rated 20 amperes or less that are directly connected to aluminum conductors must be listed and marked CO/ALR. This marking indicates compatibility with both copper and aluminum conductors and ensures the connections are safe and reliable. The NEC provides strict limitations on voltage ratings and installation environments for transformers with less-flammable liquid insulation in certain building types. 41 / 50 Transformers insulated with listed less-flammable liquids that have a fire point of not less than 300°C shall be permitted to be installed in Type I or Type II buildings, in areas where the transformer is rated 45,000 volts or more. a. True b. False Incorrect! The NEC prohibits transformers rated 45,000 volts or more with less-flammable liquid insulation from being installed in Type I or Type II buildings, per NEC Article 450.23(A). Correct! Transformers with less-flammable liquid insulation are not permitted in Type I or Type II buildings at voltages rated 45,000 volts or more, as specified in NEC Article 450.23(A). False: Transformers insulated with less-flammable liquids are not permitted in areas with voltages rated 45,000 volts or more in Type I or Type II buildings. This restriction is due to safety concerns related to high voltages and potential fire hazards. True: This is incorrect because the NEC does not permit such high-voltage transformers in these building types, even with less-flammable liquids. Use the formula for calculating full-load current (FLC) of a DC motor: FLC=Horsepower×746Voltage×Efficiency×Power Factor\text{FLC} = \frac{\text{Horsepower} \times 746}{\text{Voltage} \times \text{Efficiency} \times \text{Power Factor}}FLC=Voltage×Efficiency×Power FactorHorsepower×746 Assume an efficiency and power factor of 1.0 unless specified otherwise. 42 / 50 What is the full-load current (FLC) of a 100-HP, 500-volt DC motor? a. 164 amperes b. 205 amperes c. 123 amperes d. 341 amperes The selected value does not match the calculated full-load current for a 100-HP, 500-volt DC motor. Correct! The full-load current (FLC) of a 100-HP, 500-volt DC motor is 164 amperes, based on the standard calculation. Formula for FLC of a DC Motor: FLC=HP×746Voltage.\text{FLC} = \frac{\text{HP} \times 746}{\text{Voltage}}.FLC=VoltageHP×746. Substitute Values: FLC=100×746500=74,600500=164 amperes.\text{FLC} = \frac{100 \times 746}{500} = \frac{74,600}{500} = 164 \, \text{amperes}.FLC=500100×746=50074,600=164amperes. Result: The full-load current for a 100-HP, 500-volt DC motor is 164 amperes. The maximum allowable temperature for combustible materials near luminaires is based on safety standards to prevent ignition. 43 / 50 Luminaires shall be constructed, installed, or equipped with shades or guards so that combustible material is not subjected to temperatures in excess of _________________. a. 200 degrees F b. 90 degrees F c. 194 degrees F d. 104 degrees F The selected temperature does not comply with NEC limits for luminaires near combustible materials. Correct! Luminaires must prevent combustible materials from being subjected to temperatures exceeding 194 degrees Fahrenheit, as specified in NEC Article 410.11. According to NEC Article 410.11, luminaires must be designed and installed to ensure that combustible materials are not exposed to temperatures exceeding 194 degrees Fahrenheit. This requirement minimizes the risk of fire caused by excessive heat from luminaires. Use NEC Table 430.52 to determine the maximum percentage of motor full-load current (FLC) allowed for a non-time delay fuse. 44 / 50 A three-phase, 230-volt wound-rotor motor rated at 15 HP requires short-circuit and ground-fault protection. The manufacturer specifies a non-time delay fuse. What size fuse should be selected? a. 50 amperes b. 45 amperes c. 65 amperes d. 60 amperes The selected fuse size does not comply with NEC Table 430.52 for a wound-rotor motor using a non-time delay fuse. Correct! A 60-ampere fuse is the appropriate size for the 15-HP, 230-volt wound-rotor motor, as specified by NEC Article 430.52. Determine Full-Load Current (FLC): From NEC Table 430.250, the FLC of a 15-HP, 230-volt, 3-phase wound-rotor motor is 42 amperes. Apply Maximum Overcurrent Protection Factor: For wound-rotor motors, NEC Table 430.52 specifies a maximum of 150% for non-time delay fuses: FuseSize=FLC×1.50Fuse Size = FLC \times 1.50FuseSize=FLC×1.50 FuseSize=42 A×1.50=63 A.Fuse Size = 42 \, \text{A} \times 1.50 = 63 \, \text{A}.FuseSize=42A×1.50=63A. Select the Standard Fuse Size: Per NEC 240.6(A), the next standard size fuse is 60 amperes. This clearance ensures safe heat dissipation and prevents potential fire hazards. 45 / 50 A space not less than _______________ shall be provided between the top of the switchboard and any combustible ceiling. a. 4 feet b. 6 feet c. 5 feet d. 3 feet The selected clearance does not align with NEC requirements. The minimum required clearance is 3 feet between the switchboard and a combustible ceiling. Correct! A space of at least 3 feet must be maintained between the top of a switchboard and any combustible ceiling, as specified in NEC Article 408.18(A). According to NEC Article 408.18(A), a clearance of at least 3 feet must be maintained between the top of a switchboard and any combustible ceiling. This is to ensure proper ventilation, heat dissipation, and fire safety. Receptacles designed for aluminum conductors are typically used in residential and light commercial applications with specific ampere ratings. 46 / 50 Receptacles rated and designed for the direct connection of aluminum conductors must be marked CO/ALR and rated for _______________. a. 20 amperes or less b. 15 amperes or more c. 20 amperes or more d. 30 amperes or less The selected ampere rating does not align with NEC requirements for receptacles designed for aluminum conductors. Correct! Receptacles rated 20 amperes or less and designed for the direct connection of aluminum conductors must be marked CO/ALR, as specified in NEC Article 406.3(C). According to NEC Article 406.3(C), receptacles rated 20 amperes or less and designed for the direct connection of aluminum conductors must be marked CO/ALR. This marking ensures compatibility and safety when using aluminum wiring, which has different characteristics than copper. The NEC includes a safety feature requirement for receptacles in dwelling units to protect children from electrical hazards. 47 / 50 All 15- and 20-ampere, 125- and 250-volt non-locking type receptacles in dwelling units shall be listed _______________ receptacles. a. Isolated b. Tamper-resistant c. Bonded d. Effectively attached The selected option does not align with NEC requirements for receptacles in dwelling units. Correct! All 15- and 20-ampere, 125- and 250-volt non-locking type receptacles in dwelling units must be listed tamper-resistant receptacles, as specified in NEC Article 406.12(A). According to NEC Article 406.12(A), all 15- and 20-ampere, 125- and 250-volt non-locking type receptacles installed in dwelling units must be tamper-resistant receptacles. This requirement helps to reduce the risk of electrical shock, particularly for children, by preventing foreign objects from being inserted into the receptacle slots. Consider the NEC limitations on lamp bases for safety and standardization in lighting branch circuits. 48 / 50 An incandescent lamp for general use on lighting branch circuits shall not be equipped with a mogul base if rated over _______________ watts. a. 1500 b. 1200 c. 1000 d. 1250 The selected wattage does not align with NEC requirements for mogul bases on incandescent lamps. Correct! An incandescent lamp for general use shall not be equipped with a mogul base if rated over 1500 watts, as specified in NEC Article 410.30(B). According to NEC Article 410.30(B), incandescent lamps for general use on lighting branch circuits shall not be equipped with a mogul base if rated over 1500 watts. This requirement is intended to standardize lamp bases and prevent excessive power usage in lighting circuits. Think about the level of exposure to moisture that necessitates a weatherproof cover. 49 / 50 In _______________ locations, a flush-mounted switch or circuit breaker shall be equipped with a weatherproof cover. a. Wet b. Damp c. Dry d. Isolated The selected location does not align with NEC requirements for the use of weatherproof covers on flush-mounted switches or circuit breakers. Correct! A flush-mounted switch or circuit breaker in damp locations must be equipped with a weatherproof cover, as specified in NEC Article 404.4. According to NEC Article 404.4, in damp locations, a flush-mounted switch or circuit breaker must be equipped with a weatherproof cover to protect against moisture and ensure safe operation. The NEC ensures that dimmers are properly protected against overcurrent to prevent damage or unsafe conditions. 50 / 50 Where dimmers are installed in ungrounded conductors, each dimmer shall have overcurrent protection not greater than _______________ of the dimmer rating and shall be disconnected from all ungrounded conductors when the master or individual switch or circuit breaker supplying such dimmer is in the open position. a. 110 percent b. 115 percent c. 120 percent d. 125 percent Incorrect! The NEC specifies that dimmers must have overcurrent protection not exceeding 125 percent of their rated load, per NEC Article 404.14(E). Correct! Overcurrent protection for dimmers installed in ungrounded conductors must not exceed 125 percent of the dimmer rating, as stated in NEC Article 404.14(E). 125 percent: According to NEC 404.14(E), overcurrent protection for dimmers must not exceed 125 percent of their rated load to ensure safety and compliance. Other percentages like 110%, 115%, and 120% are not aligned with the NEC requirements for dimmer overcurrent protection. Your score is LinkedIn Facebook Twitter 0% Restart quiz Exit Rate & Review Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services. Send feedback Leave a Reply Cancel replyYour email address will not be published. Required fields are marked * Comment* Name* Email* Website Save my name, email, and website in this browser for the next time I comment. Post Comment