Report a question

You cannot submit an empty report. Please add some details.
0%

Article 400-490 Part09

This quiz consists of 50 carefully selected questions covering NEC Articles 400 through 490, which provide critical guidelines for flexible cords and cables (Article 400), switchgear and control equipment (Article 409), and installations operating above 1000 volts (Article 490). These sections of the National Electrical Code focus on safety, material specifications, and proper installation practices.

The randomly generated questions ensure a thorough assessment of your understanding, reinforcing key principles related to permitted uses of flexible cords, ampacity ratings, industrial control panels, and high-voltage equipment requirements. Some topics may reappear in different contexts to strengthen comprehension and application.

Your feedback is invaluable! If you notice any discrepancies or have suggestions for improvement, please report them. Your insights help maintain the accuracy and effectiveness of this learning tool.

Think about the protection required for the panelboard on the secondary side of the transformer to prevent electrical faults.

1 / 50

NEC 408.36(B) requires that panelboards supplied through a transformer have ________________ on the secondary side of the transformer.

Focus on the NEC article that deals with protecting motors from damage caused by overheating due to overload.

2 / 50

________ sets forth motor overload protection requirements.

Consider the temperatures that luminaires generate and the need for branch circuit conductors to have proper insulation to withstand these temperatures.

3 / 50

Branch circuit conductors that terminate in luminaires must have insulation suitable for the temperatures they will encounter.

Think about the key electrical parameters needed to ensure the correct operation of a motor circuit switch, such as the voltage it must handle.

4 / 50

The nameplate on all motor circuit switches, along with the manufacturer’s technical data, provides the horsepower rating, the _________ rating, and the ampere rating of the disconnect switch.

Consider changes made in recent NEC editions regarding the limitation on the number of overcurrent devices in panelboards.

5 / 50

Is it true that a lighting and appliance panelboard is limited to 42 overcurrent devices?

Focus on the part of the NEC that deals with the safe disconnection of motors for maintenance and emergencies.

6 / 50

Where does the NEC specifically refer to disconnecting means for a motor?

Consider what constitutes a disconnecting means in terms of providing a physical separation of the circuit to ensure safety.

7 / 50

Do start-stop and lock-out-stop buttons qualify as a disconnecting means?

Consider the primary purpose of overcurrent protection in transformer installations.

8 / 50

As specified in NEC 450.3, overcurrent devices protect the ___________ only.

Think about the NEC article that covers the safety standards and requirements for the installation and use of appliances.

9 / 50

Which NEC article specifically refers to appliances?

Consider the importance of safely securing lighting fixtures and outlets to a sturdy part of the building’s structure.

10 / 50

Both the lighting outlet and the luminaire must be supported by a structural member of the building.

Think about the NEC’s allowance for the placement of disconnects in relation to air-conditioning and refrigeration equipment.

11 / 50

Is it true that the air conditioning disconnect is permitted to be installed on or within the air-conditioning or refrigerating equipment?

Consider that overcurrent devices are designed to protect not only transformers but also the overall system, including conductors and connected equipment.

12 / 50

Is it true that overcurrent devices for transformers protect the transformer only?

Think about the type of luminaire that is specifically designed for safe installation in contact with insulation.

13 / 50

Type ______ luminaires are permitted to be installed in direct contact with thermal insulation.

Consider the NEC requirement for the installation of terminal bars for neutral and equipment grounding conductors in electrical panels.

14 / 50

Is it true that neutral and equipment grounding conductor terminal bars are installed as needed?

Consider the percentage required by NEC for the ampere rating of the disconnecting means in relation to the motor’s full-load current.

15 / 50

NEC 430.110(A) requires that the disconnecting means for motors rated at 1000 volts or less must have an ampere rating of not less than ____ of the motor’s full-load ampere rating.

Look for the NEC section that deals specifically with labeling and identifying the circuits in a panelboard.

16 / 50

The requirements for a circuit directory can be found in which NEC section?

Consider the flexibility of cord-and-plug-connected appliances, particularly in terms of providing a disconnecting means.

17 / 50

Does NEC 422.33 permit the use of a cord-and-plug-connected arrangement to serve as the appliance’s disconnecting means?

Consider the type of switch that can handle the specific electrical characteristics of motors in most applications.

18 / 50

For most applications, the motor circuit switch for a motor must be ____.

Think about the safety concerns associated with running wiring through luminaire outlet boxes that may not be rated for this use.

19 / 50

Branch circuit wiring is not permitted to pass through an outlet box that is an integral part of an incandescent luminaire unless the luminaire is identified for such use.

Consider the specific case of motor overload protection, where overcurrent devices can be used in grounded conductors as part of the system design.

20 / 50

Overcurrent devices are permitted to be used in ground conductors when used for motor overload protection.

Consider the standard requirements for motor conductors and their insulation ratings when connected to equipment with 75°C rated terminations.

21 / 50

For motors marked with design letters B, C, or D, conductors must have an insulation rating of 90 degrees Celsius. Is this statement true or false?

Think about the NEC article that deals specifically with lighting installation requirements.

22 / 50

The installation of luminaires, lighting outlets, and supports is covered in which NEC Article?

Focus on the NEC part that addresses the grounding of motor circuits to ensure safety by preventing exposed metal parts from becoming energized.

23 / 50

Where does the NEC specifically refer to grounding exposed noncurrent-carrying metal parts of motor circuits?

Think about the standard power output of smaller gasoline-powered generators and the appropriate wire gauge to safely handle their load.

24 / 50

These are typically gasoline-powered generators that use a flexible 4-wire rubber cord. A 12 AWG cord is used for ___-watt generators, while a 10 AWG cord is used for 7500-watt generators.

Focus on the article that deals with the specific requirements for air-conditioning and refrigerating equipment.

25 / 50

Where does the NEC specifically refer to air-conditioning equipment?

Think about the power ratings of small, portable generators versus larger units typically used in more demanding applications.

26 / 50

The NEC covers portable generators up to __ kW separately from those larger than __ kW.

Focus on the NEC article that deals with luminaires in specific spaces like clothes closets, where fire safety is a concern due to potential contact with combustible materials.

27 / 50

The types of luminaires permitted in clothes closets are covered in NEC _____.

Consider the percentage required for sizing motor branch-circuit conductors to ensure they can handle overload conditions without being undersized.

28 / 50

Motor branch-circuit conductors must not be smaller than ___ percent of the full-load current rating of the motor, as specified in NEC 430.22.

Focus on the section that addresses the disconnecting means location for motors and controllers to ensure safety and accessibility during operation or maintenance.

29 / 50

The disconnecting means for a motor is required to be located (1) within sight of the motor location and driven machinery location, or (2) the disconnecting means for the controller in accordance with 430.102(A) is located in sight from the motor and driven machine location. Which section of the NEC addresses this?

Focus on the NEC’s specifications for portable generators based on power output. Smaller generators have different requirements compared to larger ones.

30 / 50

The NEC provides separate coverage for portable generators up to __ kW from those exceeding __ kW.

Consider the type of panel that lacks a main breaker and only contains breakers for individual branch circuits.

31 / 50

Which type of panel contains only branch-circuit breakers?

Think about the article in the NEC that focuses specifically on lighting installations and related equipment.

32 / 50

The installation of luminaires, lighting outlets, and supports is covered under Article ____ of the NEC.

Consider whether the disconnect needs to be visible and accessible from both the controller and the motor itself.

33 / 50

Is it true that the disconnect only has to be in sight of the controller?

Think about the accessibility requirements for disconnect switches, ensuring they can be reached safely.

34 / 50

The center of the grip of a disconnect switch handle in its highest position must not be more than _________ above the floor or working platform.

Think about where the disconnect should be located to ensure easy access and safety for workers operating or servicing the motor.

35 / 50

Where is the disconnect means for a 208-volt, 3-phase motor controller required to be located?

Think about how the Code letters on a motor’s nameplate relate to starting current and the locked-rotor kVA per horsepower.

36 / 50

Is it true that the higher the Code letter on a motor’s nameplate, the lower the starting current?

Focus on the article that deals with the general requirements for appliances, including their installation and protection.

37 / 50

Where does the NEC specifically refer to appliances?

Consider the safety guidelines for placing electrical components like cleat-type lamp holders out of reach to prevent accidental contact with exposed terminals.

38 / 50

Cleat-type lamp holders located at least __ feet above the floor are permitted to have exposed terminals.

Think about the type of lighting that is embedded within ceilings or walls, which often requires specific support mechanisms like adjustable rails.

39 / 50

____________ are typically supported by adjustable rails attached to the luminaire’s rough-in box.

Think about the type of switch that is commonly used for simple control and disconnecting purposes for single-phase loads like exhaust fans.

40 / 50

NEC 430.111 permits a _________ snap (toggle) switch to serve as both the controller and the required disconnecting means for exhaust fans.

Refer to the NEC tables that provide the full-load ampere ratings for different types of motors, including single-phase, DC, and three-phase motors.

41 / 50

When selecting conductors, from which NEC table is the motor full-load ampere rating to be taken?

Look for the NEC article that deals specifically with the requirements for panelboards and their installation.

42 / 50

The general rules on the construction and installation of panelboards are found in NEC Article ___.

The overload device setting depends on the service factor of the motor. Motors with a higher service factor allow for greater tolerance in their overload protection settings.

43 / 50

A motor with a service factor of 1.25 must be protected by an overload device set to trip at no more than what percentage of the motor’s full-load current rating?

Consider the labeling requirements for motor controllers to ensure that the correct controller is used for the intended application.

44 / 50

Is it true that a controller must be marked with the manufacturer’s name or identification, voltage, current or horsepower rating, short-circuit rating, and other necessary data to indicate its proper application?

Consider which types of modern lighting technologies are recognized for their energy efficiency.

45 / 50

Most fluorescent lamps with energy-saving ballasts, compact fluorescent lamps (CFLs), LEDs, and halogen lamps meet the high-efficacy requirement.

Consider the term used in the NEC when discussing the location of equipment, especially when the motor is not directly visible.

46 / 50

The reason the Code uses the term ____ instead of motor is that, in many cases, the motor is inside an enclosure and out of sight until an access panel is removed.

Consider the most direct and reliable source for motor-specific information, which is typically attached to the motor itself.

47 / 50

When selecting motor overload protective devices, from where is the full-load ampere rating taken?

Consider the safety requirement for having the disconnect within a visible and accessible distance from the motor controller.

48 / 50

Where is the disconnect means for a 208-volt, 3-phase motor controller required to be located?

Think about the NEC’s requirements for ensuring that lighting fixtures and outlets are securely supported.

49 / 50

Is it true that both the lighting outlet and the luminaire must be supported from a structural member of the building?

Think about which sections in the NEC specifically cover motor circuits and the grounding requirements for their exposed metal parts.

50 / 50

Which NEC article specifically refers to grounding exposed noncurrent-carrying metal parts of motor circuits?

Your score is

0%

Exit

Rate & Review

Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services.

Leave a Reply

Your email address will not be published. Required fields are marked *