Understanding NEC Article 372: Cellular Concrete Floor Raceways

Introduction

NEC Article 372 provides guidelines for the use and installation of cellular concrete floor raceways, which are hollow spaces integrated into precast concrete floor slabs. These raceways serve as a concealed pathway for electrical wiring and are commonly used in high-rise office buildings due to their efficiency and adaptability.


Scope

This article applies to cellular concrete floor raceways and associated components, including header ducts, junction boxes, and inserts. The goal is to provide a safe and effective wiring method for commercial and institutional applications.


Key Features of Cellular Concrete Floor Raceways

  1. Integrated Design:
    • Floor cells form part of the structural system.
    • Header ducts and junction boxes connect and manage conductors within the cells.
  2. Versatility:
    • Suitable for a range of commercial applications, especially in high-rise buildings.
  3. Safety Compliance:
    • Systems must adhere to NEC rules for secure installation, proper grounding, and conductor limits.

Installation Requirements

Headers:
  1. Installed at right angles to the floor cells.
  2. Mechanically secured and sealed against concrete ingress.
  3. Must maintain electrical continuity throughout their length.
Connection to Cabinets and Enclosures:
  • Listed metal raceways and fittings must connect headers to distribution cabinets and other enclosures.
Junction Boxes:
  1. Positioned level with the floor grade.
  2. Sealed to prevent water or concrete entry.
  3. Must be metallic and electrically bonded to headers.
Inserts:
  1. Leveled and sealed to prevent concrete ingress.
  2. Equipped with grounded-type receptacles connected to a positive ground.
  3. Cutting for insert installation must avoid damaging conductors.
Markers:
  • Installed to identify cell locations for future reference.

Conductor and Capacity Guidelines

  1. Conductor Size:
    • Conductors larger than 1/0 AWG require special permission.
  2. Number of Conductors:
    • Combined cross-sectional area of conductors must not exceed 40% of the cell or header’s area.
  3. Ampacity:
    • Ampacity adjustments per 310.15(C) apply to ensure safe operation.
  4. Splices and Taps:
    • Only allowed in header access units or junction boxes, ensuring no splices or reinsulated conductors remain in abandoned raceways.

Prohibited Uses

  1. Corrosive Vapors:
    • Not allowed in environments with exposure to corrosive substances.
  2. Hazardous Locations:
    • Restricted unless explicitly permitted by other NEC articles.
  3. Commercial Garages:
    • Prohibited except for ceiling outlets or extensions below the floor.

Maintenance and Modifications

  1. Abandoned Outlets:
    • Conductors for discontinued outlets must be removed, and no splices can remain in the raceway.
  2. Regular Inspections:
    • Essential to maintain the integrity and compliance of the raceway system.

Applications

  1. High-Rise Office Buildings:
    • Efficient power distribution for lighting, outlets, and equipment.
  2. Institutional Facilities:
    • Adaptable for schools, hospitals, and other large-scale establishments.

Compliance Tips

  1. Follow Manufacturer Guidelines:
    • Use specified tools and components to ensure safe and effective installations.
  2. Monitor Conductor Fill:
    • Avoid overfilling raceways to prevent overheating and inefficiency.
  3. Inspect Seals and Bonding:
    • Ensure headers, junction boxes, and inserts are properly sealed and bonded.

Conclusion

NEC Article 372 provides essential standards for the safe and effective use of cellular concrete floor raceways. By integrating raceways into the structural floor system, electricians and engineers can achieve efficient power distribution in commercial buildings while adhering to safety and compliance standards.