Understanding NEC Article 445: Generators
Introduction
NEC Article 445 outlines critical installation and operational requirements for generators, ensuring their safe and effective use in various applications. These guidelines cater to stationary and portable generators and establish standards for overcurrent protection, location, marking, and emergency shutdown provisions. Understanding these rules is essential for electricians and engineers working with backup, standby, and primary power systems.
Scope
Article 445 governs generator installations and references additional articles for specific uses:
- Fire Pumps: Article 695
- Emergency Systems: Article 700
- Legally Required Standby Systems: Article 701
- Optional Standby Systems: Article 702
- Interconnected Electric Power Systems: Article 705
- Critical Operations Power Systems: Article 708
This article provides a universal framework for generator types while directing users to detailed provisions for specialized applications.
Key Highlights
Listing and Marking
- Listing Requirements: Stationary generators must be listed, adhering to UL 2200 standards. Custom or one-of-a-kind units may be field-labeled.
- Nameplate Information: Generators must include essential details such as manufacturer, voltage, power rating, reactances, and fault current data. This information aids in proper installation and compliance verification.
Location and Accessibility
Generators must be suitable for their installed locations, considering environmental and operational factors. Compliance with NFPA 37 ensures that generators are safely located to minimize risks from exhaust, noise, and vibration.
Overcurrent Protection
Generators require protective measures, including:
- Circuit Breakers: Provide robust overcurrent and fault protection.
- Two-Wire DC Generators: Overcurrent protection is applied to only one conductor.
- 65-Volt Systems: Motor-driven systems rely on motor protection devices for overcurrent control.
Disconnecting Means
All generators must have disconnecting means to isolate power for maintenance or emergencies. These means must:
- Simultaneously disconnect all ungrounded conductors.
- Be lockable in the open position.
- For parallel generators, the disconnecting system must isolate individual generators from the bus system.
Emergency Shutdown
Generators rated over 15 kW require emergency shutdown provisions:
- Remote Shutdown: Located outside the equipment room for quick access.
- One- and Two-Family Dwellings: Shutdown devices must be installed externally and clearly labeled.
Special Provisions for Portable Generators
Portable generators under 15 kW must have integrated GFCI protection for personnel safety. Differences in requirements exist for bonded and unbonded generators, ensuring compatibility with grounded premises wiring systems.
Practical Applications
- Data Centers: Parallel generator setups ensure uninterrupted power during outages.
- Construction Sites: Portable generators with GFCI protection provide temporary power safely.
- Residential Standby Systems: Integrated emergency shutdown devices facilitate safe operation and maintenance.
Conclusion
NEC Article 445 establishes comprehensive requirements for generator installations, covering everything from listing and marking to overcurrent protection and emergency shutdowns. By adhering to these guidelines, professionals can ensure safe and efficient generator operations across a wide range of settings.