Understanding NEC Article 650: Pipe Organs

NEC Article 650 provides electrical safety requirements for the circuits and equipment used in pipe organ installations. These systems include control circuits for keyboards and pipe-sounding apparatus, integrating traditional organ components with modern electronic enhancements.


Scope of Article 650

This article applies to:

  • Electrical circuits for controlling pipe organ keyboards and sounding apparatus, such as pipes.
  • Equipment associated with digital or analog sampled sound production within organ systems.

Informational Note: Pipe organs are typically large, built as part of a structure, and may combine acoustic and electronic technologies.


Key Requirements for Pipe Organ Systems

  1. Other Applicable Articles
    • Electronic Equipment: Audio processing and amplification systems must comply with Article 640.
    • Optical Fiber Cables: Installations must follow Parts I and V of Article 770.
  2. Source of Energy
    • Pipe organ systems use DC power from listed power supplies with a maximum output of 30 volts.
    • Class 1 power-limited supplies are common in these applications.
  3. Grounding or Double Insulation
    • DC power supplies must either:
      • Be double insulated.
      • Have a metallic case bonded to the input equipment grounding conductor.
  4. Conductor Specifications
    • Minimum conductor sizes:
      • 28 AWG for electronic signal circuits.
      • 26 AWG for electromagnetic valve supply.
      • 14 AWG for common-return conductors in electromagnetic supply circuits.
    • Conductors must have thermoplastic or thermosetting insulation.
    • Cables must be resistant to flame spread if not enclosed in a metal raceway.
  5. Installation Practices
    • Cables can be fastened directly to the organ structure without insulating supports.
    • Splices need not be enclosed in boxes.
    • Abandoned cables must be tagged for identification.
  6. Overcurrent Protection
    • Conductors 20 AWG through 28 AWG require overcurrent devices rated at no more than 6 amperes.
    • Common-return conductors do not need overcurrent protection.
  7. Protection from Accidental Contact
    • Wiring for the pipe organ sounding apparatus must be inside a lockable enclosure (e.g., an organ chamber).
    • Exterior pipes may form part of this enclosure.

Applications

NEC Article 650 is essential for ensuring safety in:

  • Churches and Religious Spaces: Large pipe organ installations.
  • Concert Halls: Traditional and electronic organ systems.
  • Cultural Preservation: Restorations of historical pipe organs.

Conclusion