Understanding NEC Article 724: Class 1 Power-Limited Circuits and Class 1 Remote-Control and Signaling Circuits

NEC Article 724 outlines the requirements for Class 1 power-limited circuits and Class 1 remote-control and signaling circuits. These systems are essential for operating motor controllers, lighting control systems, security devices, and other low-voltage circuits in buildings.


Scope of Article 724

This article applies to:

  • Class 1 circuits, including power-limited circuits for remote control and signaling.
  • Circuits extending from power supplies to connected equipment, excluding integral device wiring.

Informational Notes:

  • Systems like nurse call circuits, access control, and some low-voltage lighting controls may fall under Article 724.
  • Wiring for information technology equipment rooms constructed per NFPA 75 is governed by Article 645, not Article 724.

Key Requirements for Class 1 Circuits

  1. Voltage and Power Limitations (724.40)
    • Circuits are limited to 30 volts and 1000 volt-amperes (VA).
    • Transformers supplying these circuits must comply with Article 450.
  2. Circuit Protection (724.43)
    • Overcurrent devices must match conductor ampacity.
    • Specific limits apply:
      • 7 amperes for 18 AWG conductors.
      • 10 amperes for 16 AWG conductors.
  3. Wiring Methods (724.46–724.48)
    • Circuits must comply with general wiring methods in Chapter 3.
    • Cables must be installed neatly and securely to avoid damage.
    • Power-supply conductors and Class 1 circuits may share raceways if functionally associated.

Fire Safety and Environment

  1. Fire Spread Prevention (724.3(B))
    • Installations must limit fire spread or smoke production.
    • Plenum-rated cables are required for ducts or air-handling spaces.
  2. Hazardous Locations (724.3(D))
    • Class 1 circuits are prohibited in hazardous locations unless permitted by specific articles.

Special Considerations

  1. Identification and Access (724.30, 724.21)
    • Circuits must be labeled to prevent interference during testing or servicing.
    • Wiring must not block access to panels or equipment.
  2. Circuit Integrity (CI) Cables (724.3(G))
    • Vertical installations of CI cables must comply with fire-rated support and separation methods.
  3. Aerial Circuits (724.52)
    • Circuits extending between buildings must follow Article 225 standards for aerial installations.

Applications

Article 724 supports systems such as:

  • Motor Controls: Elevators, conveyors, and shunt-trip circuits for breakers.
  • Security Systems: Access controls and alarms.
  • Lighting Controls: Dimming systems and remote switches.
  • Low-Voltage Systems: Specialty control circuits for building automation.

Conclusion

NEC Article 724 ensures the safe installation of Class 1 circuits by addressing voltage limits, overcurrent protection, fire safety, and wiring methods. These standards protect personnel and property while supporting critical control and signaling functions.