Understanding NEC Article 724: Class 1 Power-Limited Circuits and Class 1 Remote-Control and Signaling Circuits
NEC Article 724 outlines the requirements for Class 1 power-limited circuits and Class 1 remote-control and signaling circuits. These systems are essential for operating motor controllers, lighting control systems, security devices, and other low-voltage circuits in buildings.
Scope of Article 724
This article applies to:
- Class 1 circuits, including power-limited circuits for remote control and signaling.
- Circuits extending from power supplies to connected equipment, excluding integral device wiring.
Informational Notes:
- Systems like nurse call circuits, access control, and some low-voltage lighting controls may fall under Article 724.
- Wiring for information technology equipment rooms constructed per NFPA 75 is governed by Article 645, not Article 724.
Key Requirements for Class 1 Circuits
- Voltage and Power Limitations (724.40)
- Circuits are limited to 30 volts and 1000 volt-amperes (VA).
- Transformers supplying these circuits must comply with Article 450.
- Circuit Protection (724.43)
- Overcurrent devices must match conductor ampacity.
- Specific limits apply:
- 7 amperes for 18 AWG conductors.
- 10 amperes for 16 AWG conductors.
- Wiring Methods (724.46–724.48)
- Circuits must comply with general wiring methods in Chapter 3.
- Cables must be installed neatly and securely to avoid damage.
- Power-supply conductors and Class 1 circuits may share raceways if functionally associated.
Fire Safety and Environment
- Fire Spread Prevention (724.3(B))
- Installations must limit fire spread or smoke production.
- Plenum-rated cables are required for ducts or air-handling spaces.
- Hazardous Locations (724.3(D))
- Class 1 circuits are prohibited in hazardous locations unless permitted by specific articles.
Special Considerations
- Identification and Access (724.30, 724.21)
- Circuits must be labeled to prevent interference during testing or servicing.
- Wiring must not block access to panels or equipment.
- Circuit Integrity (CI) Cables (724.3(G))
- Vertical installations of CI cables must comply with fire-rated support and separation methods.
- Aerial Circuits (724.52)
- Circuits extending between buildings must follow Article 225 standards for aerial installations.
Applications
Article 724 supports systems such as:
- Motor Controls: Elevators, conveyors, and shunt-trip circuits for breakers.
- Security Systems: Access controls and alarms.
- Lighting Controls: Dimming systems and remote switches.
- Low-Voltage Systems: Specialty control circuits for building automation.
Conclusion
NEC Article 724 ensures the safe installation of Class 1 circuits by addressing voltage limits, overcurrent protection, fire safety, and wiring methods. These standards protect personnel and property while supporting critical control and signaling functions.