Understanding NEC Article 810: Antenna Systems

NEC Article 810 outlines the requirements for the installation, grounding, and protection of antenna systems used in radio, television, and other communication setups. This article ensures safety and system integrity for receiving and transmitting equipment in residential, commercial, and industrial settings.


Scope of Article 810

This article applies to:

  • Antenna systems for receiving and transmitting radio and television signals.
  • Types of antennas covered include wire-strung, multi-element, vertical rods, flat, or parabolic antennas.
  • Connecting cables from antennas to equipment.

Exclusions: Systems used to couple carrier current to power line conductors are not covered.


Key Requirements for Antenna Systems

  1. Material and Support (810.11–810.12)
    • Antennas and lead-in conductors must be corrosion-resistant, made of materials like copper, bronze, or aluminum.
    • Supports must securely hold antennas to withstand wind and ice loading. Antennas must not attach to electric service masts or power poles​.
  2. Clearance and Avoidance of Contact (810.13)
    • Antennas must maintain a safe distance from power conductors to prevent accidental contact.
    • Minimum clearance of 2 feet is required for circuits under 250 volts; greater clearances apply for higher voltages​.
  3. Grounding and Bonding (810.15, 810.21)
    • Metal masts and supports for antennas must be grounded per the requirements of 810.21.
    • Grounding conductors must be run in a straight line and be no smaller than 10 AWG copper or equivalent.
    • Connections must be made to grounding electrodes as outlined in 250.52​.
  4. Antenna Discharge Units (810.20)
    • Each lead-in conductor from an outdoor antenna must have a discharge unit to protect against lightning surges.
    • Discharge units must be located near the point of entry to the building and grounded as per 810.21​.

Specific Guidelines for Transmitting Stations

  1. Conductor Sizing (810.52)
    • Antenna conductors must meet minimum size requirements based on span length and material.
    • Lead-in conductors must match or exceed the size of the antenna conductors​.
  2. Indoor Installations (810.18, 810.70)
    • Lead-in conductors inside buildings must maintain a 4-inch separation from other conductors unless separated by a non-conductive barrier.
    • Transmitter access doors must include interlocks that disconnect high-voltage circuits when opened​.

Applications of Article 810

  • Residential Settings: Television and amateur radio antennas.
  • Commercial Buildings: Communication and broadcasting setups.
  • Industrial Installations: Specialized radio and data transmission systems.

Conclusion

NEC Article 810 ensures the safe installation of antenna systems by addressing grounding, conductor sizing, clearances, and protection against lightning surges. Following these standards enhances both the safety and performance of communication systems.