What you’ll learn
After this post, you will be able to explain what a current transformer does, why its secondary must never be left open-circuited while the primary is energised, and what to do instead.
What a current transformer is for
A current transformer (CT) is an instrument transformer: it steps a circuit’s current down to a lower value that ordinary meters, ammeters, wattmeters, and protective relays can safely use. The primary has only a few turns — often it is just the power conductor itself passing through the core — while the secondary has many turns wound around it, so a high primary current becomes a small, measurable secondary current. A CT rated 200:5, for example, turns 200 A in the circuit into 5 A through the meter. Together with the potential transformer (PT), which steps voltage down the same way, the CT lets ordinary instruments watch high-voltage, high-current circuits safely, at low values.
The rule, stated plainly
A current transformer should always be short-circuited when it is not connected to an external load. Never leave a CT secondary open-circuited while the primary is carrying current. The handbook calls this the chapter’s most important safety point, and it is a hazard, not just a measurement error.
Why an open CT is dangerous
In normal operation the CT is a balanced machine. The primary current is fixed by the circuit it measures — the CT does not control it. The secondary current flowing through the meter (the burden) creates a magnetic flux that almost exactly opposes the primary’s flux, so the net flux in the core stays small and the magnetising current stays low. That is what the CT’s magnetic circuit is designed for: low magnetising current under load.
Open the secondary and that balance collapses. With no secondary current there is no opposing flux, so the whole primary current becomes magnetising current. The core flux surges, the core saturates, and the transformer starts acting as a step-up transformer: the many-turn secondary now has a huge changing flux cutting it, and it induces an excessively high voltage across the open terminals. That voltage is high enough to shock anyone touching the terminals, to arc across them, to break down the insulation, and to overheat and damage the core. The handbook’s words are blunt: an unloaded CT acts as a step-up transformer inducing excessively high secondary voltage.
The worked example: a 200:5 CT, open-circuited
Take a CT rated 200:5, measuring a feeder carrying 200 A. Step 1 — normal: the secondary delivers 5 A to the ammeter, the secondary flux cancels the primary flux, the core flux stays small, and the secondary terminals sit at a few volts. Step 2 — someone disconnects the ammeter without shorting the CT first: the secondary circuit opens, the opposing flux disappears, and the full 200 A of primary current becomes magnetising current. Step 3 — the surge: the core flux builds sharply, the core saturates, and the many-turn secondary induces a dangerously high voltage across the open terminals — high enough to shock, to arc, and to damage the insulation. Step 4 — the fix that should have happened first: before the meter was touched, a shorting link across the CT secondary terminals would have kept a closed path for the secondary current, keeping the flux balanced and the terminals safe. (The handbook states the rule and the mechanism but gives no numeric open-circuit voltage for this example; the numbers above are the CT’s own ratio, and the voltage is described qualitatively, as the handbook describes it — excessively high.)
The opposite rule for the potential transformer
Do not mix the two instrument transformers up: the PT has the opposite rule. A PT steps voltage down, and its secondary must never be short-circuited — a shorted PT secondary draws an enormous current, like shorting any voltage source. So the pair of rules is: CT secondary — never open, always short it when unloaded; PT secondary — never short, always leave it open or properly loaded. One rule per transformer, and they are opposites.
Common mistakes
- “An open CT just stops measuring.” It does not — it becomes a hazard. The open secondary can develop dangerously high voltage, arc, and damage the CT’s insulation and core.
- “The CT only carries a few amps, so it is safe.” The secondary carries a few amps, but the primary carries the full circuit current — 200 A in the example — and when the secondary opens, all of it becomes magnetising current.
- “I’ll short the CT after I remove the meter.” Too late — short it first. The shorting link goes across the secondary terminals before the meter is disconnected, and it stays on until the meter (or another load) is reconnected.
- “CT and PT rules are the same.” They are opposites: a CT secondary must never be left open; a PT secondary must never be shorted.
- “The danger is only a wrong reading.” It is not — it is shock, arcing, insulation breakdown, and core damage. The handbook calls it the chapter’s most important safety point for a reason.
- “The CT controls the primary current.” It does not — the primary current is set by the circuit being measured. The CT only scales it down for the meter.
- “More secondary turns means a safer CT.” The many-turn secondary is exactly what makes the open-circuit voltage so high — it is a step-up winding when the flux surges.
Summary
A current transformer steps a high circuit current down to a few amps a meter can use — a 200:5 CT turns 200 A into 5 A. In normal use the secondary current cancels the primary flux, keeping the core flux small. Open the secondary and that balance is gone: the whole primary current becomes magnetising current, the flux surges, and the many-turn secondary induces an excessively high voltage across the open terminals. So the rule is absolute: a CT secondary is always short-circuited when it is not connected to a load — short it before the meter comes off, and never energise the primary with the secondary open. And remember the opposite rule for the PT: its secondary must never be shorted.
Quick-check questions
- What does a current transformer do?
- What is the safety rule for a CT secondary?
- Why does an open-circuited CT develop a dangerously high secondary voltage?
- What is the rule for a PT secondary, and why is it the opposite?
- When should the shorting link be applied to a CT?
Answers: 1. It steps a circuit’s current down to a lower value that meters, ammeters, wattmeters, and protective relays can safely use. 2. It must always be short-circuited when not connected to an external load — never leave it open while the primary is energised. 3. With no secondary current there is no opposing flux, so the whole primary current becomes magnetising current, the flux surges, and the many-turn secondary acts as a step-up winding inducing excessively high voltage. 4. A PT secondary must never be short-circuited — a shorted PT draws an enormous current, like shorting any voltage source. The two rules are opposites. 5. Before the meter (or other load) is disconnected — and it stays on until a load is reconnected.
Based on DOE-HDBK-1011/92, Electrical Science, Module 13, paraphrased for study.
Top 10 Scorers
| Pos. | Name | Score | Duration |
|---|---|---|---|
| There is no data yet |
What is a current transformer (CT) for?
It steps a circuit's current down to a lower value that meters, ammeters, wattmeters, and protective relays can safely use
Question Explanation:
An instrument current transformer steps circuit current down to a lower value for the same instruments and relays — ammeters, voltmeters, wattmeters, and protective relays — so they can work on high-current circuits safely.
How is a CT built?
The secondary has many turns around a primary of only a few turns, so high currents can be measured
Question Explanation:
A CT's secondary has many turns around a primary of only a few turns, so high currents can be measured — the many-turn secondary steps the current down to a few amps.
What is the safety rule for a CT secondary?
It should always be short-circuited when not connected to an external load — never leave it open while the primary is energised
Question Explanation:
A CT should always be short-circuited when not connected to an external load. This is the chapter's most important safety point — an open-circuited CT secondary is a high-voltage hazard, not just a measurement error.
Why does the core flux stay small in normal CT operation?
The secondary current through the meter creates a flux that almost exactly opposes the primary's flux
Question Explanation:
In normal operation the secondary current flowing through the meter creates a magnetic flux that almost exactly opposes the primary's flux, so the net flux in the core stays small and the magnetising current stays low.
What happens inside a CT when its secondary is opened while the primary carries current?
With no opposing flux, the whole primary current becomes magnetising current, the flux surges, and the many-turn secondary induces excessively high voltage
Question Explanation:
Open the secondary and the balance collapses: with no secondary current there is no opposing flux, so the whole primary current becomes magnetising current, flux builds, and the CT acts as a step-up transformer inducing excessively high secondary voltage.
What dangers does an open-circuited CT present?
Shock, arcing across the terminals, insulation breakdown, and core damage from overheating
Question Explanation:
The excessively high secondary voltage is high enough to shock anyone touching the terminals, to arc across them, to break down the insulation, and to overheat and damage the core. It is a hazard, not just a measurement error.
A CT rated 200:5 measures a feeder carrying 200 A. What is the normal secondary current?
5 A
Question Explanation:
A CT rated 200:5 turns 200 A in the circuit into 5 A through the meter — the ratio 200/5 = 40:1.
When should the shorting link be applied to a CT secondary?
Before the meter or other load is disconnected, and it stays on until a load is reconnected
Question Explanation:
The shorting link goes across the secondary terminals before the meter is disconnected — shorting it after the meter is removed is too late — the hazard exists from the moment the secondary opens.
What is the rule for a potential transformer (PT) secondary, and how does it compare with the CT rule?
A PT secondary must never be short-circuited — the opposite of the CT rule, because a shorted PT draws an enormous current
Question Explanation:
A PT steps voltage down, and its secondary must never be short-circuited — a shorted PT secondary draws an enormous current, like shorting any voltage source. So: CT secondary — never open; PT secondary — never short.
Why do PTs and CTs exist at all?
So ordinary meters and relays can safely watch high-voltage and high-current circuits, at low values
Question Explanation:
PTs and CTs exist precisely so meters and relays can work on high-voltage and high-current circuits safely, at low values — stepping voltage and current down to what ordinary instruments can handle.