Illustration of two transformer tests side by side: one with the output wires shorted, one with them open
⏱ 6 min read🎬 Video · 7:57📖 DOE Module 13 · Transformer Tests
Illustration of two transformer tests side by side: one with the output wires shorted, one with them open

What you’ll learn

After this post, you will be able to name the two kinds of loss in a transformer, explain how the open-circuit test measures one and the short-circuit test measures the other, and calculate a transformer’s efficiency from the two test results.

A transformer is not 100% efficient — but it is close

A transformer trades voltage for current and loses almost nothing in the process — a good one runs at 98% efficiency or better. The small power it does lose goes to two places, and each place has its own test to measure it. That is the neat part: you never have to guess at the losses, because each test isolates exactly one of them.

Loss one: copper loss — the windings’ resistance

Copper loss is the ordinary I²R loss in the primary and secondary windings:

Copper loss = I_P²R_P + I_S²R_S (watts)

It depends on the load current, so it is zero at no load and grows with the square of the current. You measure it with the short-circuit test: short the secondary, apply just enough primary voltage to drive full-load current, and measure the power in. With the secondary shorted, the core flux is tiny, so almost all the power you measure is winding resistance — copper loss.

Loss two: core loss — magnetising the iron

Core loss is the power spent magnetising the core, and it has two causes: hysteresis loss — the energy lost reversing the core’s magnetic field as the magnetising AC rises, falls, and reverses — and eddy-current loss — currents induced circulating in the core itself. Core loss depends on the voltage and frequency, not on the load, so it is present even at no load. You measure it with the open-circuit test: leave the secondary open, apply full rated voltage to the primary, and measure the power in. With no load current, there is no copper loss to speak of — the power you measure is the core loss.

No-load current: small, but not zero

With the secondary open-circuited, the primary still draws a very small current — the no-load current, or exciting current (I_E). It produces the flux and supplies the hysteresis and eddy-current losses. It has two components: the magnetising current (I_m), lagging the applied voltage by 90°, and the core-loss current (I_H), in phase with the applied voltage. I_H is very small compared with I_m, so I_m is approximately equal to I_E. A worked example from the handbook: a 120/440 V, 5 kVA transformer, secondary open, primary drawing 0.2 A at PF 0.3. Then I_E = 0.2 A; I_H = 0.2 × 0.3 = 0.06 A; θ = arccos 0.3 = 72.5°, and I_m = 0.2 × sin 72.5° ≈ 0.2 × 0.95 = 0.19 A. The magnetising current does almost all of the work of making the flux; the core-loss current is the small in-phase part that pays for the losses.

The worked examples: finding the losses, then the efficiency

Example 1 — copper loss and secondary resistance: a 5:1 step-down transformer, full-load secondary current 20 A, short-circuit (copper-loss) test reading 100 W, primary resistance 0.3 Ω. First the primary current: I_P = 20/5 = 4 A. Then the secondary resistance: R_S = (100 − 0.3 × 4²) / 20² = (100 − 4.8) / 400 = 0.24 Ω. And the secondary’s share of the copper loss: 20² × 0.24 = 96 W. (The remaining 4 W is the primary’s 4² × 0.3 = 4.8 W, rounding to the test’s 100 W total.)

Example 2 — efficiency from the two tests: a 10 kVA transformer, copper loss 100 W (short-circuit test), core loss 70 W (open-circuit test), load power factor 0.90. Output power = 10,000 × 0.90 = 9,000 W. Efficiency = 9,000 / (9,000 + 100 + 70) × 100 = 98.2%. That is a typical transformer efficiency — and it shows why the two tests matter: add the two measured losses to the output, and you have the efficiency without ever loading the transformer to full power on a test bench.

The general forms: Efficiency = (Power output / Power input) × 100 = (P_S / P_P) × 100, or equivalently Power output / (Power output + Copper loss + Core loss) × 100, or with the load power factor, (V_S·I_S·PF) / ((V_S·I_S·PF) + Copper loss + Core loss) × 100.

Common mistakes

  • “Core loss grows with load.” It does not — core loss depends on voltage and frequency, so it is there even at no load. Copper loss is the one that grows with load, as the square of the current.
  • “The open-circuit test measures copper loss.” It measures core loss. With the secondary open there is no load current, so the power in is the power spent magnetising the core.
  • “The short-circuit test measures core loss.” It measures copper loss. With the secondary shorted, the flux is tiny, so the power in is almost all winding resistance.
  • “Efficiency is output divided by input, and you have to measure both.” You can also get it from output plus the two test losses: output / (output + copper + core) × 100. The 10 kVA example gives 98.2% that way.
  • “No-load current is zero because nothing is connected.” It is small but not zero — about 0.2 A in the handbook’s example — and it is the current that makes the flux and pays the core losses.
  • “Hysteresis and eddy-current losses are the same thing.” They are the two different causes of core loss: hysteresis is the energy of reversing the core’s magnetic field; eddy-current loss is currents circulating in the core itself.
  • “A transformer with 98% efficiency wastes almost nothing, so losses don’t matter.” At 10 kVA, 1.8% is 170 W of heat — and it is there all the time the transformer is energised, loaded or not, because core loss never switches off.

Summary

A transformer loses power in exactly two places: the windings (copper loss, I²R, growing with load) and the core (hysteresis plus eddy-current loss, present whenever the transformer is energised). The short-circuit test isolates the copper loss; the open-circuit test isolates the core loss. Add the two measured losses to the output power and you have the efficiency — 98.2% for the handbook’s 10 kVA example. And the no-load current, small as it is, is the current that makes the flux and pays the core losses.

Quick-check questions

  1. What are the two kinds of loss in a transformer?
  2. Which test measures copper loss, and how does it work?
  3. Which test measures core loss, and how does it work?
  4. A 10 kVA transformer has 100 W copper loss, 70 W core loss, and a 0.90 load power factor. What is its efficiency?
  5. Why is the no-load current not zero?

Answers: 1. Copper loss (I²R in the windings) and core loss (hysteresis plus eddy-current loss in the iron). 2. The short-circuit test: short the secondary, apply enough primary voltage for full-load current, and measure the power in — almost all of it is winding resistance. 3. The open-circuit test: leave the secondary open, apply full rated voltage, and measure the power in — with no load current, it is the core loss. 4. Output = 10,000 × 0.90 = 9,000 W; efficiency = 9,000 / (9,000 + 100 + 70) × 100 = 98.2%. 5. Because the primary must still draw the exciting current that produces the flux and supplies the core losses — about 0.2 A in the handbook’s example.

Based on DOE-HDBK-1011/92, Electrical Science, Module 13, paraphrased for study.

Report a question

You cannot submit an empty report. Please add some details.
0%
Illustration of two transformer tests side by side: one with the output wires shorted, one with them open

Two Tests That Reveal a Transformer’s Hidden Losses

This quiz consists of 10 carefully selected questions covering Transformer Tests, which provides essential guidelines for understanding transformer losses and how to measure them. This section focuses on copper loss and core loss, the open-circuit and short-circuit tests, and calculating transformer efficiency.

The randomly generated questions ensure a thorough assessment of your understanding, reinforcing key principles related to Transformer Tests. Some topics may reappear in different contexts to strengthen comprehension and application.

Your feedback is invaluable! If you notice any discrepancies or have suggestions for improvement, please report them. Your insights help maintain the accuracy and effectiveness of this learning tool.

Output over output plus both losses.

1 / 10

A 10 kVA transformer has 100 W copper loss, 70 W core loss, and a 0.90 load power factor. What is its efficiency at full load?

Two test readings give the efficiency directly.

Small, but it makes the flux.

2 / 10

What is the no-load current (exciting current), and why is it not zero?

Nothing connected, but the core still needs magnetising.

Shorted secondary, full-load current.

3 / 10

How does the short-circuit test work, and what does it measure?

Shorted secondary means tiny flux, so the reading is copper loss.

Subtract the primary's share first.

4 / 10

A 5:1 step-down transformer has a full-load secondary current of 20 A, a short-circuit test reading of 100 W, and a primary resistance of 0.3 Ω. What is the secondary resistance?

The test reading covers both windings — split it.

Open secondary, full voltage.

5 / 10

How does the open-circuit test work, and what does it measure?

Open secondary means no load current, so the reading is core loss.

Hysteresis and eddy currents.

6 / 10

What causes core loss?

Core loss is there whenever the transformer is energised.

I²R, grows with load.

7 / 10

What is copper loss, and how does it change with load?

Double the current, quadruple the copper loss.

Windings and core.

8 / 10

What are the two kinds of loss in a transformer?

Each loss has its own test.

I_H is in phase, I_m lags 90°.

9 / 10

In the handbook's no-load example, a 120/440 V, 5 kVA transformer draws 0.2 A at PF 0.3 with the secondary open. What are I_H and I_m?

The core-loss part is the small in-phase part.

One lags 90°, one is in phase.

10 / 10

What are the two components of the no-load current?

The magnetising part does almost all of the work.

Your score is

0%

Exit

Rate & Review

Thank you for taking the time to leave us a review! Your feedback is greatly appreciated and helps us improve our services.

Top 10 Scorers

Pos.NameScoreDuration
There is no data yet

What are the two kinds of loss in a transformer?

1/10

What is copper loss, and how does it change with load?

2/10

What causes core loss?

3/10

How does the short-circuit test work, and what does it measure?

4/10

How does the open-circuit test work, and what does it measure?

5/10

A 5:1 step-down transformer has a full-load secondary current of 20 A, a short-circuit test reading of 100 W, and a primary resistance of 0.3 Ω. What is the secondary resistance?

6/10

A 10 kVA transformer has 100 W copper loss, 70 W core loss, and a 0.90 load power factor. What is its efficiency at full load?

7/10

What is the no-load current (exciting current), and why is it not zero?

8/10

What are the two components of the no-load current?

9/10

In the handbook's no-load example, a 120/440 V, 5 kVA transformer draws 0.2 A at PF 0.3 with the secondary open. What are I_H and I_m?

10/10