What you’ll learn
After this post, you will be able to explain the difference between delta and wye transformer connections, work out line and phase voltage and current for each of the four bank combinations, and explain where the √3 (about 1.73) comes from.
A quick distinction first
Volume 3 already covered wye vs. delta as a way to wire three-phase loads. This post is the transformer side of the same idea: when three single-phase transformer windings are connected into a three-phase bank, the way you connect them — delta or wye — decides the line and phase voltages and currents on each side of the bank. Same √3, different job.
Delta: a closed loop
In a delta (Δ) connection the three phases are connected in series to form a closed loop — each winding joins the next, end to end, with the three line wires taken from the three corners. Because each winding sits directly across two lines, the phase voltage equals the line voltage:
V_L = V_φ (delta)
But the line current is bigger than the phase current, because each line wire carries current from two windings at once. The two phase currents are 120° apart, so they add vectorially, not arithmetically — and the vector sum works out to √3 times the phase current:
I_L = √3 · I_φ (delta)
Wye: a common neutral
In a wye (Y) connection the three common ends of the windings are joined at one terminal marked “N” — the neutral — and the other three ends go to the three-phase lines. Here it is the other way round: each line wire carries only its own winding’s current, so line current equals phase current:
I_L = I_φ (wye)
But the line voltage is bigger than the phase voltage, because the voltage between two lines spans two windings 120° apart, and again the vector addition gives √3:
V_L = √3 · V_φ (wye)
That is where √3 (about 1.73) comes from in every three-phase calculation: two quantities 120° apart add vectorially to √3 times one of them, never to twice it.
Four bank combinations
A three-phase transformer bank can connect its primary and its secondary each as delta or wye, giving four combinations: Δ–Δ, Δ–Y, Y–Δ, and Y–Y. The handbook’s Table 1 lists the line and phase voltage and current for each, in terms of the applied line voltage V, the line current I, and the turns ratio a (= N1/N2). The pattern is simple once you know the two rules above: the delta side takes V_L = V_φ and I_L = √3·I_φ, the wye side takes V_L = √3·V_φ and I_L = I_φ, and the secondary values are scaled by the turns ratio, with √3 factors appearing on the delta side of a mixed bank.
The worked examples: 440 V and 10.4 A from the handbook
Example 1 — primary winding voltage, 440 V line applied:
- Δ–Δ: 440 V
- Y–Y: 440 / 1.73 = 254.3 V
- Y–Δ: 254.3 V
- Δ–Y: 440 V
Read it this way: whenever the primary is delta, each winding sees the full 440 V line voltage; whenever the primary is wye, each winding sees only 440/√3 = 254.3 V — the line voltage split across two windings.
Example 2 — primary phase current, 10.4 A line current:
- Δ–Δ: 10.4 / 1.73 = 6 A
- Y–Y: 10.4 A
- Y–Δ: 10.4 A
- Δ–Y: 6 A
Mirror image: whenever the primary is delta, each winding carries only 10.4/√3 = 6 A; whenever it is wye, each winding carries the full 10.4 A line current.
Example 3 — secondary currents, 20 A primary line current and a turns ratio of 4:1:
- Δ–Δ: line 80 A, phase 46.2 A
- Y–Y: line 80 A, phase 80 A
- Y–Δ: line 138.4 A, phase 80 A
- Δ–Y: line 46.2 A, phase 46.2 A
The turns ratio steps the current up four times (20 A → 80 A line in the Δ–Δ and Y–Y banks), and the √3 factor then appears on whichever side is delta: in Y–Δ the secondary line current is 80 × √3 = 138.4 A, while in Δ–Y the primary line current is already √3-divided, so the secondary line current comes out at 80/√3 = 46.2 A.
Common mistakes
- “Line voltage is always √3 times phase voltage.” Only in wye. In delta, line voltage equals phase voltage — it is the line current that is √3 times the phase current.
- “Line current is always √3 times phase current.” Only in delta. In wye, line current equals phase current — it is the line voltage that is √3 times the phase voltage.
- “Two windings at 120° add to twice one winding.” They add vectorially, not arithmetically: the sum is √3 (about 1.73) times one winding, never 2 times.
- “Delta and wye are just two names for the same thing.” They give different line and phase values, and only wye gives you a neutral terminal — which is why wye is used when single-phase loads or a grounded neutral are needed.
- “The turns ratio alone sets the secondary line voltage.” It sets the phase voltage; the bank connection then decides whether the line voltage equals it (delta) or is √3 times it (wye).
- “√3 is an approximation you can round away.” √3 ≈ 1.73 is the exact vector result of 120° separation. Rounding it to 1.7 or 2 changes the answers — 440/1.73 = 254.3 V, not 258.8 V or 220 V.
- “This post repeats the Vol 3 Wye vs. Delta post.” It does not — Vol 3 covered wiring three-phase loads; this post covers transformer banks and their line/phase values through all four Δ/Y combinations.
Summary
Delta connects the three windings in a closed loop: V_L = V_φ and I_L = √3·I_φ. Wye joins three ends at a neutral: V_L = √3·V_φ and I_L = I_φ. The √3 comes from adding two quantities 120° apart vectorially. A bank can be Δ–Δ, Δ–Y, Y–Δ, or Y–Y; the turns ratio scales the secondary values, and √3 appears on whichever side is delta. With 440 V applied, a delta primary winding sees 440 V and a wye one sees 254.3 V; with 10.4 A on the line, a delta primary winding carries 6 A and a wye one carries 10.4 A.
Quick-check questions
- In a delta connection, how do line voltage and line current relate to phase voltage and phase current?
- In a wye connection, how do line voltage and line current relate to phase voltage and phase current?
- Where does √3 come from in three-phase calculations?
- A 440 V line is applied to a Y–Y bank. What is the primary winding (phase) voltage?
- A 10.4 A line current feeds a Δ–Δ bank. What is the primary phase current?
Answers: 1. V_L = V_φ and I_L = √3·I_φ. 2. V_L = √3·V_φ and I_L = I_φ. 3. Two quantities 120° apart add vectorially to √3 (about 1.73) times one of them. 4. 440/1.73 = 254.3 V. 5. 10.4/1.73 = 6 A.
Based on DOE-HDBK-1011/92, Electrical Science, Module 13, paraphrased for study.
Top 10 Scorers
| Pos. | Name | Score | Duration |
|---|---|---|---|
| There is no data yet |
How are the three windings connected in a delta connection?
All three phases connected in series to form a closed loop, with the line wires taken from the three corners
Question Explanation:
In a delta connection all three phases are connected in series to form a closed loop, and the three line wires are taken from the three corners of the loop.
How are the three windings connected in a wye connection?
Three common ends joined at a common terminal marked "N" (neutral); the other three ends go to the three-phase lines
Question Explanation:
In a wye connection the three common ends are joined at a common terminal marked "N" (neutral), and the other three ends go to the three-phase lines.
In a delta connection, what are the line voltage and line current in terms of phase values?
V_L = V_φ and I_L = √3 · I_φ
Question Explanation:
In delta each winding sits directly across two lines, so V_L = V_φ; each line wire carries current from two windings 120° apart, so I_L = √3·I_φ.
In a wye connection, what are the line voltage and line current in terms of phase values?
V_L = √3 · V_φ and I_L = I_φ
Question Explanation:
In wye each line wire carries only its own winding's current, so I_L = I_φ; the voltage between two lines spans two windings 120° apart, so V_L = √3·V_φ.
Where does √3 (about 1.73) come from in three-phase calculations?
Two quantities 120° apart add vectorially to √3 times one of them
Question Explanation:
The √3 comes from adding two quantities 120° apart vectorially: the sum is √3 times one of them — and that is why the √3 shows up in the line values.
A 440 V line is applied to a transformer bank. What is the primary winding voltage for a Δ–Δ bank and for a Y–Y bank?
Δ–Δ: 440 V; Y–Y: 254.3 V
Question Explanation:
With 440 V applied: Δ–Δ primary phase voltage is 440 V (each winding sees the full line voltage), while Y–Y is 440/1.73 = 254.3 V (the line voltage is split across two windings).
A 10.4 A line current feeds a transformer bank. What is the primary phase current for a Δ–Δ bank and for a Y–Y bank?
Δ–Δ: 6 A; Y–Y: 10.4 A
Question Explanation:
With 10.4 A on the line: Δ–Δ primary phase current is 10.4/1.73 = 6 A (each line wire's current splits between two windings), while Y–Y is 10.4 A (each winding carries the full line current).
What are the four possible three-phase transformer bank combinations?
Δ–Δ, Δ–Y, Y–Δ, and Y–Y
Question Explanation:
A bank can connect its primary and its secondary each as delta or wye, giving four combinations: Δ–Δ, Δ–Y, Y–Δ, and Y–Y.
With 20 A primary line current and a turns ratio of 4:1, what is the secondary line current for a Y–Δ bank?
138.4 A
Question Explanation:
The turns ratio steps the current up four times (20 A → 80 A), and the delta secondary makes the line current √3 times the phase current: 80 × √3 = 138.4 A.
How does this post differ from the Volume 3 post "Wye vs. Delta: Two Ways to Wire Three Phases"?
Volume 3 covered wiring three-phase loads; this post covers transformer banks and their line/phase values through all four Δ/Y combinations
Question Explanation:
Volume 3 covered wye vs. delta as a way to wire three-phase loads. This post is the transformer side: how the bank connection decides line and phase voltages and currents for Δ–Δ, Δ–Y, Y–Δ, and Y–Y.
- Tags:
- VOL4
People Who like this post