What you’ll learn
After this post, you will be able to explain mutual induction, calculate a transformer’s voltage and current from its turns ratio, and use the square of the turns ratio to work out the impedance a load presents to the source.
Two coils, one changing field
A transformer is two coils of wire sharing one changing magnetic field. The coil fed from an AC source is the primary winding; the coil delivering AC to the load is the secondary winding. There is no electrical connection between them — the energy crosses by magnetic induction. The AC in the primary makes a magnetic field that expands and contracts; when those flux lines cut the windings of the nearby secondary coil, a voltage is induced in it. That is mutual induction, and the induced EMF depends on how the two coils sit relative to each other.
In a real transformer the windings sit close together on the same core, because separating them wastes efficiency: flux that passes through one coil but not the other is magnetic leakage, and a longer magnetic circuit means more leakage. In the handbook’s diagram the primary and secondary are drawn on separate legs just for clarity; in practice half of each winding is on each leg, with insulation between windings and core. The alternating primary voltage magnetises the core first one way and then the other, and the alternating flux linking both windings induces the same volts-per-turn, in the same direction, in each. The voltage induced in the primary opposes the applied voltage and is called the counter-electromotive force (CEMF).
The turns ratio sets the voltage
The one number that runs the whole machine is the turns ratio:
TR = N_P / N_S
where N_P is the number of turns on the primary and N_S is the number on the secondary. Winding voltage is directly proportional to turns, so the voltage ratio equals the turns ratio:
V_P / V_S = N_P / N_S
A voltage ratio of 1:5 means 5 V on the secondary for every 1 V on the primary — a step-up transformer, because the secondary voltage is higher. A ratio of 5:1 means 1 V on the secondary for every 5 V on the primary — a step-down transformer.
The current goes the other way
Current is inversely proportional to voltage, and therefore inversely related through the turns ratio:
V_P / V_S = I_S / I_P, and N_P / N_S = I_S / I_P
A step-up in voltage is a proportional step-down in current, and vice versa. The transformer does not create power — it trades voltage for current (minus a small loss to winding resistance and core magnetising, covered in the losses post).
The worked examples: voltage and current from the handbook
Example 1 — voltage ratio: a transformer steps 120 V down to 6 V. It has 300 primary turns and 15 secondary turns. Voltage ratio = 120/6 = 20:1, and turns ratio = 300/15 = 20:1. The two ratios match, exactly as the theory says. (One small note: the handbook’s printed solution writes “120/60” in one step — an evident typesetting slip for 120/6; the stated result of 20:1 is consistent with 6 V.)
Example 2 — secondary voltage from turns: a transformer has 240 V on the primary, 250 primary turns, and 50 secondary turns. V_S = (50/250) × 240 = 48 V.
Example 3 — primary voltage and turns: a transformer has a turns ratio of 1:4, a secondary of 5,000 turns, and 60 V on the secondary. V_P = 60/4 = 15 V, and N_P = 5,000/4 = 1,250 turns.
Example 4 — current ratio: a transformer steps 120 V up to 500 V, with 4 A on the primary. I_S = (120/500) × 4 = 0.96 A. The voltage went up about four times, so the current came down to about a quarter.
The square of the turns ratio sets the impedance
Here is the part people miss: the turns ratio also sets the impedance relationship between primary and secondary, and it does so by its square:
(N_P / N_S)² = Z_P / Z_S
Maximum power transfers between circuits through a transformer when the impedances are equal — matched. So a transformer can match a source to a load: pick the turns ratio whose square equals the impedance ratio you need. A small built example (the handbook states the relation but gives no numeric impedance example, so this one is built from the formula): a transformer with a turns ratio of 2:1 has an 8 Ω load on its secondary. The impedance seen from the primary is Z_P = 2² × 8 = 32 Ω. Double the turns, quadruple the impedance — that square is why getting the ratio right matters so much.
Common mistakes
- “A transformer creates power.” It does not — it trades voltage for current. Power out is power in minus the small copper and core losses.
- “Voltage ratio and turns ratio are different things.” They are the same number: V_P/V_S = N_P/N_S. If the turns ratio is 20:1, the voltage ratio is 20:1.
- “Step up the voltage and the current goes up too.” It goes down, in the same proportion. Stepping 120 V up to 500 V with 4 A in gives 0.96 A out.
- “Impedance ratio equals the turns ratio.” It equals the square of the turns ratio: (N_P/N_S)² = Z_P/Z_S. A 2:1 transformer turns 8 Ω into 32 Ω, not 16 Ω.
- “The primary and secondary are electrically connected.” They are not — the energy crosses by magnetic induction through the shared core. That is also why a transformer cannot pass DC: with no changing field, there is no induction.
- “Winding separation doesn’t matter.” It does — flux that passes through one coil but not the other is magnetic leakage, and it wastes efficiency. Windings are kept close, on a short magnetic circuit.
- “The handbook’s ‘120/60’ step is a different answer.” It is a typesetting slip for 120/6; the stated 20:1 result is consistent with the 6 V secondary.
Summary
A transformer is two coils sharing a changing magnetic field: the primary’s AC magnetises the core, and the alternating flux induces voltage in the secondary by mutual induction. One number — the turns ratio, N_P/N_S — sets the voltage ratio (V_P/V_S = N_P/N_S), the current ratio in reverse (N_P/N_S = I_S/I_P), and the impedance ratio by its square ((N_P/N_S)² = Z_P/Z_S). Step the voltage up and the current steps down; match the impedances by the square of the turns and maximum power transfers. And remember the handbook’s own slip: 120 V to 6 V is 20:1, not 120/60.
Quick-check questions
- What is mutual induction?
- What is the turns ratio, and how does it set the voltage ratio?
- A transformer has 240 V on the primary, 250 primary turns, and 50 secondary turns. What is the secondary voltage?
- A transformer steps 120 V up to 500 V with 4 A on the primary. What is the secondary current?
- How does the turns ratio set the impedance ratio?
Answers: 1. When flux lines from the expanding/contracting magnetic field of one coil cut the windings of another nearby coil, a voltage is induced in that coil. 2. TR = N_P/N_S, and the voltage ratio equals it: V_P/V_S = N_P/N_S. 3. V_S = (50/250) × 240 = 48 V. 4. I_S = (120/500) × 4 = 0.96 A. 5. By its square: (N_P/N_S)² = Z_P/Z_S — so a 2:1 transformer turns an 8 Ω secondary load into 32 Ω seen from the primary.
Based on DOE-HDBK-1011/92, Electrical Science, Module 13, paraphrased for study.
Top 10 Scorers
| Pos. | Name | Score | Duration |
|---|---|---|---|
| There is no data yet |
What is mutual induction?
When flux lines from the expanding/contracting magnetic field of one coil cut the windings of another nearby coil, a voltage is induced in that coil
Question Explanation:
Mutual induction is the process by which a changing magnetic field from one coil induces a voltage in a nearby coil. The induced EMF depends on the relative positions of the two coils.
Which winding is the primary, and which is the secondary?
The coil energised from an AC source is the primary; the coil delivering AC to the load is the secondary
Question Explanation:
The coil energised from an AC source is the primary winding; the coil delivering AC to the load is the secondary winding.
What is the turns ratio?
The ratio of primary turns to secondary turns, N_P / N_S
Question Explanation:
The turns ratio is the ratio of primary turns to secondary turns (Eq. 13-1): TR = N_P / N_S.
How does the turns ratio set the voltage ratio?
The voltage ratio equals the turns ratio: V_P / V_S = N_P / N_S
Question Explanation:
Winding voltage is directly proportional to turns, so the voltage ratio (VR) equals the turns ratio (TR). A VR of 1:5 means 5 V secondary per 1 V primary; 5:1 means 1 V secondary per 5 V primary.
A transformer steps 120 V down to 6 V and has 300 primary turns and 15 secondary turns. What are the voltage ratio and turns ratio?
Both are 20:1
Question Explanation:
Voltage ratio = 120/6 = 20:1, and turns ratio = 300/15 = 20:1. The two ratios match, exactly as the theory says. (The handbook prints "120/60" in one step — a typesetting slip for 120/6.)
A transformer has 240 V on the primary, 250 primary turns, and 50 secondary turns. What is the secondary voltage?
48 V
Question Explanation:
V_S = (50/250) × 240 = 48 V. The secondary has one-fifth the turns, so it gets one-fifth the voltage.
A transformer steps 120 V up to 500 V with 4 A on the primary. What is the secondary current?
0.96 A
Question Explanation:
I_S = (120/500) × 4 = 0.96 A. A step-up in voltage is a proportional step-down in current.
How does the turns ratio set the impedance ratio?
By its square: (N_P / N_S)² = Z_P / Z_S
Question Explanation:
The impedance ratio equals the square of the turns ratio: (N_P/N_S)² = Z_P/Z_S. A 2:1 transformer turns an 8 Ω secondary load into 32 Ω seen from the primary.
Why is maximum power transferred through a transformer when the impedances are matched?
Because the turns ratio can be chosen so the source impedance equals the load impedance as seen through the transformer
Question Explanation:
Maximum power transfers between circuits through a transformer when impedances are equal (matched). A definite turns ratio sets the primary-secondary impedance relationship, so the ratio can be chosen to match source to load.
What is magnetic leakage, and why are transformer windings kept close together?
Flux passing through one coil but not both; separating the windings lengthens the magnetic circuit and increases leakage, wasting efficiency