What you’ll learn
After this post, you will be able to name the four standard wiring schemes — Edison, Delta, and Wye — explain when each one is used, work out what voltages each one gives you, and spot the “high leg” in a 4-wire Delta system before it surprises you.
The language first: five words
Distribution wiring has its own vocabulary, and the chapter defines it precisely. Ampacity is the current a conductor can carry continuously without exceeding its temperature rating. A bond is the permanent joining of metallic parts or circuits, assuring electrical continuity and the capacity to safely conduct any likely current. A conductor is any wire, cable, or substance capable of carrying current. Ground is a conducting connection, intentional or accidental, between a circuit or equipment and the earth, a place of zero potential. Ground voltage is the voltage between any given conductor and any point at ground potential. Two more words complete the set: a leg is a current-carrying conductor intended to deliver power to or from a load, normally at a potential other than ground; a neutral is a current-carrying conductor normally tied to ground so its electrical potential is zero. (One printed slip to know about: the chapter summary on page 28 misprints the neutral definition with “other than ground” wording — the chapter body’s page 22 definition, tied to ground at zero potential, is the correct one.) Phase voltage, as this handbook defines it, is the greatest RMS difference of potential between any two legs of the circuit.
One three-phase source, two ways to get single-phase power
Every phase of a three-phase system is effectively a single-phase generator spaced 120 degrees from the others, so a three-phase source is a convenient single-phase source too. There are two ways to connect a single-phase load to it: phase-to-ground — load from a phase leg to any ground point — or phase-to-phase — load between any two legs. Which voltages those two methods give you depends on whether the source is Delta or Wye, and that is where the schemes part company.
Edison: the 120/240 V system in every house
The 3-wire, single-phase Edison system is the only approved method of wiring single-phase power, and it is the system in every house. A centre-tapped transformer with the centre tap grounded gives half voltage — 120 V — on either side, or full voltage — 240 V — across both sides. Physically it is two insulated conductors plus one bare conductor: the current-carrying legs and neutral are insulated, and the uninsulated conductor is the safety ground, bonded to the system ground point and to each junction box and device. At half voltage (120 V) current goes supply leg → load → neutral, and the ground carries no current unless a fault occurs, when it carries fault current safely to ground. At full voltage (240 V) the insulated conductors span the full winding and the bare conductor is bonded to the grounded centre tap; in a balanced system the neutral carries no current — ground capacity only — and on an unbalanced load or a fault the bare conductor carries current but stays at zero volts because it is tied to ground. Two voltages, one grounded centre, and a bare conductor that does nothing until the day it saves someone.
Delta: the transmission scheme, grounded or not
The 3-wire, three-phase Delta system is the simplest three-phase system, normally used for transmission in the intermediate voltage class — roughly 15,000 down to 600 V. Unlike single-phase, a three-phase system needs neither a separate neutral nor a ground to operate safely, but all three- and four-wire three-phase systems can include an effective ground path for safety. Delta comes in two variants. Ungrounded Delta is confined to protected environments — fully enclosed ducts, overhead lines unreachable without extraordinary means — because each conductor’s ground voltage equals the full phase voltage: there is no ground reference at all, and every conductor sits at full voltage to earth. Corner-grounded Delta puts a ground point on one corner of the triangle: that lowers one phase’s ground reference to zero while retaining the phase-to-phase voltage, and the corner-grounded phase acts like the Edison grounded neutral — it carries current and holds ground potential. It is economical in wiring, and the grounded phase can physically protect the other two from accidental grounding or lightning outdoors. But it is rarely used for low voltage (below 600 V) because of the absence of a safety ground that many facilities require for circuits with potential worker contact. Scheme choice follows the exposure, not just the voltage.
The 4-wire Delta: Edison convenience on a Delta frame — and the high leg
The 4-wire, three-phase Delta system combines ungrounded Delta for three-phase loads with Edison convenience for single-phase loads: one side of the Delta has a grounded-neutral conductor on a centre tap of one phase. Single-phase voltage each side of the half-tap is one-half the normal phase-to-phase voltage — the same half/full arrangement as Edison, with a grounded neutral — so at any location either full-voltage three-phase power or half/full-voltage single-phase power is available. But it carries three strict precautions: (1) balance all loads carefully on single- and three-phase legs; (2) measure neutral-to-phase to identify the “high leg” — also called the “bastard voltage” — the voltage between one leg and the grounded neutral is considerably higher than the rest of the single-phase system; and (3) never use the high leg as a single-phase source, because no ground or grounded neutral exists for that circuit. The high leg is a trap for the unwary: identify it by measurement and never feed single-phase loads from it. The centre tap gives you two familiar 120 V legs and one leg that is not 120 V at all — and the only way to know which is which is to measure.
This chapter gives no numeric worked example, so here is a walkthrough built from the chapter’s rules and flagged as such. Take a 240 V Delta system with a centre-tapped phase. The two legs either side of the tap give you 120 V each to the grounded neutral — familiar Edison voltages, safe for single-phase loads. The third leg — the high leg — measures considerably higher than 120 V to that same neutral, because it sits across the full Delta geometry rather than half of one winding. A worker who assumes all three legs are 120 V to neutral and wires a single-phase load to the high leg has connected a 120 V load to a much higher voltage, with no grounded neutral in that circuit to protect it. The fix is a meter, not a guess: measure neutral-to-phase on all three legs, mark the high one, and never use it as a single-phase source.
Wye: the safest all-purpose low-voltage system
The 4-wire, three-phase Wye system — centre-grounded Wye — has completely different voltage characteristics from Delta: phase-to-ground voltage equals phase voltage divided by 1.73. It extends three insulated current-carrying conductors plus an insulated grounded neutral to the loads, giving, by conductor choice, reduced-voltage single-phase (a phase leg to neutral), full-voltage single-phase (any two phase legs), or full-voltage three-phase. Its precautions are to balance single-phase loads and to size the neutral’s full-load ampacity to 1.73 times the highest phase ampacity — the subject of the next post. Bonds are established between the grounded neutral and all system components. The handbook recognises it as the safest possible multi-purpose distribution system for low voltage, commonly seen in the 208/120 V range in many facilities: 208 V phase-to-phase, 120 V phase-to-neutral, because 208 divided by 1.73 is 120.
Common mistakes
- “A neutral is at a potential other than ground.” No — a neutral is a current-carrying conductor normally tied to ground so its electrical potential is zero. The chapter summary misprints this; the chapter body’s definition is the correct one.
- “All three legs of a 4-wire Delta are 120 V to neutral.” No — two are, and the third is the high leg, considerably higher. Measure neutral-to-phase on all three legs and never feed single-phase loads from the high leg.
- “The high leg is just another single-phase source.” It is not: no ground or grounded neutral exists for that circuit. Never use the high leg as a single-phase source.
- “Ungrounded Delta is fine anywhere.” It is confined to protected environments — fully enclosed ducts, overhead lines unreachable without extraordinary means — because each conductor’s ground voltage equals the full phase voltage.
- “Corner-grounded Delta is the cheap answer for low voltage.” It is economical in wiring, but rarely used below 600 V because of the absence of a safety ground many facilities require for circuits with potential worker contact.
- “A three-phase system needs a neutral to operate.” Unlike single-phase, a three-phase system needs neither a separate neutral nor a ground to operate safely — though all three- and four-wire systems can include an effective ground path for safety.
- “The bare conductor in an Edison system carries load current.” At 120 V it carries no current unless a fault occurs; at 240 V in a balanced system the neutral carries no current either. The bare conductor is the safety ground, bonded to the system ground point and to each junction box and device.
Summary
Edison gives you 120 V or 240 V from a centre-tapped, centre-grounded transformer — two insulated conductors plus a bare safety ground, the only approved single-phase method. Delta is the simplest three-phase scheme, for intermediate-voltage transmission: ungrounded only in protected environments, corner-grounded to give one phase a zero ground reference, but rarely below 600 V for lack of a safety ground. The 4-wire Delta mixes Delta three-phase with Edison single-phase — and hides a high leg, considerably higher than the rest to neutral, that must be measured, marked, and never used as a single-phase source. Wye, centre-grounded, gives phase-to-neutral voltage of phase voltage divided by 1.73, three insulated conductors plus an insulated grounded neutral, and every voltage choice at once — the safest all-purpose low-voltage system, commonly 208/120 V. Four schemes, one rule: know your voltages to ground before you connect anything.
Quick-check questions
- What is a neutral, and what is a leg?
- How does the Edison system give 120 V and 240 V?
- What are the two variants of the 3-wire Delta system, and where is each used?
- What is the high leg in a 4-wire Delta system, and what must you never do with it?
- What voltages does a centre-grounded Wye system give, and why is it the safest low-voltage scheme?
Answers
- A neutral is a current-carrying conductor normally tied to ground so its electrical potential is zero. A leg is a current-carrying conductor intended to deliver power to or from a load, normally at a potential other than ground.
- A centre-tapped transformer with the centre tap grounded gives half voltage (120 V) on either side or full voltage (240 V) across both sides. Two insulated conductors plus one bare safety ground, bonded to the system ground point and each junction box/device.
- Ungrounded Delta — confined to protected environments (fully enclosed ducts, unreachable overhead lines), each conductor’s ground voltage equals the full phase voltage. Corner-grounded Delta — a ground point on one corner lowers that phase’s ground reference to zero while retaining phase-to-phase voltage; economical, but rarely used below 600 V for lack of a safety ground.
- The high leg (bastard voltage) is the leg whose voltage to the grounded neutral is considerably higher than the rest of the single-phase system. Never use it as a single-phase source, because no ground/grounded neutral exists for that circuit.
- Phase-to-ground voltage = phase voltage / 1.73, so a 208 V system gives 120 V phase-to-neutral. It offers reduced-voltage single-phase, full-voltage single-phase, or full-voltage three-phase from three insulated conductors plus an insulated grounded neutral, with bonds between grounded neutral and all components — recognised as the safest possible multi-purpose distribution system for low voltage.
Based on DOE-HDBK-1011/92, Electrical Science, Module 15, paraphrased for study.
Top 10 Scorers
| Pos. | Name | Score | Duration |
|---|---|---|---|
| There is no data yet |
What is ampacity?
The current a conductor can carry continuously without exceeding its temperature rating
Question Explanation:
Ampacity is the current a conductor can carry continuously without exceeding its temperature rating.
What is a neutral?
A current-carrying conductor normally tied to ground so its electrical potential is zero
Question Explanation:
A neutral is a current-carrying conductor normally tied to ground so its electrical potential is zero. (The chapter summary misprints this with "other than ground" wording; the chapter body's definition is the correct one.)
What is a leg?
A current-carrying conductor intended to deliver power to or from a load, normally at a potential other than ground
Question Explanation:
A leg is a current-carrying conductor intended to deliver power to or from a load, normally at a potential other than ground.
How does the Edison system give 120 V and 240 V?
A centre-tapped transformer with the centre tap grounded gives half voltage (120 V) on either side or full voltage (240 V) across both sides
Question Explanation:
The 3-wire, single-phase Edison system uses a centre-tapped transformer with the centre tap grounded: half voltage (120 V) on either side, full voltage (240 V) across both sides.
In the Edison system, what does the bare conductor do?
It is the safety ground, bonded to the system ground point and to each junction box/device; it carries no current unless a fault occurs, when it carries fault current safely to ground
Question Explanation:
The uninsulated conductor is the safety ground, bonded to the system ground point and to each junction box/device. At 120 V it carries no current unless a fault occurs, when it carries fault current safely to ground.
Why is ungrounded Delta confined to protected environments?
Each conductor's ground voltage equals the full phase voltage — there is no ground reference at all
Question Explanation:
Ungrounded Delta is confined to protected environments — fully enclosed ducts, overhead lines unreachable without extraordinary means — because each conductor's ground voltage equals the full phase voltage.
What does corner-grounded Delta do, and why is it rarely used below 600 V?
A ground point on one corner lowers that phase's ground reference to zero while retaining phase-to-phase voltage; rarely used below 600 V because of the absence of a safety ground many facilities require
Question Explanation:
Corner-grounded Delta puts a ground point on one corner: that phase's ground reference drops to zero while phase-to-phase voltage is retained, and the grounded phase acts like the Edison grounded neutral. It is rarely used for low voltage (< 600 V) because of the absence of a safety ground many facilities require for circuits with potential worker contact.
What is the high leg in a 4-wire Delta system?
The leg whose voltage to the grounded neutral is considerably higher than the rest of the single-phase system — also called the "bastard voltage"
Question Explanation:
In a 4-wire Delta system, measure neutral-to-phase to identify the "high leg" / "bastard voltage" — the voltage between one leg and the grounded neutral is considerably higher than the rest of the single-phase system.
What must you never do with the high leg?
Never use it as a single-phase source, because no ground/grounded neutral exists for that circuit
Question Explanation:
Never use the high leg as a single-phase source, because no ground/grounded neutral exists for that circuit. Identify it by measurement and never feed single-phase loads from it.
In a centre-grounded Wye system, what is the phase-to-ground voltage, and what voltages does it offer?
Phase-to-ground voltage = phase voltage / 1.73; reduced-voltage single-phase (leg to neutral), full-voltage single-phase (any two legs), or full-voltage three-phase
Question Explanation:
In a centre-grounded Wye system, phase-to-ground voltage = phase voltage / 1.73. It offers reduced-voltage single-phase (phase leg to neutral), full-voltage single-phase (any two phase legs), or full-voltage three-phase — e.g. 208/120 V, because 208 / 1.73 = 120.