What you’ll learn
After this post, you will be able to explain why a generator’s voltage sags when load is added, work out voltage regulation as a percentage, and say why the sag is worse with a lagging power factor.
The voltage you get is not the voltage you set
Spin a generator with no load connected and its terminals sit at the no-load voltage — the full voltage the field produces, with nothing drawing current. Now connect a load. The voltage at the terminals drops. Add more load and it drops further. That drop is not a fault — it is the natural behaviour of a generator, and it has three causes. Understanding them is what voltage regulation is about.
Why the voltage sags: three causes
- Armature resistance (IR drop) — the armature winding has resistance, and the load current flowing through it drops voltage: V = I × R. More load current, more drop. This is the simplest cause and the easiest to calculate.
- Armature reaction — the load current in the armature makes its own magnetic field, and that field pushes against the main field from the rotor. At unity power factor it mostly distorts the main field; at lagging power factor it directly weakens it — a demagnetizing effect that cuts the generated voltage itself. This is the biggest cause of the sag with inductive loads.
- Armature reactance (IX drop) — the armature winding has reactance too, and the load current flowing through it drops voltage in quadrature. Like the resistance drop, it grows with load current.
Voltage regulation: the number that measures the sag
Voltage regulation is the percentage change in terminal voltage from no load to full load, compared to the full-load voltage:
% regulation = (V_no-load − V_full-load) / V_full-load × 100%.
A small number means a stiff machine — the voltage barely moves when the load changes. A large number means the voltage sags a lot. Note what the formula compares: the voltage at no load against the voltage at full load, with the full-load voltage as the reference. A generator with good regulation keeps the lights from dimming when a big motor starts.
The worked example: 500 V at no load, 480 V at full load
A generator’s terminal voltage is 500 V with no load connected. At full load it is 480 V. Voltage regulation = (500 − 480) / 480 × 100% = 20 / 480 × 100% = 4.17%. Now run the same machine at a lagging power factor of 0.8: the armature reaction weakens the field more, and the full-load voltage falls to 460 V instead of 480 V. Regulation = (500 − 460) / 460 × 100% = 40 / 460 × 100% = 8.70% — more than double. Same machine, same load current, worse regulation — because the power factor changed. That is why utilities care about power factor: a lagging load does not just draw more current, it drags the voltage down harder.
Why this matters — and what the regulator is for
Left alone, a generator’s voltage sags with load and rises when load is removed — and the sag is worst with lagging loads, exactly the kind of loads (motors, transformers) that fill a plant. That is why the previous post’s voltage regulator exists: it senses the sag and raises the field current to push the voltage back up, holding the terminal voltage at its set value despite the IR drop, the reactance drop, and the armature reaction. The regulator does not remove the causes — it compensates for them. And the regulation percentage tells you how hard the regulator has to work: a machine with 4% regulation needs only a small field boost; a machine with 9% needs a much bigger one.
Common mistakes
- “The voltage sags because the prime mover slows down.” It does not — the governor holds the speed (and the frequency) steady. The sag comes from armature resistance, reactance, and armature reaction.
- “Voltage regulation is the same as the voltage regulator.” It is not. Regulation is a number — the percentage change from no load to full load. The regulator is the device that compensates for it.
- “A bigger load always means a bigger sag.” Only for the same power factor. A lagging load sags the voltage more than a unity-power-factor load of the same current.
- “Armature reaction only matters in DC machines.” It matters in AC machines too — the armature current’s field pushes against the main field, and at lagging power factor it weakens it directly.
- “Regulation is measured against the no-load voltage.” It is not. The formula divides by the full-load voltage: (V_no-load − V_full-load) / V_full-load × 100%.
- “A generator with 0% regulation would be ideal.” In theory, yes — the voltage would never move. In practice, some regulation is unavoidable; the regulator’s job is to hold the voltage steady despite it.
- “The regulator removes the sag.” It does not remove the causes — it compensates for them by raising the field current.
Summary
A generator’s terminal voltage sags when load is added, for three reasons: the IR drop in the armature resistance, the IX drop in the armature reactance, and armature reaction — the armature current’s field pushing against (and, at lagging power factor, weakening) the main field. Voltage regulation measures the sag as a percentage: (V_no-load − V_full-load) / V_full-load × 100% — 4.17% in the worked example (500 V to 480 V), and 8.70% at 0.8 lagging power factor (500 V to 460 V). The automatic voltage regulator exists to compensate for all of it, holding the terminal voltage at its set value as the load changes.
Quick-check questions
- What are the three causes of voltage sag when load is added?
- What is the voltage regulation formula?
- In the worked example, what is the regulation at unity power factor, and at 0.8 lagging power factor?
- Why is the sag worse with a lagging power factor?
- What is the difference between voltage regulation and a voltage regulator?
Answers: 1. The IR drop in the armature resistance, the IX drop in the armature reactance, and armature reaction. 2. % regulation = (V_no-load − V_full-load) / V_full-load × 100%. 3. Unity power factor: (500 − 480) / 480 × 100% = 4.17%. At 0.8 lagging power factor: (500 − 460) / 460 × 100% = 8.70%. 4. Because at lagging power factor the armature current’s field directly weakens (demagnetizes) the main field, cutting the generated voltage itself — not just dropping voltage in the winding. 5. Regulation is a number — the percentage change from no load to full load. The regulator is the device that compensates for the sag by adjusting the field current.
Based on DOE-HDBK-1011/92, Electrical Science, Module 11, paraphrased for study.
Top 10 Scorers
| Pos. | Name | Score | Duration |
|---|---|---|---|
| There is no data yet |
What is the no-load voltage of a generator?
The terminal voltage with no load connected — the full voltage the field produces, with nothing drawing current
Question Explanation:
Spin a generator with no load connected and its terminals sit at the no-load voltage — the full voltage the field produces, with nothing drawing current.
What are the three causes of voltage sag when load is added?
The IR drop in the armature resistance, the IX drop in the armature reactance, and armature reaction
Question Explanation:
The voltage sag has three causes: armature resistance (IR drop), armature reactance (IX drop), and armature reaction — the load current's field pushing against the main field.
What is armature reaction?
The load current in the armature makes its own magnetic field, which pushes against the main field from the rotor
Question Explanation:
Armature reaction is the load current in the armature making its own magnetic field, and that field pushes against the main field from the rotor. At unity power factor it mostly distorts the main field; at lagging power factor it directly weakens it.
What is the voltage regulation formula?
% regulation = (V_no-load − V_full-load) / V_full-load × 100%
Question Explanation:
Voltage regulation is the percentage change in terminal voltage from no load to full load, compared to the full-load voltage: % regulation = (V_no-load − V_full-load) / V_full-load × 100%.
In the worked example (500 V no-load, 480 V full-load), what is the voltage regulation?
4.17%
Question Explanation:
Regulation = (500 − 480) / 480 × 100% = 20 / 480 × 100% = 4.17%.
In the worked example at 0.8 lagging power factor (full-load voltage 460 V), what is the voltage regulation?
8.70%
Question Explanation:
Regulation = (500 − 460) / 460 × 100% = 40 / 460 × 100% = 8.70% — more than double the unity-power-factor value.
Why is the voltage sag worse with a lagging power factor?
Because at lagging power factor the armature current's field directly weakens (demagnetizes) the main field, cutting the generated voltage itself
Question Explanation:
At lagging power factor the armature current's field directly weakens (demagnetizes) the main field, cutting the generated voltage itself — not just dropping voltage in the winding. That is why the sag is worse with lagging loads.
Does the voltage sag because the prime mover slows down?
No — the governor holds the speed (and the frequency) steady; the sag comes from armature resistance, reactance, and armature reaction
Question Explanation:
The voltage sags because of armature resistance, reactance, and armature reaction — not because the prime mover slows down. The governor holds the speed (and the frequency) steady.
What is the difference between voltage regulation and a voltage regulator?
Regulation is a number — the percentage change from no load to full load; the regulator is the device that compensates for the sag
Question Explanation:
Regulation is a number — the percentage change from no load to full load. The regulator is the device that compensates for it by adjusting the field current.
Does the voltage regulator remove the causes of the voltage sag?
No — it compensates for them by raising the field current to push the voltage back up
Question Explanation:
The regulator does not remove the causes — it compensates for them. It senses the sag and raises the field current to push the voltage back up, holding the terminal voltage at its set value despite the IR drop, the reactance drop, and the armature reaction.