What you’ll learn
After this post, you will be able to list the four conditions for paralleling two AC generators, explain what happens when each one is wrong, and say which control shares real power and which shares reactive power.
Why run two generators together?
One generator is rarely enough. A power plant runs several machines in parallel on a common bus so the load can be shared, a machine can be taken down for maintenance without killing the plant, and capacity can grow by adding machines instead of buying one giant one. But two generators cannot simply be switched onto the same bus — they must be synchronized first. Connecting an unsynchronized machine is like trying to merge onto a highway going the wrong way: the two machines fight, huge currents flow, and something breaks.
The four conditions for paralleling
Before the breaker closes, the incoming generator must match the running bus on four things:
- Same voltage — the incoming machine’s terminal voltage must equal the bus voltage. Adjust it with the field excitation.
- Same frequency — the incoming machine must spin at the same frequency as the bus. Adjust it with the prime mover’s speed (governor).
- Same phase sequence — the three phases must come in the same order (A-B-C). If the sequence is reversed, the machines fight each other continuously. This is checked once, when the machine is installed, and then never changes.
- In phase — at the instant the breaker closes, the incoming machine’s voltage must be in step with the bus voltage: same phase angle, rising and falling together. This is the one that changes moment by moment as the machine spins.
How you know it’s in phase: lamps and the synchroscope
The classic check is the synchronizing lamps: lamps connected across the breaker brighten and dim as the incoming machine drifts in and out of phase with the bus. When the lamps go dark (or bright, depending on the connection), the two voltages are in phase and the breaker can close. A synchroscope does the same job with a needle: it shows how fast the incoming machine is drifting and in which direction, and the needle points straight up — twelve o’clock — when the machines are in phase. The operator adjusts the governor to slow the drift, then closes the breaker at the top of the swing.
What happens if you get it wrong?
- Voltage mismatch — a difference in voltage drives a large reactive circulating current between the machines, even with no load. The machines heat up and the voltage sags.
- Frequency mismatch — if the incoming machine is running fast or slow, it is out of phase the moment the breaker closes. The machines pull each other into step with a violent surge of current — a mechanical shock that can shear a shaft coupling.
- Wrong phase sequence — the machines drive each other in opposite directions. This is the worst case: a massive short-circuit-like current the instant the breaker closes.
- Out of phase — closing the breaker with the voltages opposed is like shorting the two machines together. The surge current can be many times the rated current.
Once they’re together: who takes the load?
After the breaker closes, the two machines share the load — and the sharing is controlled by two different knobs:
- Real power (kW) is shared by the prime movers. Feed more steam, water, or fuel to one machine and it takes more of the kW load; the other takes less. The governor setting decides the kW share.
- Reactive power (kVAR) is shared by the field excitation. Strengthen one machine’s field and it takes more of the kVAR load; weaken it and it takes less. The excitation decides the kVAR share and the power factor of each machine.
- Frequency is held by the governors together; voltage is held by the excitation together. A machine that tries to run fast pushes power into the bus and is held back by the other machine — that is why parallel machines stay in step.
The worked example: two 150 kW machines, one 200 kW load
Two 150 kW generators are paralleled on a common bus feeding a 200 kW load. With both governors set the same, each machine takes half the load: 100 kW each, and each runs at two-thirds of its rating. Now the operator raises the governor setting on Generator A: A takes more of the load — say 120 kW — and B drops to 80 kW, while the total stays 200 kW and the frequency stays 60 Hz. If the operator instead strengthens A’s field, A takes more of the reactive load and its power factor falls, while B’s power factor rises — the kW split does not change. The lesson: the governor divides the kW, the field divides the kVAR.
Common mistakes
- “You can close the breaker whenever the voltages look close.” You cannot. Voltage, frequency, phase sequence, and phase angle must all match at the instant of closing.
- “Phase sequence is checked every time.” It is not. Phase sequence is checked once at installation; voltage, frequency, and phase are checked every time.
- “The governor controls the voltage.” It does not. The governor (prime mover) controls speed and frequency — and the kW share. The field excitation controls the voltage — and the kVAR share.
- “Once paralleled, the machines share the load equally.” Only if their settings are equal. The operator decides the split: governor for kW, field for kVAR.
- “A small voltage difference doesn’t matter.” It does. Even a small voltage difference drives a large reactive circulating current between the machines.
- “The synchroscope needle spinning fast is fine.” It is not. A fast-spinning needle means a big frequency difference — slow the drift down with the governor before closing the breaker.
- “One generator can be shut down any time.” Only after its load has been transferred to the other machines — otherwise the remaining machines are suddenly overloaded.
Summary
Paralleling lets several generators share one bus, but only if they are synchronized first: same voltage, same frequency, same phase sequence, and in phase at the instant the breaker closes. Lamps or a synchroscope show when the moment is right. After paralleling, the governor divides the real power (kW) and the field excitation divides the reactive power (kVAR). Get any condition wrong and the machines fight with surge currents that can break them — get them right and the machines share the load quietly, for years.
Quick-check questions
- What are the four conditions for paralleling two AC generators?
- What tool shows whether two machines are in phase, and what does it show at the moment to close the breaker?
- What happens if the phase sequence is wrong?
- Which control shares real power (kW), and which shares reactive power (kVAR)?
- In the worked example, how is a 200 kW load shared by two 150 kW machines with equal governor settings?
Answers: 1. Same voltage, same frequency, same phase sequence, and in phase at the instant the breaker closes. 2. Synchronizing lamps (they go dark, or bright, depending on the connection) or a synchroscope — its needle points straight up, twelve o’clock, when the machines are in phase. 3. The machines drive each other in opposite directions, with a massive short-circuit-like current the instant the breaker closes. 4. The prime mover / governor shares the real power (kW); the field excitation shares the reactive power (kVAR). 5. Each takes 100 kW — half the load — and each runs at two-thirds of its 150 kW rating.
Based on DOE-HDBK-1011/92, Electrical Science, Module 10, paraphrased for study.
Top 10 Scorers
| Pos. | Name | Score | Duration |
|---|---|---|---|
| There is no data yet |
Why are AC generators run in parallel on a common bus?
To share the load, allow maintenance without killing the plant, and add capacity by adding machines
Question Explanation:
A power plant runs several machines in parallel on a common bus so the load can be shared, a machine can be taken down for maintenance without killing the plant, and capacity can grow by adding machines instead of buying one giant one.
What are the four conditions for paralleling two AC generators?
Same voltage, same frequency, same phase sequence, and in phase at the instant the breaker closes
Question Explanation:
Before the breaker closes, the incoming generator must match the running bus on four things: same voltage, same frequency, same phase sequence, and in phase at the instant the breaker closes.
How is the incoming generator's voltage matched to the bus?
By adjusting the field excitation
Question Explanation:
The incoming machine's terminal voltage must equal the bus voltage, and it is adjusted with the field excitation.
How is the incoming generator's frequency matched to the bus?
By adjusting the prime mover's speed (governor)
Question Explanation:
The incoming machine must spin at the same frequency as the bus, and it is adjusted with the prime mover's speed (governor).
When is phase sequence checked?
Once, when the machine is installed — then it never changes
Question Explanation:
Phase sequence is checked once, when the machine is installed, and then never changes. Voltage, frequency, and phase are checked every time.
What does a synchroscope show, and what does it show at the moment to close the breaker?
How fast the incoming machine is drifting and in which direction; the needle points straight up (twelve o'clock) when the machines are in phase
Question Explanation:
A synchroscope shows how fast the incoming machine is drifting and in which direction, and the needle points straight up — twelve o'clock — when the machines are in phase. The operator adjusts the governor to slow the drift, then closes the breaker at the top of the swing.
What happens if the breaker is closed with the two voltages out of phase?
A surge current many times the rated current flows, like shorting the two machines together
Question Explanation:
Closing the breaker with the voltages opposed is like shorting the two machines together. The surge current can be many times the rated current.
What happens if the phase sequence is wrong when the breaker closes?
The machines drive each other in opposite directions, with a massive short-circuit-like current
Question Explanation:
Wrong phase sequence is the worst case: the machines drive each other in opposite directions, with a massive short-circuit-like current the instant the breaker closes.
After paralleling, which control shares the real power (kW) and which shares the reactive power (kVAR)?
The prime mover / governor shares the kW; the field excitation shares the kVAR
Question Explanation:
Real power (kW) is shared by the prime movers — feed more steam, water, or fuel to one machine and it takes more of the kW load. Reactive power (kVAR) is shared by the field excitation — strengthen one machine's field and it takes more of the kVAR load.
In the worked example, how is a 200 kW load shared by two 150 kW machines with equal governor settings, and what happens if Generator A's governor is raised?
Each takes 100 kW; raising A's governor makes A take more (e.g. 120 kW) and B drop to 80 kW, total still 200 kW
Question Explanation:
With both governors set the same, each machine takes half the load: 100 kW each, at two-thirds of its rating. Raising the governor setting on Generator A makes A take more of the load — say 120 kW — and B drops to 80 kW, while the total stays 200 kW and the frequency stays 60 Hz.
- Tags:
- VOL3