What You’ll Learn
- Which equipment Article 340 covers — from arc welders and motor drives to RF transmitters, MRI machines, and large electromagnets
- What 340.3 says Article 340 is for: guidance for building industry-specific safety-related work practices
- The seven exposure thresholds of 340.4, and why they are stated in both volts and milliamperes
- How the current limit is calculated in the formula bands — including the worked example at 10 kHz
- Why, at radio frequencies, shock thresholds depend on current and frequency and not on voltage
A Different Kind of Equipment, a Different Kind of Threshold
Most of NFPA 70E is written around conventional power systems: 50/60 Hz distribution, panels, motors, and feeders. Article 340 covers power electronic equipment — equipment that converts, controls, or generates electrical energy in ways that produce frequencies far beyond the power line, and sometimes radiation fields as well. Section 340.1 lists the family:
- Electric arc welding equipment
- High-power radio, radar, and television transmitting towers and antennas
- Industrial dielectric and radio frequency (RF) induction heaters
- Shortwave or RF diathermy devices
- Equipment that includes rectifiers and inverters, such as motor drives, uninterruptible power supply (UPS) systems, and lighting controllers
- Generators producing sub-RF (1 kHz to 3 kHz) and RF (3 kHz to 100 MHz) fields
- Ionizing radiation field generators, including X-rays, magnetrons, klystrons, thyratrons, vacuum tubes, and similar high-voltage vacuum devices
- Nonionizing radiation field generating equipment, including antennas and RF transmission lines, radar equipment, industrial scientific and medical equipment, RF induction and dielectric heaters, industrial microwave heaters and diathermy radiators, magnetic resonance imagers (MRIs), and large electromagnets
The commentary adds that the list is not all-inclusive: photovoltaic, fuel cell, and wind generation systems, for example, generally incorporate power electronic devices such as power converters as well. The informational note points to outside standards for deeper guidance — IEEE C95.1 on human exposure to electric, magnetic, and electromagnetic fields, IEC 60479-1 on the effects of current on human beings, and ICRP Publication 33 on protection against ionizing radiation from external sources used in medicine.
What Article 340 Is For: Section 340.3
Section 340.3 states the article’s application in one sentence: the purpose of Article 340 is to provide guidance for safety personnel in preparing specific safety-related work practices within their industry. In other words, Article 340 does not replace the work practices of Chapter 1 — it gives the people writing industry-specific practices for this unusual equipment a set of hazard thresholds and personnel measures to build on. The threshold table in 340.4 is the quantitative heart of that guidance.
The Threshold Table: Section 340.4
Section 340.4 sets electrical hazard thresholds: exposure levels shall not exceed those identified in the list unless appropriate controls are implemented. Each band pairs a voltage with a current — except in the highest bands, where only current appears, for a reason explained below.
| Frequency band | Voltage threshold | Current threshold |
|---|---|---|
| DC (0 Hz to 1 Hz) | 100 V | 40 mA |
| 50/60 Hz power | 50 V | 5 mA |
| AC (1 Hz to 3 kHz) | 50 V | 3 mA |
| AC (3 kHz to 100 kHz) | — | 1 × f mA (f in kHz) |
| AC (100 kHz to 3 MHz) | — | 100 mA |
| AC (3 MHz to 30 MHz) | — | 100(f/3)^0.3 mA (f in MHz) |
| AC (30 MHz to 110 MHz) | — | 200 mA |
Read the table as three zones. In the low-frequency zone — DC through 3 kHz — both a voltage and a current limit apply, and the current limits are small: 40 mA for DC, 5 mA at power frequency, and just 3 mA across the 1 Hz to 3 kHz band. These are the frequencies at which the body’s response to current is most dangerous per milliampere, which is why the familiar 50-volt figure from the rest of the standard appears here paired with milliampere limits in the single digits. In the formula zone — 3 kHz to 30 MHz — the allowable current rises with frequency, first linearly (1 × f) and then by a gentler power curve. In the high zone — 100 kHz to 110 MHz — the limit is a flat current value: 100 mA, then 200 mA above 30 MHz.
Working the Formulas
The two formula bands are meant to be calculated, not memorized. In the 3 kHz to 100 kHz band, the limit is 1 × f milliamperes, with f in kilohertz: at 10 kHz, the threshold is 1 × 10 = 10 mA; at 50 kHz, it is 50 mA; at the top of the band, 100 kHz, it reaches 100 mA — which is exactly where the next band’s flat 100 mA limit picks up. In the 3 MHz to 30 MHz band, the limit is 100(f/3)^0.3 milliamperes, with f in megahertz: at 3 MHz the formula gives 100 × 1^0.3 = 100 mA, again matching the band below it; at 30 MHz it gives 100 × 10^0.3 ≈ 100 × 2.0 ≈ 200 mA, matching the flat 200 mA limit of the final band. The table is continuous at its seams — each band hands off to the next at the same value.
Why Voltage Disappears from the Table
The second informational note to 340.4 carries the article’s key teaching point: RF electric shock thresholds depend on current and frequency, not voltage. That is why the voltage column empties out above 3 kHz. At power frequencies, voltage is a useful predictor because body impedance behaves in a relatively familiar way, and the rest of NFPA 70E is built around voltage-based boundaries and the 50-volt rule. At radio frequencies that relationship breaks down — what the body experiences is governed by the current that flows and the frequency at which it flows. A worker evaluating an RF exposure with a power-frequency mindset — “it’s only X volts” — is using the wrong variable entirely. The first informational note points to IEEE C95.1-2019 for hazard threshold information for workers trained in sub-RF and RF contact electric shock, and the commentary notes that Commentary Table 340.1 contains quantitative data on the physiological effects of current on the human body.
Worked Scenario
A technician maintains an industrial RF induction heater operating at 10 kHz and needs to set the exposure limit for a task that could involve contact with an energized part. She does not reach for the 50-volt rule — at 10 kHz, 340.4 puts her in the 3 kHz to 100 kHz band, where the threshold is a current calculated from frequency: 1 × f, with f in kHz, gives 1 × 10 = 10 mA. Her work practice therefore treats 10 mA as the exposure ceiling and builds the controls — insulation, guarding, procedure — around keeping any contact current at or below it. Later the same week she reviews a second unit, a dielectric heater running at 450 kHz. That frequency falls in the 100 kHz to 3 MHz band, so no calculation is needed: the threshold is a flat 100 mA. And when a colleague asks why neither limit is expressed in volts, she gives the note’s answer: at these frequencies, shock thresholds depend on current and frequency, not voltage.
Common Mistakes and Safety Notes
- Applying the 50-volt rule at RF. Above 3 kHz the 340.4 thresholds are current-based; voltage is not the controlling variable.
- Quoting only half a low-frequency threshold. The DC, 50/60 Hz, and 1 Hz–3 kHz bands each pair a voltage with a current limit — both apply.
- Using the wrong units in the formulas. The 1 × f band takes f in kilohertz; the 100(f/3)^0.3 band takes f in megahertz. Swapping them changes the answer by orders of magnitude.
- Assuming the equipment list is closed. The 340.1 scope is not all-inclusive — PV, fuel cell, and wind systems with power converters fall under the same thinking.
- Exceeding a threshold without controls. Section 340.4 permits exposure above the listed levels only when appropriate controls are implemented.
- Forgetting the guidance behind the numbers. IEEE C95.1 addresses exposure to electric, magnetic, and electromagnetic fields; 340.3 makes Article 340 the basis for industry-specific work practices, not a substitute for them.
Summary
Article 340 covers safety-related work practices around power electronic equipment — welders, drives, UPS systems, lighting controllers, RF transmitters and heaters, ionizing and nonionizing radiation equipment including MRIs and large electromagnets — and 340.3 frames it as guidance for safety personnel building industry-specific work practices. Section 340.4 sets the exposure thresholds: DC is limited to 100 V and 40 mA; 50/60 Hz power to 50 V and 5 mA; 1 Hz to 3 kHz to 50 V and 3 mA; then current alone takes over — 1 × f mA (f in kHz) from 3 to 100 kHz, a flat 100 mA to 3 MHz, 100(f/3)^0.3 mA (f in MHz) to 30 MHz, and 200 mA to 110 MHz. The bands meet seamlessly at their edges, and the reason voltage drops out of the table is the article’s central lesson: at RF, shock thresholds depend on current and frequency, not voltage.
Quick-Check Questions
- What are the 340.4 thresholds for DC and for 50/60 Hz power?
Answer: DC (0 Hz to 1 Hz): 100 volts and 40 milliamperes. 50/60 Hz power: 50 volts and 5 milliamperes. - A contact exposure occurs at 10 kHz. What is the current threshold, and how is it calculated?
Answer: 10 mA — the 3 kHz to 100 kHz band uses 1 × f mA with f in kHz, so 1 × 10 = 10 mA. - What is the threshold in the 100 kHz to 3 MHz band?
Answer: A flat 100 mA; no formula and no voltage value applies in that band. - Why do the higher-frequency rows of the table list no voltage?
Answer: Because RF electric shock thresholds depend on current and frequency, not voltage. - What is the purpose of Article 340 under 340.3?
Answer: To provide guidance for safety personnel in preparing specific safety-related work practices within their industry.
Based on NFPA 70E (2024), Article 340, paraphrased for study.