What You’ll Learn
- How Annex E supports the electrical safety program that Article 110.3 requires — as three layered lists
- The ten typical principles: what a program believes and commits to, from inspecting equipment to auditing itself
- The eight typical controls: the operating rules a program runs on, including the two that surprise people most
- The twelve procedure elements: what has to be determined and assessed before a task is performed
- How to audit an existing program against the three lists and find the gaps that matter
The Foundation Under Article 110.3
Article 110.3 requires an electrical safety program — this is the annex that shows what one is made of. Informative Annex E states its own purpose plainly: it provides information that can be used as the foundation for an effective electrical safety program. It does not hand down a finished program. Instead it offers three typical lists, and each list works at a different level. The principles are the program’s commitments — the things it holds true and acts on continuously. The controls are its operating rules — how the organization and its employees agree to behave around electrical energy. The procedures are its task-level discipline — what gets determined and assessed, item by item, before work is performed. A program missing any one layer has a characteristic weakness: principles without controls are slogans, controls without procedures are intentions, and procedures floating free of principles are paperwork nobody believes in.
The Ten Principles: What the Program Commits To
The typical electrical safety program principles in E.1 are introduced with “include, but are not limited to” — they are a floor, not a ceiling. Read as a set, they trace the life of safe work from the condition of the equipment to the verification of the program itself:
- Inspecting and evaluating the electrical equipment
- Maintaining the electrical equipment’s insulation and enclosure integrity
- Planning every job and documenting first-time procedures
- De-energizing, if possible (see 120.6)
- Anticipating unexpected events
- Identifying the electrical hazards and reducing the associated risk
- Protecting employees from electric shock, burn, blast, and other hazards due to the working environment
- Using the right tools for the job
- Assessing people’s abilities
- Auditing the principles
Three of these deserve a second look. “De-energizing, if possible” is a principle, not a preference — the program’s default answer to every task is an electrically safe work condition, and energized work is the exception that must justify itself. “Planning every job and documenting first-time procedures” quietly solves the recurring-work problem: the first time a task is done, its procedure gets written down, so the tenth performance is not improvised from memory. And the last principle, “auditing the principles,” makes the program self-checking — a program that is never audited against its own principles drifts, and nobody notices until an incident does the auditing instead.
The Eight Controls: How the Program Runs
The typical electrical safety program controls in E.2 are the management machinery that turns principles into daily behavior:
- The employer develops programs and procedures, including training, and the employees apply them
- Employees are to be trained to be qualified for working in an environment influenced by the presence of electrical energy
- Procedures are to be used to identify the electrical hazards and to develop job safety plans to eliminate those hazards or to control the associated risk for those hazards that cannot be eliminated
- Every electrical conductor or circuit part is considered energized until proved otherwise
- De-energizing an electrical conductor or circuit part and making it safe to work on is, in itself, a potentially hazardous task
- Tasks to be performed within the limited approach boundary or arc flash boundary of exposed energized electrical conductors and circuit parts are to be identified and categorized
- Precautions appropriate to the working environment are to be determined and taken
- A logical approach is to be used to determine the associated risk of each task
Two controls carry the deepest safety logic in the whole annex. “Every conductor is energized until proved otherwise” reverses the burden of proof: equipment is guilty of being live until testing proves it innocent, so the absence of voltage is something you demonstrate, never something you assume. And its companion — “de-energizing is itself a potentially hazardous task” — kills a dangerous myth. The work of opening disconnects, testing for absence of voltage, and applying grounds is performed on equipment that must be treated as energized throughout, so the act of making a job safe is itself planned and protected as hazardous work. Note also the division of labor in the first control: the employer develops the programs, procedures, and training; the employees apply them. Neither half works alone.
The Twelve Procedure Elements: What Gets Determined Before the Task
The typical electrical safety program procedures in E.3 move from the program level down to the task level. Procedures can include determination and assessment of the following:
- Purpose of the task
- Qualifications and number of employees to be involved
- Identification of hazards and assessment of risks of the task
- Limits of approach
- Safe work practices to be used
- Personal protective equipment (PPE) involved
- Insulating materials and tools involved
- Special precautionary techniques
- Electrical single-line diagrams
- Equipment details
- Sketches or photographs of unique features
- Reference data
Read the list as a planning checklist and its logic shows. It starts with why the task exists and who should do it — the right number of people, with the right qualifications — then works through the hazards of this specific task, the boundaries that apply, and the practices, PPE, and insulating tools the work requires. The back half is documentation: single-line diagrams, equipment details, sketches or photographs of unique features, and reference data. That documentation tail is easy to underrate. Unique features are exactly where generic procedures fail — the oddball backfeed, the nonstandard arrangement, the thing the last crew learned the hard way — and a sketch or photograph captured in the procedure is how that knowledge reaches the next crew.
Worked Scenario
A maintenance manager at a mid-sized fabrication shop decides to audit the shop’s electrical safety program against Annex E before writing anything new. She works the three lists as a checklist. Against E.1, the shop scores well on equipment inspection and tool selection, but two principles are missing entirely: first-time procedures are never documented — each new task is figured out on the fly and the knowledge leaves with whoever did it — and the principles have never been audited in the program’s six years. Against E.2, the gap is a control she had never seen stated anywhere: the shop treats de-energizing as the safe part of the job, with no recognition that establishing an electrically safe work condition is itself a potentially hazardous task requiring its own precautions. Boundary tasks, she also finds, are neither identified nor categorized as the sixth control calls for. Against E.3, the shop’s task procedures consistently cover PPE and safe work practices but almost never record equipment details, and nobody has ever attached a sketch or photograph of a unique feature — including the dual-fed panel in Building 2 that has surprised two different crews. The audit produces a short, specific fix list: document first-time procedures, audit the program annually, treat de-energizing as hazardous work in every job plan, categorize boundary tasks, and photograph the dual-fed panel into its procedure. Not one item on that list came from buying anything — it came from holding an existing program up against thirty typical elements and seeing which ones were absent.
Common Mistakes and Safety Notes
- Treating the lists as exhaustive. Each list “can include, but is not limited to” its items — they are typical elements, a foundation to build on, not a compliance ceiling.
- Building procedures with no principles behind them. Task paperwork that is not anchored in program principles and controls becomes a signature exercise nobody believes in.
- Assuming equipment is dead until proved live. The control runs the other way: every conductor or circuit part is considered energized until proved otherwise.
- Calling de-energizing “the safe part.” Establishing an electrically safe work condition is itself a potentially hazardous task, performed on equipment treated as energized until proved otherwise.
- Skipping the documentation elements. Single-line diagrams, equipment details, and sketches or photographs of unique features are procedure elements in their own right — unique features are where generic procedures fail.
- Never auditing. Auditing the principles is itself one of the principles; a program that is not checked against them drifts silently.
Summary
Annex E lays out the anatomy of an effective electrical safety program in three layers. Ten typical principles set the commitments — know your equipment, maintain it, plan every job, de-energize if possible, anticipate surprises, match people and tools to the work, and audit the principles themselves. Eight typical controls supply the operating rules — employer develops and employees apply, hazards are identified and planned against, every conductor is energized until proved otherwise, de-energizing is itself hazardous work, boundary tasks are categorized, and risk is assessed by a logical approach. Twelve typical procedure elements define what a task-level procedure determines, from purpose and qualifications through hazards, boundaries, PPE, and tools, to the diagrams, equipment details, sketches, and reference data that carry knowledge to the next crew. Foundation, machinery, and discipline — a program needs all three.
Quick-Check Questions
- How many typical principles, controls, and procedure elements does Annex E list?
Answer: Ten principles (E.1), eight controls (E.2), and twelve procedure elements (E.3). - What is the last of the ten principles, and why does it matter?
Answer: Auditing the principles. It makes the program self-checking, so drift from its own commitments is caught by the audit rather than by an incident. - State the fourth control in E.2.
Answer: Every electrical conductor or circuit part is considered energized until proved otherwise. - What does E.2 say about de-energizing a conductor or circuit part?
Answer: That de-energizing it and making it safe to work on is, in itself, a potentially hazardous task. - Which E.3 elements capture the unique features of a specific installation, and how?
Answer: Sketches or photographs of unique features — along with electrical single-line diagrams and equipment details — document the installation-specific facts a generic procedure would miss.
Based on NFPA 70E (2024), Informative Annex E, paraphrased for study.