What you’ll learn
After this post, you will be able to explain why a single-phase motor cannot start on its own, how phase splitting fakes a rotating field, and what the centrifugal switch does — and when it fails.
The problem: one phase, no rotation
A three-phase motor starts by itself because its three currents make a field that rotates. A single-phase motor has only one current, so its stator field does not rotate — it pulses back and forth, like a light blinking on and off. A pulsing field has no direction: it pulls the rotor forward as much as backward, and the net starting torque is zero. Give the rotor a spin by hand and it will keep going (the pulsing field can sustain rotation once it is moving), but on its own it just sits there and hums. A single-phase motor needs a trick to get started — and the trick is called phase splitting.
The trick: two windings, two different currents
Phase splitting uses two stator windings instead of one, wound 90 electrical degrees apart and connected in parallel across the same single-phase supply:
- The main winding — low resistance, high reactance. Its current lags the voltage a lot.
- The starting winding — higher resistance, lower reactance. Its current lags the voltage much less.
Both windings see the same voltage, but because their impedances differ, their currents are out of phase with each other. Two currents out of phase in two windings 90° apart make a field that appears to rotate — not a true three-phase rotation, but close enough to produce starting torque. The rotor feels a sweeping field, current is induced in its bars, and the motor starts turning. The split-phase motor has faked a rotating field out of a single phase.
The centrifugal switch: the starting winding’s exit
The starting winding is only needed to get the motor moving. It is built with thin wire and is not meant to carry current continuously — leave it in circuit and it will overheat. So a centrifugal switch on the motor shaft disconnects it: as the motor speeds up, the switch opens at about 70–80% of synchronous speed, cutting the starting winding out. From then on the motor runs on the main winding alone, as a single-phase induction motor. The hand-off is automatic — the motor’s own speed throws the switch.
The worked example: starting a fan motor, step by step
Take a split-phase motor driving a small fan, on a 120 V single-phase supply. Step 1 — switch on: both windings are energized. The main winding draws a large lagging current; the starting winding draws a smaller, less-lagging current. The two currents are out of phase, the field appears to rotate, and starting torque appears — the rotor begins to turn. Step 2 — accelerating: the rotor picks up speed, the slip falls, and the motor’s torque follows the torque–slip curve toward its running point. Step 3 — at about 70–80% of synchronous speed the centrifugal switch opens and the starting winding drops out. Step 4 — running: the motor continues on the main winding alone at a few percent slip, driving the fan. If the load stalls the motor below the switch speed, the switch closes again and the starting winding comes back in — that is also how the motor restarts itself after a stall.
What goes wrong
- Failed centrifugal switch (stuck closed): the starting winding stays in circuit after the motor is up to speed. It overheats, its insulation burns, and the motor fails — often with a smell of burnt varnish. This is the classic split-phase failure.
- Failed centrifugal switch (stuck open): the starting winding never connects, so the motor has no starting torque. It hums at standstill and will not start — but it will run if you spin it by hand.
- Starting winding burnout: the thin starting winding is only rated for a few seconds of use. Repeated failed starts, or a motor that cannot reach switch speed because of a heavy load, will burn it out.
- Wrong rotation: a split-phase motor’s direction is set by which way the starting winding is connected relative to the main winding. Swap the starting winding leads and the motor runs the other way.
Where single-phase motors live
Single-phase induction motors are for very small jobs: household appliances, fans, buffers, and small commercial equipment — anywhere only a single-phase supply is available and the power needed is small. They are not used for heavy industrial work: their starting torque is modest, their efficiency is lower than a three-phase motor’s, and the starting winding and switch are extra parts that can fail. For anything big, three-phase is the answer.
Common mistakes
- “A single-phase motor starts like a three-phase motor.” It does not — a single-phase field only pulses, so the motor has no starting torque without phase splitting.
- “The starting winding runs all the time.” It does not — the centrifugal switch disconnects it at 70–80% of synchronous speed. It is a starting-only winding.
- “Phase splitting makes a true rotating field.” It does not — it makes a field that appears to rotate, good enough to start the motor but not a true three-phase rotation.
- “The two windings are identical.” They are not — the starting winding has higher resistance and lower reactance than the main winding, and that difference is what puts their currents out of phase.
- “If the motor hums but won’t start, the motor is dead.” Not necessarily — a stuck-open centrifugal switch gives exactly that symptom, and the motor will run if spun by hand.
- “A burnt smell means the main winding failed.” Often it is the starting winding — it stayed in circuit because the centrifugal switch stuck closed.
- “Single-phase motors are just small three-phase motors.” They are a different design, built around the phase-splitting trick, for small loads on single-phase supplies.
Summary
A single-phase supply makes a field that pulses, not one that rotates, so a single-phase motor has no starting torque on its own. The split-phase trick gives it two stator windings 90° apart with different impedances — main winding low resistance and high reactance, starting winding higher resistance and lower reactance — so their currents are out of phase and the field appears to rotate, producing starting torque. At 70–80% of synchronous speed a centrifugal switch drops the starting winding out, and the motor runs on the main winding alone. The classic failure is the switch sticking closed and burning the starting winding. Single-phase motors are for small jobs — appliances, fans, buffers — not heavy industry.
Quick-check questions
- Why can’t a single-phase motor start on its own?
- How does phase splitting fake a rotating field?
- How do the main and starting windings differ?
- What does the centrifugal switch do, and when?
- What happens if the centrifugal switch sticks closed?
Answers: 1. A single-phase field only pulses back and forth, so it pulls the rotor equally in both directions and the net starting torque is zero. 2. Two stator windings 90 electrical degrees apart with different impedances carry currents out of phase with each other, so the field appears to rotate and produces starting torque. 3. The main winding has low resistance and high reactance (its current lags a lot); the starting winding has higher resistance and lower reactance (its current lags much less). 4. The centrifugal switch on the shaft disconnects the starting winding at about 70–80% of synchronous speed, leaving the motor to run on the main winding alone. 5. The starting winding stays in circuit after the motor is up to speed, overheats, and burns out.
Based on DOE-HDBK-1011/92, Electrical Science, Module 12, paraphrased for study.
Top 10 Scorers
| Pos. | Name | Score | Duration |
|---|---|---|---|
| There is no data yet |
Why does a single-phase motor have no starting torque on its own?
Its stator field only pulses back and forth, pulling the rotor equally in both directions, so the net starting torque is zero
Question Explanation:
A single-phase motor has only one current, so its stator field does not rotate — it pulses back and forth. A pulsing field has no direction: it pulls the rotor forward as much as backward, and the net starting torque is zero.
What is phase splitting?
Using two stator windings of unequal impedance spaced 90 electrical degrees apart, so their currents are out of phase and the field appears to rotate
Question Explanation:
Phase splitting uses two stator windings of unequal impedance spaced 90 electrical degrees apart in parallel on a single-phase source. With the same voltage applied, their currents are out of phase by about 30 degrees — the currents peak at different times and the stator field appears to rotate.
How do the main and starting windings differ in a split-phase motor?
The main winding has low resistance and high reactance; the starting winding has higher resistance and lower reactance
Question Explanation:
In a split-phase motor the starting winding has higher resistance and lower reactance than the main winding. With the same voltage applied, the main-winding current lags the starting-winding current enough to give a rotating field and starting torque.
What does the centrifugal switch do in a split-phase motor?
It disconnects the starting winding at about 70–80% of synchronous speed
Question Explanation:
At 70–80% of synchronous speed a centrifugal switch on the shaft opens and disconnects the starting winding. From then on the motor runs on the main winding alone.
Why must the starting winding be disconnected after starting?
It is built with thin wire, is not meant to carry current continuously, and would overheat if left in circuit
Question Explanation:
The starting winding is only needed to get the motor moving. It is built with thin wire and is not meant to carry current continuously — leave it in circuit and it will overheat.
What happens if the centrifugal switch sticks closed?
The starting winding stays in circuit, overheats, and burns out
Question Explanation:
A failed centrifugal switch stuck closed leaves the starting winding in circuit after the motor is up to speed. It overheats, its insulation burns, and the motor fails — often with a smell of burnt varnish. This is the classic split-phase failure.
What happens if the centrifugal switch sticks open?
The starting winding never connects, so the motor hums at standstill and will not start — but it will run if spun by hand
Question Explanation:
A stuck-open centrifugal switch means the starting winding never connects, so the motor has no starting torque. It hums at standstill and will not start — but it will run if you spin it by hand.
In the worked example, what happens step by step when a split-phase fan motor is switched on?
Both windings energize and the field appears to rotate, the rotor accelerates, the switch opens at 70–80% speed, and the motor runs on the main winding alone
Question Explanation:
Step 1 — both windings energized, currents out of phase, field appears to rotate, starting torque appears. Step 2 — the rotor accelerates. Step 3 — at about 70–80% of synchronous speed the centrifugal switch opens and the starting winding drops out. Step 4 — the motor runs on the main winding alone at a few percent slip.
How is a split-phase motor's direction of rotation changed?
By swapping the starting winding leads relative to the main winding
Question Explanation:
A split-phase motor's direction is set by which way the starting winding is connected relative to the main winding. Swap the starting winding leads and the motor runs the other way.
Where are single-phase induction motors used?
Very small jobs — household appliances, fans, buffers, and small commercial equipment on single-phase supplies
Question Explanation:
Single-phase induction motors are for very small commercial applications such as household appliances and fans and buffers — anywhere only a single-phase supply is available and the power needed is small. They are not used for heavy industrial work: their starting torque is modest and their efficiency is lower than a three-phase motor's.
- Tags: