What you’ll learn
After this post, you will be able to explain why a synchronous motor cannot start on its own, how it is brought up to speed, what pull-in and pull-out torque mean, and what the torque angle is.
A motor that runs at exactly field speed — but cannot start
An induction motor’s rotor chases the rotating field and never catches it. A synchronous motor does the opposite: its rotor locks onto the rotating field and runs at exactly synchronous speed — no slip at all. That sounds better, and in some ways it is: exact speed, no slip, and (as the next post shows) the ability to fix a factory’s power factor. But it comes with a catch that defines the whole machine: a synchronous motor has no starting torque. Switch it on at standstill and it just sits there, humming, while the field sweeps past it. It cannot start itself.
Why no starting torque?
The synchronous motor’s rotor is not a cage of bars — it is an electromagnet, excited by a separate DC source through slip rings and brushes. Torque only develops when the rotor’s magnetic poles lock into step with the rotating stator field, pole to pole. At standstill the stator field is sweeping past the rotor at full synchronous speed — 3,600 rpm for a 2-pole 60 Hz machine — alternating between pulling the rotor forward and pushing it backward thousands of times a second. The pushes and pulls average to zero. The rotor cannot catch a field moving that fast from rest, so no torque develops. Torque exists only at synchronous speed — which is exactly the speed the motor cannot reach on its own.
How it is started: two ways up to speed
The rotor must be brought up to synchronous speed by something else, and then the DC excitation is applied and the rotor pulls into step:
- A pony motor: a small DC motor on the same shaft spins the synchronous motor up to synchronous speed. AC is then applied to the stator, and the DC machine becomes a DC generator, supplying the rotor’s field excitation. Load is applied only after the motor is in step.
- A squirrel-cage starting winding (the usual way): a squirrel-cage winding is embedded in the face of the rotor poles. With the DC excitation off, the motor starts as an induction motor, accelerating on its cage winding to about 95% of synchronous speed. Then DC is applied to the field, and the rotor pulls into synchronism. The torque needed to pull it into step at that moment is the pull-in torque — if the load is too heavy, the rotor cannot pull in and the motor will not synchronize.
Locked in step: the torque angle
Once running, the rotor is locked to the field and turns at exactly synchronous speed, whatever the load (until it is overloaded). What changes with load is not the speed but the torque angle (α) — the angle between the centre line of a rotating-field pole and the centre line of a rotor DC-field pole. At no load the two poles line up (α = 0). Under load the rotor pole falls behind the stator pole — the angle opens up — while the speed stays exactly synchronous. The more load, the bigger the angle, and the more torque the motor makes. If the load pulls the rotor so far back that the angle reaches about 90°, the poles slip past each other, synchronism is lost, no torque is developed, and the motor stops. The maximum torque the motor can develop without losing synchronism is the pull-out torque. Unlike an induction motor, which slows and stalls, a synchronous motor that is overloaded simply falls out of step and stops.
The worked example: starting a synchronous motor, step by step
Take a synchronous motor with a squirrel-cage starting winding, driving a large fan. Step 1 — start: with the DC field off, AC is applied to the stator and the motor accelerates as an induction motor on its cage winding, up to about 95% of synchronous speed. Step 2 — pull-in: DC is applied to the rotor field. The rotor poles snap into step with the rotating field — the pull-in torque does the work of locking them together. Step 3 — running: the motor turns at exactly synchronous speed (1,800 rpm for a 4-pole 60 Hz machine), the torque angle sitting at whatever value the fan load needs. Step 4 — overload: if the fan load grows until the torque angle approaches 90°, the motor pulls out of synchronism and stops dead, rather than slowing down. The operator must reduce the load and restart it from the beginning.
Common mistakes
- “A synchronous motor starts like an induction motor.” It does not — it has no starting torque and needs a starting device (a pony motor or a cage winding) to bring it to speed first.
- “A synchronous motor has slip.” It does not — it runs at exactly synchronous speed, with zero slip. Slip belongs to induction motors.
- “Pull-in torque and pull-out torque are the same.” They are not. Pull-in torque is the torque needed to pull the rotor into synchronism when the DC field is applied (at about 95% speed). Pull-out torque is the maximum torque the motor can develop without losing synchronism once it is running.
- “The rotor slows down under load, like an induction motor.” It does not — the speed stays exactly synchronous. What changes is the torque angle: the rotor pole falls further behind the stator pole as the load grows.
- “If it is overloaded it stalls slowly.” It does not — it falls out of step and stops. There is no graceful slow-down.
- “The rotor needs no DC supply.” It does — the rotor is excited by an external DC source through slip rings and brushes. Without excitation there is no rotor field to lock to the stator field.
- “Synchronous speed is approximate.” It is exact — the rotor is locked to the field, so its speed is the synchronous speed, set by frequency and poles: N_S = 120f / P.
Summary
A synchronous motor’s rotor is a DC electromagnet that locks onto the rotating stator field and runs at exactly synchronous speed — no slip, no speed change with load. But torque only exists at synchronous speed, so the motor cannot start itself: it must be brought to about 95% speed by a pony motor or by a squirrel-cage winding in the rotor poles, and then the DC field is applied and the pull-in torque locks it into step. Under load the speed never changes — the torque angle opens up instead — until the angle reaches about 90°, when the motor pulls out of synchronism and stops. Pull-in gets it into step; pull-out is the most it can hold.
Quick-check questions
- Why does a synchronous motor have no starting torque?
- What are the two ways to start a synchronous motor?
- What is pull-in torque?
- What is the torque angle, and what happens when it reaches about 90°?
- How does a synchronous motor’s speed behave under load?
Answers: 1. Torque only develops when the rotor locks into step with the rotating field, and at standstill the field sweeps past the rotor so fast that the pushes and pulls average to zero. 2. A DC pony motor on the same shaft brings it to synchronous speed, or (more commonly) a squirrel-cage winding in the rotor poles starts it as an induction motor to about 95% of synchronous speed, then DC is applied. 3. The torque needed to pull the rotor into synchronism when the DC field is applied. 4. The angle between a rotating-field pole and a rotor DC-field pole; it opens up as load grows, and at about 90° the motor loses synchronism and stops. The maximum torque before that is the pull-out torque. 5. It stays exactly at synchronous speed — the speed never changes with load; only the torque angle changes.
Based on DOE-HDBK-1011/92, Electrical Science, Module 12, paraphrased for study.
Top 10 Scorers
| Pos. | Name | Score | Duration |
|---|---|---|---|
| There is no data yet |
How is a synchronous motor different from an induction motor in speed?
A synchronous motor runs at exactly synchronous speed with no slip; an induction motor always runs a little slower than the field
Question Explanation:
A synchronous motor's rotor locks into step with the rotating field and runs at synchronous speed — no slip at all. An induction motor's rotor chases the field and always runs a little slower (slip).
Why does a synchronous motor have no starting torque?
Torque only develops when the rotor locks into step with the rotating field, and at standstill the field sweeps past so fast the pushes and pulls average to zero
Question Explanation:
Torque is only developed when running at synchronous speed, so a synchronous motor is not self-starting. At standstill the stator field sweeps past the rotor at full synchronous speed, alternating between pulling forward and pushing backward, averaging to zero.
What is the synchronous motor's rotor, and how is it excited?
An electromagnet excited by an external DC source through slip rings and brushes
Question Explanation:
A synchronous motor's stator produces the same rotating field as an induction motor's, but its rotor is an electromagnet fed from an external DC source through slip rings and brushes. That DC excitation is what lets the rotor lock to the field.
What is the pony-motor starting method?
A small DC motor on the same shaft brings the synchronous motor to synchronous speed; AC is then applied, and the DC machine becomes a generator supplying the rotor field
Question Explanation:
A DC motor on a common shaft brings the synchronous motor to synchronous speed, AC is then applied to the stator, and the DC machine becomes a DC generator supplying rotor field excitation, after which load is applied.
What is the more common starting method for a synchronous motor?
A squirrel-cage winding embedded in the face of the rotor poles starts it as an induction motor to about 95% of synchronous speed, then DC is applied
Question Explanation:
More commonly, a squirrel-cage winding embedded in the face of the rotor poles starts the synchronous motor as an induction motor to about 95% of synchronous speed, then DC is applied and it pulls into synchronism.
What is pull-in torque?
The torque needed to pull the rotor into synchronism when the DC field is applied
Question Explanation:
The torque needed to pull the rotor into synchronism when the DC field is applied is the pull-in torque. If the load is too heavy, the rotor cannot pull in and the motor will not synchronize.
What is the torque angle (α)?
The angle between the centre line of a rotating-field pole and the centre line of a rotor DC-field pole
Question Explanation:
The torque angle α is the angle between rotor and stator poles. At no load the centre lines of a rotating-field pole and a DC field pole coincide; under load the rotor pole shifts backward relative to the stator pole with no change in speed.
What happens when the torque angle reaches about 90°?
The motor loses synchronism — the poles slip past each other, no torque is developed, and the motor stops
Question Explanation:
If load pulls the rotor out of synchronism (α ≈ 90°), the motor stops; the maximum torque it can develop without losing synchronism is the pull-out torque. Unlike an induction motor, which slows and stalls, a synchronous motor that is overloaded simply falls out of step and stops.
What is pull-out torque?
The maximum torque the motor can develop without losing synchronism
Question Explanation:
The maximum torque a synchronous motor can develop without losing synchronism is the pull-out torque. If the load exceeds it, the torque angle reaches about 90° and the motor stops.
How does a synchronous motor's speed behave under load?
It stays exactly at synchronous speed — only the torque angle changes
Question Explanation:
Once running, the rotor is locked to the field and turns at exactly synchronous speed, whatever the load (until it is overloaded). What changes with load is the torque angle — the rotor pole falls behind the stator pole while the speed stays exactly synchronous.