What you’ll learn
After this post, you will be able to define magnetic flux, magnetic flux density, weber, permeability, magnetomotive force (mmf), ampere-turns, field intensity, and reluctance, and describe ferromagnetic, paramagnetic, and diamagnetic materials as they relate to permeability, with an example and approximate relative permeability for each.
Magnetism is the other half of electricity
Electricity and magnetism are not two separate subjects. Current makes a magnetic field, and a changing magnetic field makes voltage. Every motor, generator, and transformer you will meet later is built on this chapter. Learn its vocabulary now, and those machines will make sense when you get to them.
What makes a magnet?
Magnetism is the property of certain metals and metallic oxides to attract other metals. Magnets can be natural or manufactured. The handbook’s root cause is simple to picture: electrons spinning on their own axis around the nucleus. In magnetic materials, atoms form domains whose electrons tend to spin in the same direction. When those domains line up, you get north and south poles. The law of magnetism is like the law of electrostatics, with poles instead of charges: like poles repel, unlike poles attract.
Magnetic flux and flux density
Magnetic flux, given the symbol Φ (phi), is the group of magnetic field lines emitted outward from the north pole of a magnet. Its SI unit is the weber (Wb). 1 weber = 1 × 10^8 magnetic field lines. Magnetic flux density, B, is flux per unit area, measured perpendicular to the direction of the flux. Its SI unit is the weber per square metre, called the tesla (T). Formula: B = Φ / A, where B is in teslas, Φ is in webers, and A is area in square metres. Worked examples from the handbook: 5,000 field lines divided by 1 × 10^8 lines per weber equals 50 microwebers. And a flux of 800 microwebers over an area of 4 × 10^-4 square metres gives B = 2 teslas. Note: the handbook first prints that area as 0.004 square metres, but its solution uses 4 × 10^-4 square metres, giving 2 teslas, not 0.2 — use the solution’s area.
Permanent magnets, temporary magnets, and permeability
A hard material, such as cobalt steel, retains its magnetism after the magnetising field is removed — a permanent magnet. A temporary magnet does not. Permeability, μ, is the ability of a material to concentrate magnetic lines of flux. A material that is easily magnetised has high permeability. Relative permeability, μR, is the permeability of a material divided by the permeability of a vacuum, μ0 = 4π × 10^-7 henries per metre. Formula: μR = μ / μ0.
Three kinds of magnetic material
- Ferromagnetic: iron, steel, nickel, cobalt, alnico, and peralloy. These are strongly magnetic. Ferrites, ceramic materials with the ferromagnetic properties of iron, have a relative permeability of about 50 to 200 and are used in radio-frequency transformer coils.
- Paramagnetic: aluminium, platinum, manganese, and chromium. Their relative permeability is slightly more than 1.
- Diamagnetic: bismuth, antimony, copper, zinc, mercury, gold, and silver. Their relative permeability is less than 1.
Electromagnetism: current makes a field
In 1819, Oersted showed that current through a conductor produces a magnetic field around it. Bend the conductor into a loop, and the field lines concentrate inside the loop, all aiding in the same direction. Several loops make a coil. Put an iron core inside the coil, and the flux density increases. The core’s polarity is the coil’s polarity. The left-hand rule for a single conductor relates the direction of current to the direction of the field lines, and the left-hand rule for coils gives the polarity of the coil and of an electromagnet. The handbook states current flow here in the electron-flow convention, from the negative terminal, through the coil, to the positive terminal.
Magnetomotive force, field intensity, and reluctance
Magnetomotive force, mmf, written Fm, is the strength of the magnetic field in a coil. It depends on current and on the number of turns, and it is expressed in ampere-turns (At). Formula: Fm = N × I, where N is turns and I is current in amperes. Worked example: N = 1,000 turns, I = 5 milliamperes, so Fm = 5 ampere-turns. Field intensity, H, is mmf per unit length of coil. Stretch a coil to twice its length, and H halves at the same ampere-turns. Formula: H = Fm / L = NI / L, where H is in ampere-turns per metre and L is the length between the poles in metres. Worked examples: an 80-turn, 20-centimetre coil at 6 amperes gives NI = 480 ampere-turns and H = 2,400 ampere-turns per metre. Stretched to 40 centimetres, H falls to 1,200 ampere-turns per metre. The same coil wound on a 40-centimetre iron core also gives 1,200 ampere-turns per metre — teaching that H depends on length, not on the core material. Reluctance, written as a script R, is the opposition to the production of flux — the magnetic analogue of resistance. It is measured in ampere-turns per weber (At/Wb). It is inversely proportional to permeability: iron cores, with high permeability, have low reluctance; air, with low permeability, has high reluctance. An air gap, the air space between poles, dominates a magnetic circuit: a shorter gap gives a stronger field in the gap, because air will not concentrate the lines and a larger gap only lets them spread. Formula: R = mmf / Φ.
Common mistakes
- “Flux and flux density are the same thing.” They are not. Flux is the total field, in webers. Flux density is how concentrated it is, in teslas — flux divided by area.
- “A bigger coil always means a stronger field.” Not by itself. Field intensity depends on ampere-turns divided by length. Stretch the coil and H falls, even with the same turns and current.
- “Air is just empty space, so it does not matter.” In a magnetic circuit it matters most. Air has high reluctance, so an air gap weakens the field and dominates the circuit.
- “Paramagnetic and diamagnetic mean the same thing.” They are opposites in effect: paramagnetic materials have a relative permeability slightly above 1, diamagnetic materials slightly below 1.
Summary
Magnetism comes from aligned electron spins forming domains and poles. Flux is the total field in webers, flux density is flux per area in teslas. Permeability says how well a material concentrates flux: ferromagnetic materials are strong, paramagnetic slightly above air, diamagnetic slightly below. Current makes a field, a coil multiplies it by its turns, and magnetomotive force pushes flux through reluctance — iron helps, air fights.
Quick-check questions
- What is magnetic flux, and what is its unit?
- What is the difference between flux and flux density?
- Which material class has a relative permeability slightly less than 1, and give one example?
- A coil has 1,000 turns and carries 5 milliamperes. What is its magnetomotive force?
- Why does an air gap weaken a magnetic circuit?
Answers: 1. Magnetic flux is the group of magnetic field lines emitted from the north pole of a magnet; its unit is the weber. 2. Flux is the total field, in webers; flux density is flux per unit area, in teslas, B = Φ / A. 3. Diamagnetic — examples include copper, gold, silver, bismuth, antimony, zinc, mercury. 4. Fm = N × I = 1,000 × 0.005 = 5 ampere-turns. 5. Air has low permeability and therefore high reluctance, so it opposes the production of flux and lets the field lines spread.
Based on DOE-HDBK-1011/92, Electrical Science, Module 1, paraphrased for study.