What you’ll learn
After this post, you will be able to define magnetic circuit, magnetomotive force (mmf), reluctance, magnetic saturation, and hysteresis, and describe how they relate to flux in a circuit.
A circuit, but for flux
An electric circuit has voltage pushing current through resistance. A magnetic circuit has magnetomotive force pushing flux through reluctance. The two ideas run in parallel, and the handbook uses that parallel throughout this chapter. If you can read Ohm’s Law, you can read a magnetic circuit.
The magnetic circuit law
A magnetic circuit is a complete path for magnetic flux, made of magnetic material — usually iron — with a coil supplying the magnetomotive force. The flux in the circuit depends on the mmf and on the reluctance of the path. Formula: Fm = Φ × R, where Fm is magnetomotive force in ampere-turns, Φ is flux in webers, and R is reluctance in ampere-turns per weber. Rearranged: Φ = Fm / R. This is the magnetic twin of Ohm’s Law, E = I × R. The mmf plays the role of voltage, flux plays the role of current, and reluctance plays the role of resistance. Worked example from the handbook: a coil of 200 turns carrying 2 amperes gives Fm = 400 ampere-turns. If the circuit’s reluctance is 2,000 ampere-turns per weber, the flux is Φ = 400 / 2,000 = 0.2 weber.
Flux density from field intensity
Flux density and field intensity are linked by permeability: B = μ × H, where μ is the permeability of the material. For a material with relative permeability μR, that becomes B = μ0 × μR × H, with μ0 = 4π × 10^-7 henries per metre. The handbook puts it this way: flux density is the total flux divided by cross-sectional area, B = Φ / A, in teslas, while field intensity is the magnetising force, H = (N × I) / l, in ampere-turns per metre. Working through both directions helps: given turns, current, and length, find H; given H and permeability, find B; given core area, find total flux.
Series and parallel magnetic circuits
Like electric circuits, magnetic circuits can be in series or in parallel. In series, the same flux travels through each part of the ring in turn, so the total reluctance is the sum of the individual reluctances — and the mmf drops add the same way voltage drops add. In parallel, the flux splits between branches, and the total mmf is the same across each branch, while flux adds. The handbook works the series case carefully: total reluctance if the overlap, core gap, and the way each section’s B-H position changes the effective reluctance — when a section saturates, it stops behaving like its usual reluctance, which then dominates the circuit behavior.
Saturation: the iron fills up
Increase the magnetising force on an iron core and the flux rises — at first steeply, then more slowly, until the core can take no more. That plateau is saturation: every magnetic domain in the iron is already aligned, so extra H produces almost no extra B. The handbook’s B-H curve shows this clearly — the steep middle section, then the knee, then the flat top. In a saturated circuit, flux becomes almost independent of current. Engineers avoid it or design around it because it makes inductors behave erratically, heats cores, and distorts waveforms. Recognise it in exam questions by the flat top of the B-H curve, and by numbers where raising H gives almost no rise in Φ.
Hysteresis: the iron remembers
Take a core up to saturation, then reduce the magnetising force to zero. The flux does not return to zero — some remains. That leftover flux is called residual magnetism. To bring B back to zero you must apply a reverse magnetising force: the coercive force. Plot this as you reverse and re-reverse the current, and you trace a loop — the hysteresis loop. Its area is proportional to energy lost as heat in one cycle, so it is wider for hard magnetic materials (good permanent magnets, bad cores) and narrower for soft iron (good cores, poor magnets). If a question mentions core loss, ask whether it is hysteresis loss or eddy-current loss — they are different mechanisms.
Common mistakes
- “More turns always means more flux.” Not past saturation. Once the core is saturated, more ampere-turns produce almost no more flux — the B-H curve goes flat.
- “Reluctance is the same as resistance.” It plays the same role in its circuit law, but it is a magnetic property that depends on the material and geometry, not on free electrons.
- “When you switch off the coil, the magnetism disappears.” Not in iron. Residual magnetism stays until a coercive force removes it.
- “An air gap is just empty space.” In a magnetic circuit it is the dominant reluctance. A small gap can set the whole circuit’s behaviour.
Summary
A magnetic circuit follows the same law as an electric one: mmf pushes flux through reluctance, Fm = Φ × R. Permeability links B and H, series and parallel circuits combine reluctances the way resistors combine, saturation caps the flux, and hysteresis leaves a memory in the iron — and a loss every cycle.
Quick-check questions
- What is the magnetic circuit law, and what does each symbol mean?
- A coil of 200 turns carries 2 amperes in a circuit with reluctance 2,000 ampere-turns per weber. What is the flux?
- What is magnetic saturation?
- What is residual magnetism, and what force is needed to remove it?
- Why does an air gap dominate a magnetic circuit?
Answers: 1. Fm = Φ × R: magnetomotive force equals flux times reluctance, the magnetic twin of Ohm’s Law. 2. Φ = Fm / R = 400 / 2,000 = 0.2 weber. 3. All domains aligned; extra H produces almost no extra B. 4. Magnetism left after the magnetising force is removed; coercive force removes it. 5. Air has low permeability, so its reluctance is high; the gap sets the total.
Based on DOE-HDBK-1011/92, Electrical Science, Module 1, paraphrased for study.